LITTELFUSE SL1026

New Improved Littelfuse 1026 maximum duty arrester series
a
b
e
3 ELECTRODE GDT
a=TIP
b=RING
e=GROUND
(centre electrode)
55 KILO AMPS CAPABILITY. (SINGLE SHOT)
40 KILO AMPS CAPABILITY. REPETITIVE
GRAPHICAL SYMBOL
LITTELFUSE MAXIMUM DUTY 3 TERMINAL ARRESTER
TOTALLY NON-RADIOACTIVE, UL RECOGNISED
275V
400V
700V
DC sparkover
(V)
200-350
300-500
490-910
(i)
Impulse sparkover (max)
(V)
800
900
1000
(ii)
(A)
40
40
40
(iii)
(KA)
40
40
40
(iv)
ELECTRICAL CHARACTERISTICS
Alternating discharge current
Impulse discharge current
Insulation resistance
(Ω)
2 x 10
2 x 10
2 x 10
(v)
Capacitance (max)
(pF)
2.5
2.5
2.5
(vi)
Holdover
(V)
150
150
150
(vii)
Gap to gap transfer time
(ns)
100
100
100
(viii)
Voltage colour code
BLACK
YELLOW
RED
Type colour code
BLACK
BLACK
BLACK
55
55
55
Impulse discharge current
Single shot
KA
(i)
End to centre or end to end, measured using a rate of rise of voltage of 100V/s.
(ii)
End to centre, measured using a rate of rise of voltage of 1KV/µsec.
(iii) Measured at 1 sec duration, 5 shots @ 3 min intervals, 50Hz.
(iv) Measured at 8/20µsec, 5 shots each polarity between one end and centre.
(v)
Measured at ± 100V dc.
(vi) Measured at 1 MHz, end to centre.
(vii) Measured using test based on ITU (formally CCITT) K12, section 4.2, test
3, with PS2 set to 0V & PS1 variable.
(viii) Measured using a voltage rising at 1kV/µs (relative to the centre electrode)
applied simultaneously to both end electrodes via separate 1k resistors.
These devices are designed so that the failure mode is most likely to be open circuit
rather than short-circuit. They may be used as a replacement for the 16 series (now
obsolete) to handle higher a.c. fault currents.
ORDERING INFORMATION
SL 1026 –
Voltage
All dimensions in mm
w w w. l i t t e l f u s e . c o m
75