PROTEC 587B162LPE

05064
587B062LPE
thru
Only One Name Means ProTek’Tion™
587B302LPE
LOW PROFILE 240V AC POWER LINE SURGE SUPPRESSOR
APPLICATIONS
✔ Hard Wired Equipment AC Power Protection
✔ Load Side Distribution Systems
✔ Secondary Protection for Light Industrial AC Power
IEC COMPATIBILITY (EN61000-4)
✔ 61000-4-5 (Surge): 1kA, 8/20µs - Level 4(Line-Line)
FEATURES
U.S PATENT 4,563,720
Meets ANSI/IEEE C62.41 Outdoor Requirements
Listed to CSA, File LR65240 (Except 587B302LPE)
Differential Mode Protection
Low Clamping Voltage
Nanosecond Response Time
Long Life and Maintenance Free
Finger Safe Connectors
FIGURE 1
TRANSIENT VOLTAGE THREAT
CONDITION
8
6
Kilovolts
✔
✔
✔
✔
✔
✔
✔
MECHANICAL CHARACTERISTICS
4
2
✔ Plastic Package
✔ Weight: 360 Grams (Approximate)
✔ Flammability Rating UL 94V-0
✔ Device Marking: Part Number, Date Code, Logo, Voltage and Current Rating
0
0
10
20
30
40
50
60
Time - µs
FIGURE 2
TYPICAL CLAMPING ACTION
OF A 15 AMP MODULE
DESCRIPTION
6
4
Kilovolts
The 587B Low Profile (LPE) Series is designed for European applications where no
line to ground or neutral to ground suppression is allowed. These modules employ a
three stage technology proven to be the most cost effective and reliable method in
protecting sensitive electronic equipment from over voltage transients.
2
0
This series is designed to protect AC powered equipment from the 6,000 Volt peak
open circuit voltage and 3,000 Amp short circuit current as defined in ANSI/IEEE
C62.41, Category CI.
The 587BxxxLPE Series offers a high degree of protection against 240 VAC EMI line
noise. It is ideal for protecting 800 Volt components because the solid state TVS
technology assures that the line-to-neutral voltage will not exceed 800 Volts. While
the modules are designed for transient voltage protection, the advanced circuitry will
also attenuate the amplitude and slow the rate of rise of high frequency noise acting
as an EMI filter. The 587BxxxLPE Series includes common mode protection, which
are effective in reducing interference from line to equipment and are effective in
reducing equipment generated noise to meet FCC, VDE and CSA interference
requirements.
05064.R4 12/03
1
0
10
20
30
Time - µs
40
50
60
Figures 1 and 2 are photographs of digitized waveforms
showing the typical clamping action of a 16 ampere module.
A 12 Ohm resistor is used to represent a 10 Amp equipment
load. The load is then subjected to the ANSI/IEEE C62.41
Category CI test conditions (6,000V/3,000A). These photographs contrast the effect on equipment with and without the
protector.
www.protekdevices.com
587B062LPE
thru
587B302LPE
DEVICE CHARACTERISTICS
SPECIFICATIONS @ 25°C
RESPONSE TO TRANSIENT VOLTAGES
MAXIMUM RATINGS
Operating Line Voltage: 240 VAC +10%
Maximum Line Current: 587B062LPE: 5A
587B102LPE: 10A
587B162LPE: 16A
587B302LPE: 30A
Transient Voltage: 6000Vpeak
Transient Current: 3000Apeak
Current Leakage: @ 240 VAC
Line-to-Neutral: 1.0mA
Storage & Operating -40°C to 85°C
Temperature:
(Measured at center of
mounting surface)
CLAMPING
TEST CONDITION
PROTECTION
MODE
MAXIMUM
CLAMPING
VOLTAGE
OPEN CIRCUIT
VOLTAGE
@ 1.2/50 µs
SHORT CIRCUIT
CURRENT
@ 8/20 µs
DIFFERENTIAL
(Line-to-Neutral)
800V
6000V
3000A
COMMON
(Neutral-to-Ground)
(Line-to-Ground)
N/A
N/A
N/A
ARRESTER DEFINITIONS
Clamping Voltage: The clamping voltage of an arrester is the voltage that appears across its terminals during conduction of a transient current.
Standard Wave Form: The waveform of a surge current or voltage is designated by a combination of two numbers. The first number is for the time
of the wave front expressed in microseconds from zero to the peak of the wave. The second number is for the time of the wavetail also expressed in
microseconds from zero to the instant that the wavetail reaches one half of the crest or peak value, i.e., 8/20 µs waveform.
Transient Current: The transient current of an arrestor is the peak surge current which flows through the arrester when voltage clamping occurs.
OPERATION
For maximum effectiveness, the protector should be installed directly after the AC line on/off switch and fuse. This will protect the electronics from
the AC line switch arcing and the severe transients caused by a fuse clearing.
Some heat is produced when operating at full current load, and heat sinking may be required to maintain case temperature below 85°C. The case
temperature is measured at the center of the mounting surface. The unit should not be mounted to a low combusting temperature material such as
wood.
High energy transients will cause a large circulating current in the AC input line (2,500A is possible). To prevent electromagnetic coupling, the AC line
on the input side of the protector must be dressed away from other wiring, magnetic shielding may be required. In addition, the electrical service
must be connected to a low impedance earth ground.
05064.R4 12/03
2
www.protekdevices.com
587B062LPE
thru
587B302LPE
PACKAGE OUTLINE & DIMENSIONS
3.81”
(96.8 mm)
1.63”
(44.14 mm)
1.10”
(27.9 mm)
3.50”
(88.9 mm)
0.586”
(14.43 mm)
2.30”
(58.42 mm)
4.38”
(111.3 mm)
Note: Connector accepts 10-24 gauge wire.
Line 1 Out
Line In
Dia 0.181”
SURGEBUSTER ®
AC LINE
SURGE SUPPRESSOR
587B162LPE
Neutral In
Ground In
Line 2 Out
Neutral 1 Out
Neutral 2 Out
®
240 VAC
50/60 Hz
16A
Ground Out
MADE IN USA
COPYRIGHT © ProTek Devices 2003
SPECIFICATIONS: ProTek reserves the right to change the electrical and or mechanical characteristics described herein
without notice (except JEDEC).
DESIGN CHANGES: ProTek reserves the right to discontinue product lines without notice, and that the final judgement
concerning selection and specifications is the buyer’s and that in furnishing engineering and technical assistance,
ProTek assumes no responsibility with respect to the selection or specifications of such products.
05064.R4 12/03
3
ProTek Devices
2929 South Fair Lane, Tempe, AZ 85282
Tel: 602-431-8101 Fax: 602-431-2288
E-Mail: [email protected]
Web Site: www.protekdevices.com
www.protekdevices.com