ADVANTECH ADAM-6015

ADAM-6015
ADAM-6017
ADAM-6018
ADAM-6015
7-ch Isolated RTD Input Module
8-ch Isolated Analog Input Module
with 2-ch DO
8-ch Isolated Thermocouple Input
Module with 8-ch DO
ADAM-6017
RoHS
COMPLIANT
2002/95/EC
ADAM-6018
RoHS
COMPLIANT
2002/95/EC
RoHS
COMPLIANT
2002/95/EC
Specifications
Specifications
Specifications
Analog Input
Analog Input
Analog Input









Channels
7 (differential)
Input Impedance
> 10 MΩ
Input Connections 2 or 3 wire
Input Type
Pt, Balco and Ni RTD
RTD Types and Temperature Ranges
Pt 100
-50° C ~ 150° C
0° C
~ 100° C
0° C
~ 200° C
0° C
~ 400° C
-200° C ~ 200° C
Pt 1000 -40° C ~ 160° C
Supports both IEC 60751 ITS90 (0.03851 W/W/°C)
and JIS C 1604 (0.03916 W/W/°C)
Balco 500 -30° C ~ 120° C
Ni 518
-80° C ~ 100° C
0° C
~ 100° C
Accuracy
± 0.1 % or better
± 25 ppm/° C
Span Drift
± 6 μV/° C
Zero Drift
Wire Burn-out Detection
 Channels
 Input Impedance
 lnput Type
 lnput Range
 Accuracy
 Span Drift
 Zero Drift
Digital Output
 Channels
2
 Open Collector to 30 V, 100 mA max. load
 Power Dissipation 300 mW for each module
Ordering Information
 ADAM-6017
8-ch Isolated AI with 2-ch
DO Module
Ordering Information
 ADAM-6015
8 (differential)
> 10 MΩ (voltage)
120 Ω (current)
mV, V, mA
±150 mV, ±500 mV, ±1 V
±5 V, ±10 V, 0-20 mA,
4-20 mA
±0.1% or Better (voltage)
±0.2% or Better (current)
±25 ppm/° C
±6 μV/° C
General
 LAN
10/100Base-T(X)
 Power Consumption 2 W @ 24 VDC
 Connectors
1 x RJ-45 (LAN), Plug-in
screw terminal block (I/O
and power)
 Watchdog
System (1.6 second)
and Communication
(programmable)
 Power Input
10 ~ 30 VDC
 Supports Peer-to-Peer




Channels
8 (differential)
Input Impedance
> 10 MΩ
Thermocouple
lnput Type
Thermocouple Type and Range:
J 0
~ 760° C
K 0
~ 1,370° C
T -100 ~ 400° C
E 0
~ 1,000° C
R 500 ~ 1,750° C
S 500 ~ 1,750° C
B 500 ~ 1,800° C
Accuracy
±0.1% or Better
Span Drift
±25 ppm/° C
Zero Drift
±6 μV/° C
Wire Burn-out Detection
Digital Output
 Channels
8
 Open Collector to 30 V, 100 mA max. load
 Power Dissipation 300 mW for each module
Ordering Information
7-ch Isolated RTD Input
Module
Common Specifications




 ADAM-6018
 Supports GCL
 Supports Modbus/TCP, TCP/IP, UDP and
HTTP Protocols
Analog Input




Resolution
Sampling Rate
CMR @ 50/60 Hz NMR @ 50/60 Hz 16-bit
10 sample/second (total)
90 dB
60 dB
Protection
 Over Voltage
±35 VDC
Protection
 Isolation Protection 2,000 VDC
8-ch Isolated
Thermocouple Input w/
8DO
 Built-in TVS/ESD Protection
 Power Reversal Protection
Environment
 Operating
-10 ~ 70° C
Temperature
 Storage Temperature-20 ~ 80° C
 Humidity (Operating)20 ~ 95% RH
(non-condensing)
 Humidity (Storage) 0 ~ 95% RH
(non-condensing)
Online Download www.advantech.com/products