ALLEN-BRADLEY 700S

Contactors & Control Relays
Safety Control Relays
700S-CF
Specifications
Conformity to Standards
IEC 60947-5-1
IEC 60947-5-1 Annex L — Special
Requirements for Mechanically Linked
Contact Elements
EN50011, EN50005, EN50022
UL 508
VDE 0660
Description
Bulletin 700S-CF Safety Control Relays provide mechanically linked,
positively guided contacts, which are required in feedback circuits
for modern safety applications. The positively guided N.C. auxiliary
contacts will not change state if a N.O. contact welds. Consult your
local sales office or price list for pricing information.
Features
• Positively guided/mechanically linked auxiliary contacts
• Front-mounted auxiliary contact:
– Permanently fixed
– Protective cover to prevent manual operation
– Red contact housing for easy identification
– Incorporates IEC 60947-5-1 “Mechanically Linked” symbol
• AC and DC operating coils
• SUVA third-party certification
CSA 22.2 No. 14
Approvals
SUVA Third-Party Certified
CE Certified
CSA Certified
UL Listed (File No. E14840, Guide No. NKCR)
C-Tick not required
Your order must include:
• Catalogue number of the relays required, complete with coil
suffix.
• Catalogue number of adder decks, timers and accessories
required.
• If required, the part number of replacement coils.
9-17
Contactors & Control Relays
Safety Control Relays
700S-CF
Product Selection
Type CF Control Relays — 8-Pole AC Coil Voltage
AC-12
AC-15
Ith [A]
40°C
Connection Diagrams
Contacts
Ie [A]
60°C
24/
48V
Main
Contacts
120V 240V 400V 500V 600V 690V
A1
Auxiliary
Contacts
13
21
33
43
14
22
34
44
13
21
33
43
14
22
34
44
13
21
33
43
14
22
34
44
53
61
71
81
54
62
72
82
53
61
71
83
54
62
72
84
53
61
73
83
54
62
74
84
K1
A2
Main
Contacts
20
20
10
10
10
6
2.5
1
A1
A2
A1
10
6
6
6
5
3
1.6
1
NC
Catalogue
Number !
4
4
700S-CF440⊗C
5
3
700S-CF530⊗C
6
2
700S-CF620⊗C
1
K1
Adder
Deck
Contacts
NO
K1
1
A2
! All Catalogue Numbers are factory-stocked.
⊗
AC Coil Voltage Code
The Catalogue Number is incomplete. Select a coil voltage code from the table below to complete the Catalogue Number. Example: 120V 60 Hz:
Catalogue Number 700S-CF440⊗C becomes Catalogue Number 700S-CF440DC.
Voltage
12
24
32
36
42
50 Hz
R
K
V
W
60 Hz
Q
J
–
V
50/60 Hz
–
KJ
–
–
Voltage
230
230240
50 Hz
–
VA
60 Hz
–
–
50/60 Hz
KF
–
KA
9-18
100110
110
KP
–
D
–
KP
–
KP
–
KD
–
48
100
X
Y
–
X
–
KY
120
208
208240
L
–
–
F
KG
H
L
–
–
–
KL
600
200
P
S
KG
D
–
–
–
KG
KL
277
347
380
380400
400
400415
T
–
–
–
N
–
G
A
T
I
E
–
–
–
–
–
–
–
KN
–
KB
240
200220
127
440
220230
480
500
550
B
–
M
C
–
N
B
–
–
C
–
–
–
–
Contactors & Control Relays
Safety Control Relays
700S-CF
Product Selection
Type CF Control Relays — 8-Pole DC Coil Voltage
AC-12
AC-15
Ith [A]
40°C
Connection Diagrams
Contacts
Ie [A]
60°C
24/
48V
Main
Contacts
120V 240V 400V 500V 600V 690V
A1
Auxiliary
Contacts
13
21
33
43
14
22
34
44
13
21
33
43
14
22
34
44
13
21
33
43
14
22
34
44
53
61
71
81
54
62
72
82
53
61
71
83
54
62
72
84
53
61
73
83
54
62
74
84
K1
A2
Main
Contacts
20
20
10
10
10
6
2.5
1
A1
A2
A1
10
6
6
6
5
3
1.6
NC
Catalogue
Number !
4
4
700S-CF440⊗C
5
3
700S-CF530⊗C
6
2
700S-CF620⊗C
1
K1
Adder
Deck
Contacts
NO
1
1
K1
A2
! All Catalogue Numbers are factory-stocked.
⊗
DC Coil Voltage Code
The Catalogue Number is incomplete. Select a coil voltage code from the table below to complete the Catalogue Number. Example: 24V DC:
Catalogue Number 700S-CF440⊗C becomes Catalogue Number 700S-CF440ZJC.
Voltage
9
12
24
36
48
60
64
72
80
110
115
125
220
230
250
Standard
ZR
ZQ
ZJ
ZW
ZY
ZZ
ZB
ZG
ZE
ZD
ZP
ZS
ZA
ZF
ZT
With diode
suppressor
—
—
DJ
—
—
—
—
—
—
—
—
—
—
—
—
9-19
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
General
Contact Ratings — NEMA
Minimum Contact Rating
Contact Ratings — IEC
AC-15 (solenoids,
contactors) at rated
voltage
Catalogue
Number
700S-CF
A600, P600
A600, Q600
17V
Location of
welded
N.O.
contacts
10 mA
State of N.C. Contacts if N.O. contact welds
Main
Front aux.
Main
Open
Open
Front aux.
Open
Open
24V
10A
6A
48V
10A
6A
Left side
aux.
Open !
Open
120V
240V
10A
10A
6A
5A
Right side
aux.
Open !
Open
400V
6A
3A
480V/500V
40ºC
Yes!
Mechanically Linked Contacts➋
Aux.
Contact
(Frontmounted)
2.5A
1.6A
600V
1A
1A
690V
1A
1A
Ith
20A
10A
AC-12 (Non-inductive, or
230V
8 kW
slightly inductive loads,
400V
14 kW
resistance furnaces)
690V
24 kW
20A
General
Mechanical Life
60º C
Ith
! Side-mounted auxiliary contacts provide “mirror contact” performance.
➋ Defined in IEC 60947-5-1 annex L. Positive guidance is a relationship between
contacts of opposite types (i.e., N.O. and N.C.)
6A
Catalogue
Number
700S-CF
Aux.
Contact
(Frontmntd.)
[Mil]
15
15
Electrical Life
AC-15
(240V, 3A)
[Mil]
1.5
1.5
Weight
AC Op.
Mechanism
[g]
390
–
2 x A4
2 x A4
230V
8 kW
400V
14 kW
Terminal CrossSections
690V
24 kW
Terminal Type
24V
12A
Switching DC Loads
DC-12
L
/R < 1ms, Resistive Loads
12A
48V
9A
9A
110V
3.5A
3.5A
220V
0.55A
0.55A
440V
0.2A
0.2A
DC-14
24V
9A
9A
L
48V
5A
5A
Loads
110V
2A
2A
with economy resistor in
series
220V
0.4A
0.4A
440V
0.16A
0.16A
24V
5A
5A
/R < 15ms, Inductive
DC-13
Switching electromagnets
9-20
48V
3A
3A
110V
1.2A
1.2A
220V
0.6A
0.6A
440V
0.3A
0.15A
Terminal Size
per IEC 60947-1
Flex.
with
Wire
End
Ferrule
1 Conductor
2 Conductor
[mm2]
[mm2]
1…4
1…4
0.5…2.5
0.75…2.5
1 Conductor
2 Conductor
[mm2]
[mm2]
1.5…6
1.5…6
0.5…2.5
0.75…2.5
Max. Wire Size
per UL/CSA
[AWG]
16…10
18…14
Tightening
Torque
[lb-in]
8.9…22
8.9…13.3
Tightening
Torque
[Nm]
1…2.5
1…1.5
Solid
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
General (continued)
General (continued)
Aux.Contact
(Side-mounted)
Contact Ratings — IEC
AC-15 (solenoids, contactors) at rated
voltage
Catalogue Number 700S-CF
Rated Insulation Voltage Ui
120V
6
IEC
690V
240V
5
UL; CSA
600V
400V
3
Rated Impulse Strength Uimp
8 kV
500V
1.6
Ith
10A
Ith
6A
AC
115, 230, 400, 500, 690V
DC-13 (Solenoids and
24V
3A
DC
24, 48, 110, 220, 440V
contactors), IEC60947
48V
1.5A
110V
0.6A
Short-Circuit Protection IEC 1581 Fuse, gG
220V
0.3A
Rated Frequency
440V
0.2A
Ambient Temperature
[AWG]
18…14
[lb-in]
8.9…13.3
IEC 60947
AC-12 (Non-inductive, or
40ºC
slightly inductive loads,
resistance furnaces), IEC60947 60ºC
Max. Wire Size per UL/CSA
High Test Voltage
1 minute (per IEC 947-4)
Rated Voltage Ue
Tightening Torque
Tightening Torque
[Nm]
1…1.5
Catalogue
Number
700S-CF
Operating Voltage
DC!
10A
50/60 Hz, DC
Storage
–55…+80 °C (–67…176 °F)
Operation at nominal current
–25…+60 °C (–13…140 °F)
Conditioned 15% current
reduction after AC-1 at > 60°C
–25…+70 °C (–13…158 °F)
Corrosion Resistance
humid-alternating climate,
cyclic, per IEC 68-2-30 and
DIN 50 016, 56 cycles
Control Circuit
AC 50/60 Hz
2500V
Altitude
2000m above mean sea level,
per IEC 60947-4
Type of Protection
Pick-up
[x Us]
0.85…1.1
Dropout
[x Us]
0.3…0.6
Pick-up
[x Us]
0.8…1.1
Dropout
[x Us]
0.1…0.6
Inrush
[VA/W]
70/50
Seal
[VA/W]
8/2.6
Inrush/Seal
[W]
6.5
Pick-up Time
[ms]
15…30
Dropout Time
[ms]
10…60
Pick-up Time
[ms]
40…70
Dropout Time
[ms]
7…15
IP 2X (IEC 529 and DIN 40050)
Finger Protection
in connected state
safe from touch by fingers and back
of hand per VDE 0106, Part 100
Coil
Consumption
AC 50/60 Hz
DC
Operating Times
AC 50/60 Hz
DC
! For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us.
For 24V DC, code ZJ or DJ, use operating voltage 0.7…1.25 x Us.
9-21
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
Auxiliary Contacts
NO
NC
1
0
Catalogue
Number
100S-C all
700S-CF all
100-SA10
100S-C AC only
700S-CF AC only
100-SA20
100S-C09…C23
700S-CF all➋
100-SB10
100S-C09…C23 AC only
700S-CF AC only➋
100-SB20
-3
-4
-3
-SA10
-3
-4
-4
-3
-3
0
-4
2
-3
-4
Auxiliary Contact Blocks for Side
Mounting without Sequence
Terminal Designations !
• 1- and 2-pole
• Two-way numbering for right or left
mounting on the contactor
• Quick and easy mounting without
tools
• Electronic-compatible contacts down
to 17V, 10mA
For Use With
Catalogue Number
Connection Diagrams
-4
Description
-SA20
1
0
13
44
14
43
-SB10
13
14
24
33
43
0
44
2
23
34
Auxiliary Contact Blocks for Side
Mounting with Sequence Terminal
Designations !
• 1- and 2-pole
• Two-way numbering for right or left
mounting on the contactor
• Quick and easy mounting without
tools
• Electronic compatible contacts down
to 17V, 10mA
• L = Late break/Early make
-SB20
! AC Coils: Max. 2 N.O. auxiliary contacts may be mounted on the side. DC coils: Max. 1 N.O. auxiliary contact may be mounted on the side. No additional N.C. auxiliary
contacts may be added to safety contactors and control relays listed in this publication. For additional contact configurations, consult your local Rockwell Automation/AllenBradley distributor.
➋ Double Numbering — Left-side mounting only is recommended for Catalogue Number 700S-CF… due to double numbering.
Marking Systems
Uniform labelling materials for contactors, motor starting equipment, timing relays and circuit breakers
Package Qty.
Catalogue
Number
Label Sheet
• Sheet with 105 self-adhesive paper labels, 6 x 17 mm
10
100-FMS
Marking Tag Sheet
• Sheet with 160 perforated paper labels, 6 x 17 mm
• To be used with a transparent cover
10
100-FMP
Transparent Cover
• To be used with marking tag sheets
100
100-FMC
System V4/V5
100
100-FMA1
System Bul. 1492W
100
100-FMA2
Description
Marking Tag Adaptors
• 100 each
• To be used with marking tag:
9-22
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
Control Modules
Connection
Diagrams
Description
DC Interface (electronic)
• Interface between the DC control signal (PLC) and the contactor
AC operating mechanism
• Control voltage 18…30V DC (24V DC nominal)
• For coil voltage of 110… 240V AC
• Suitable for all 100S-C contactor sizes, 9…85 A
• Requires no additional surge suppression for the coils
• Power consumption
– 0.1 W at 18V DC
– 0.25 W at 24V DC
– 0.5 W at 30V DC
Surge Suppressors
For limitation of coil
switching transients.
• Plug-in, coil mounted
• Suitable for all 100S-C
contactor sizes, 9…85
A
• RC, Varistor and
Diode Versions
K1M
For Use With
Catalogue
Number
Catalogue
Number
100S-C with AC coils
700S-CF with AC
coils
100-JE
(K1M)
RC Module
AC Operating
Mechanism
24…48V, 50/60 Hz
110…280V, 50/60 Hz
380…480V, 50/60 Hz
100S-C with AC coils
700S-CF with AC
coils
100-FSC48
100-FSC280
100-FSC480
Varistor
Module
AC/DC
Operating
Mechanism
12…55V AC/12…77V DC
56…136V AC /78…180V DC
137…277V AC /181…350V
DC
278…575V AC
100S-C all
700S-CF all
100-FSV55
100-FSV136
100-FSV277
100-FSV575
Diode Module
DC Operating
Mechanism
12…250V DC
100S-C with DC coils
100-FSD250
700S-CF with
DC coils
9-23
Contactors & Control Relays
Safety Control Relays
100-D
Auxiliary Contacts
Description
NO
NC
1
1
2
0
• Side-mounted
• With IEC sequence terminal designations
Connection
Diagrams
53 63
74 84
54 64
73 83
• Electronically compatible auxiliary contacts
• Ideal for use when switching low-power control
circuits
• Contact ratings:
AC-1
250V, 0.1 A
AC-15, DC-13
3…125V, 1…100V,
1
1
For Use with
Catalogue
Number
Catalogue
Number
100-D
Left or right
outside mounting
100-DS2-11
100-D
Left or right
outside mounting
100-DS2-20
100-D
Left or right
outside mounting
100-DS2-B11
Labeling Material
• Uniform labeling materials for contactors, motor protection devices, timing relays, and circuit breakers.
Marking Systems (for 100-D95...D860 contactors)
Package Qty.
Catalogue
Number
Label Sheet
• 10 sheets with 105 self-adhesive paper labels each, 6 x 17mm
10
100-FMS
Marking Tag Sheet
• 10 sheets with 160 perforated paper labels each, 6 x 17mm
• To be used with a transparent cover
10
100-FMP
Transparent Cover
• 100 each
• To be used with marking tag sheets
100
100-FMC
System V4/V5
100
100-FMA1
System Bul. 1492W
100
100-FMA2
Description
Marking Tag Adaptors
• 100 each
• To be used with marking tag:
9-24
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
Auxiliary Contacts
Internal Auxiliary Contacts
Catalogue Numbers
100S-C09...100S-C23
Side-Mounted Auxiliary Contacts
Catalogue Numbers
100-SA, 100-SB, 100-MC
25
10
Current Switching
AC-12 Ith
at 40°C
[A]
at 60°C
[A]
20
[V]
24 48 120 240 400 415 500 690
24 48 120 240 400 415 500 690
[A]
10 10 10 10
6
[V]
24 48 110 220 400
24 48 110 220 400
[A]
5
5
AC-15 at Rated Operating Voltage
DC-13 at Rated Operating Voltage
2
6
6
5
2.5 1
0.7 0.25 0.12
6
2
6
5
3
2.5 1.6 1
0.7 0.25 0.12
Continuous Current Rating per UL/CSA
AC
DC
Short-Circuit Protection
gG Fuse
Type 2 Coordination
Rated Impulse Voltage Uimp
Insulation Voltage (between control and load circuit) per
DIN, VDE 0106, Part 101 (NAMUR recommendation)
[A]
[A]
10A, 600V (NEMA A600)
5A, 600V (NEMA P600)
10A, 600V (NEMA A600)
2.5A, 600V (NEMA Q600)
[A]
10
10
[kV]
8
6
250
500
17V, 10mA
17V, 10mA
Mutually unrestricted between
all N.O. and N.C. contacts
100-SA, 100-SB: Mirror output
performance per IEC60947-4 Annex F
100-MC: Mutually unrestricted
between all N.O. and N.C. contacts
2 x A4
2 x A4
[V]
Contact reliability per DIN 19240 without contamination, normal
industrial atmosphere
Mechanically Linked Contacts per IEC
60947-5-1 Annex L (SUVA Third-party
certified)
Terminals
Terminal Type
Wire Size per IEC 60947-1
Flexible w/Wire-End Ferrule 1 Conductor
[mm2]
1…4
0.5…2.5
2 Conductor
[mm2]
1…4
0.75…2.5
Solid/Stranded Conductor
2
1 Conductor
[mm ]
1.5…6
0.5…2.5
2 Conductor
[mm2]
1.5…6
0.75…2.5
Nm
[AWG]
[lb-in]
1...2.5
16…10
8.9…22
1…1.5
18…14
8.9…13.3
Recommended Tightening Torque (min...max)
Wire Size per UL/CSA
Recommended Tightening Torque (min...max)
9-25
Contactors & Control Relays
Safety Control Relays
100-DS2
Auxiliary Contacts
Side-Mounted Auxiliary Contacts
Catalogue Numbers
100-DS2
Conventional
Electronically Compatible
16
0.1 at 250V
Current Switching
AC-12 Ith
at 40°C
[A]
at 60°C
[A]
AC-15 at Rated Operating Voltage
DC-13 at Rated Operating Voltage
12
[V]
230 240 400 415 500 690
[A]
5.5
[V]
24 48 110 220 440
[A]
5
5
2
3
2.5
1.6
1
1… 100mA
at 3… 125V
0.7 0.25 0.12
Continuous Current Rating per UL/CSA
AC
DC
Short-Circuit Protection
gG Fuse
Type 2 Coordination
Rated Impulse Voltage Uimp
Insulation Voltage (between control and load circuit) per
DIN, VDE 0106, Part 101 (NAMUR recommendation)
[A]
[A]
10A, 600V (NEMA A600)
2.5A, 600V (NEMA Q600)
[A]
10
[kV]
8
—
[V]
Contact reliability per DIN 19240 without contamination, normal
industrial atmosphere
Mechanically Linked Contacts per IEC
60947-5-1 Annex L (SUVA Third-party
certified)
17V, 5mA
17V, 1mA
Mirror contact performance per IEC
60947-4 Annex F
Mirror contact performance per IEC
60947-4 Annex F
2 x A4
2 x A4
Terminals
Terminal Type
Wire Size per IEC 60947-1
Flexible w/Wire-End Ferrule 1 Conductor
[mm2]
1…2.5
1…2.5
2 Conductor
[mm2]
1…2.5
1…2.5
1 Conductor
[mm2]
1… 4
1… 4
2 Conductor
[mm2]
1… 4
1… 4
Nm
[AWG]
[lb-in]
1.4…2.3
16…12
12…20
1.4…2.3
16…12
12…20
Solid/Stranded Conductor
Recommended Tightening Torque (min...max)
Wire Size per UL/CSA
Recommended Tightening Torque (min...max)
9-26
Contactors & Control Relays
Safety Control Relays
100S-C and 700S-CF
Dimensions—mm (inches)
Dimensions are not intended for manufacturing purposes.
Mounting Position
c2
AC Contactors and Control Relays
➊
c1
c
DC Contactors and Control Relays
AC Contactors and Control Relays
a
b
c
c1
c2
∅d
d1
d2
Catalogue Number
45
(1-25/32)
81
(3-3/16)
119.5
(4-3/4)
114.5
(4-43/64)
6
(1/4)
2 - 4.5
(2 - 3/16)
60
(2-23/64)
35
(1-25/64)
100S-C09…100S-C23, 700S-CF
45
(1-25/32)
81
(3-3/16)
136.5
(5-37/64)
131.6
(5-11/32)
6.5
(17/64)
2 - 4.5
(2 - 3/16)
60
(2-23/64)
35
(1-25/64)
100S-C30, 100S-C37
54
(2-1/8)
81
(3-3/16)
139.5
(5-11/16)
134.6
(5-29/64)
6.5
(17/64)
2 - 4.5
(2 - 3/16)
60
(2-23/64)
45
(1-25/32)
100S-C43
72
(2-53/64)
122
(4-51/64)
156
(6-11/32)
150.5
(6-1/8)
8.5
(21/64)
4 - 5.4
(4 - 7/32)
100
(3-15/16)
55
(2-11/64)
100S-C60…100S-C85
c2
∅d
d1
d2
Catalogue Number
DC Contactors and Control Relays
a
b
c
c1
45
(1-25/32)
81
(3-3/16)
145.5
(5-49/64)
140.5
(5-37/64)
6
(1/4)
2 - 4.5
(2 -3/16)
60
(2-23/64)
35
(1-25/64)
100S-C09Z...100S-C16Z, 700SCF
45
(1-25/32)
81
(3-3/16)
162.5
(6-7/16)
158
(6-1/4)
6
(1/4)
2 - 4.5
(2 -3/16)
60
(2-23/64)
35
(1-25/64)
100S-C23Z
45
(1-25/32)
81
(3-3/16)
180.5
(7-5/32)
175.5
(6-61/64)
6.5
(17/64)
2 - 4.5
(2 -3/16)
60
(2-23/64)
35
(1-25/64)
100S-C30...100S-C37
54
(2-1/8)
81
(3-3/16)
183.5
(7-17/64)
179
(7-3/32)
6.5
(17/64)
2 - 4.5
(2 -3/16)
60
(2-23/64)
45
(1-25/32)
100S-C43Z
72
(2-53/64)
122
(4-51/64)
156
(6-11/32)
150.5
(6-1/8)
8.5
(21/64)
4 - 5.4
(4 -7/32)
100
(3-15/16)
55
(2-11/64)
100S-C60D...100S-C85D
Accessories
mm
(inches)
Auxiliary contact block for side mounting 1- or 2-pole
Contactors with
a+9
(a + 23/64)
Electronic Timing Module on coil terminal side
b + 24
(b + 15/16)
Mechanical Interlock on side of contactor
a+9
(a + 23/64)
Interface Module on coil terminal side
b+9
(b + 23/64)
Surge Suppressor on coil terminal side
b+3
(b + 1/8)
Labelling with label sheet
marking tag sheet with clear cover
marking tag adapter for System V4/V5
marking tag adapter for System Bul. 1492W
+0
+0
+ 5.5
+ 5.5
(+ 0)
(+ 0)
(+ 7/32)
(+ 7/32)
9-27
Contactors & Control Relays
Safety Control Relays
100S-D Contactors and Accessories
Dimensions—mm (inches)
Dimensions are not intended for manufacturing purposes.
Mounting Position
e2
c1
e4
e1
➊
e3
b
d1
øe
ød
d2
c
a
Catalogue Number
a
b
c
c1
ød
d1
d2
øe
e1
e2
e3
e4
100S-D95, 100S-D110
120
170
156
110.5
5.2
145
100
M6
16
38.5
147
8
100S-D95-EI…100S-D180-EI, 100S-D140, 100S-D180
120
170
156
110.5
5.2
145
100
M8
20
39
160
10
100S-D210-EI…100S-D420-EI
155
205
180
110.5
6.5
180
130
M10
25
48
193
12.5
100S-D630-EI…100S-D860-EI
255
310
265
110.5
10
230
225
M12
40
70
291
22
Contactor with
[mm]
Auxiliary contact block
100-DS2…
a + 13.5 each
Mechanical interlock
100-DM…
a+a
Frame terminal block
100-DTB110
100-DTB180
100-DTB420
b + 7 each
b + 7 each
b + 8.5 each
Label holder
c…+ 5
➊ Convention DC coil contactors will have an additional auxiliary contact block mounted which will add 13.5mm (0.53in) to the “a” dimension on the right hand side.
9-28