CRYDOM A2490E

Series 1 240 VAC
• Crydom's signature family of solid-state relays. Ratings from 10A to
125A @ 12-280 VAC
• SCR output for heavy industrial loads
• AC or DC control
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
PRODUCT SELECTION
Control Voltage
3-32 VDC
90-280 VAC
18-36 VAC
10A
25A
50A
75A
90A
110A
125A
D2410
A2410
A2410E
D2425
A2425
A2425E
D2450
A2450
A2450E
D2475
A2475
A2475E
D2490
A2490
A2490E
D21110
A24110
A24110E
D24125
A24125
A24125E
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2)
Maximum Load Current (3) [Arms]
Minimum Load Current [mArms]
Maximum Surge Current (16.6ms) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum I2 t for Fusing (8.3 msec) [A2 sec]
Minimum Power Factor (with Maximum Load)
For Contact information visit our web
site.
24-280
600
10
500
10
40
120
1.6
1.48
60
24-280
600
10
500
25
40
250
1.6
1.02
260
24-280
600
10
500
50
40
625
1.6
0.63
1620
24-280
600
10
500
75
40
1000
1.6
0.31
4150
24-280
600
10
500
90
40
1200
1.6
0.28
6000
24-280
600
10
500
110
150
1500
1.7
0.25
9340
24-280
600
10
500
125
150
1750
1.7
0.22
12700
0.5
0.5
0.5
0.5
0.5
0.5
0.5
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.
INPUT SPECIFICATIONS (1)
Description
( D PREFIX)
( A PREFIX)
( E SUFFIX)
3-32 VDC
-32
3.0 VDC
1.0 VDC
3.4-20 mA
1500 Ohm
1/2 Cycle
1/2 Cycle
90-280 Vrms
90 Vrms
10 Vrms
2.0-4.0 mA
60 K Ohm
10
40
18-36 Vrms
18 Vrms
4.0 Vrms
3 mA
9.0 K Ohm
10
40
Control Voltage Range
Maximum Reverse Voltage
Maximum Turn-On Voltage
Minimum Turn-Off Voltage
Typical Input Current
Nominal Input Impedance [Ohms]
Maximum Turn-On Time [msec] (4)
Maximum Turn-Off Time [msec]
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 V DC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Encapsulation
Terminals
Recommended Terminal Screw Torque Range:
Fastons:
Parameters
4000 Vrms
109 Ohm
8 pF
-40 to 80 °C
-40 to 125 °C
3 oz (86.5g)
Thermally conductive Epoxy
Screw and saddle Clamps Furnished, Unmounted
6-32 Screws - 10 in/lbs. 8-32 & 10-32 Screws - 20 in. lbs. (Screws dry without grease)
Single pair (up to 25A) Double pair* (50A model only) *Caution: User must connect to both pairs
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
3) Heat sinking required, for derating curves see page 3.
4) Turn-on time for Random turn-on versions is 0.02 msec (DC Control Models)
For Contact information visit our web
site.
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.
MECHANICAL SPECIFICATIONS
THERMAL DERATE INFORMATION
AGENCY APPROVALS
UL E116949
CSA LR81689
VDE 10143 UG (Not Applicable: -B and 4D)
Rev. 070308
For Contact information visit our web
site.
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.
For Contact information visit our web
site.
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.
ANNEX - ENVIROMENTAL INFORMATION
For Contact information visit our web
site.
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.