CX Series • SIP SSR • Ratings of 5A @ 660 VAC • SCR output for heavy industrial loads • AC or DC control • Zero-crossing (resistive loads) or random-fire (inductive loads) output PRODUCT SELECTION Control Voltage 3-15 VDC 4-15 VDC 15-32 VDC 18-36 VAC 90-140 VAC CX240D5 CX380D5 CXE380D5 CXE240D5 CXE240A5 CX240A5 CX480D5 CXE480D5 AVAILABLE OPTIONS OUTPUT SPECIFICATIONS (1) Description Operating Voltage (47-63Hz) [Vrms] Transient Overvoltage [Vpk] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2) Maximum Load Current [Arms] Minimum Load Current [Arms] Maximum Surge Current (16.6ms) [Apk] Maximum On-State Voltage Drop @ Rated Current [Vpk] Maximum I²t for fusing (8.3 msec) [A² sec] Minimum Power Factor (with Maximum Load) For Contact information visit our web site. 12-280 600 0.1 500 5 0.06 250 1.4 260 0.5 www.crydom.com 48-530 1200 0.1 500 5 0.06 250 1.4 260 0.5 48-660 1200 0.1 500 5 0.06 250 1.4 260 0.5 ©2008 Crydom, Inc. Specifications subject to change without notice. INPUT SPECIFICATIONS (1) Description CX240Dx CX380Dx Nominal Voltage Control Voltage Range Minimum Turn-On Voltage Drop Out Voltage Typical Input Current Nominal Input Impedance Maximum Turn-On Time [msec] (3) Maximum Turn-Off Time [msec] 5 VDC 3-15 VDC 3.0 VDC 1.0 VDC 15 mAdc 300 Ohm 1/2 Cycle 1/2 Cycle 5 VDC 4-15 VDC 4.0 VDC 1.0 VDC 15 mAdc 240 Ohm 1/2 Cycle 1/2 Cycle CXExxxDx 24 VDC 15-32 VDC 15.0 VDC 1.0 VDC 15 mAdc 1500 Ohm 1/2 Cycle 1/2 Cycle CX240A5 120 VAC 90-140 VAC 90.0 Vrms 10.0 Vrms 10 mArms 14.1 Ohm 10 40 CXE240A5 24 VAC 18-36 VAC 18.0 Vrms 2.0 Vrms 10 mArms 2.1 Ohm 10 40 GENERAL SPECIFICATIONS Description Parameters Dielectric Strength, Input/Output/Base (50/60Hz) Minimum Insulation Resistance (@ 500 VDC) 4000 Vrms 10 9 Ohm Maximum Capacitance, Input/Output Ambient Operating Temperature Range Ambient Storage Temperature Range Weight (typical) Encapsulation 10 pF -30 to 80 °C -30 to 125 °C 0.4 oz. (11g) Therminally Conductive Epoxy GENERAL NOTES 1) All parameters at 25°C unless otherwise specified. 2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 3) Turn-On time for random turn-on versions is 0.1 msec (DC Control Models). MECHANICAL SPECIFICATIONS DC CONTROL. PIN 1: AC LOAD PIN 2: AC LOAD PIN 3: +DC CONTROL PIN 4: -DC CONTROL AC CONTROL. PIN 1: AC LOAD PIN 2: AC LOAD PIN 3: AC CONTR OL PIN 4: AC CONTR OL AGENCY APPROVALS UL E116949 CSA LR81689 VD E 70938 UG(240 V, 380V, DC Control Only) VG (240 V, 380 V, DC Control Only) Rev. 06132008 For Contact information visit our web site. www.crydom.com ©2008 Crydom, Inc. Specifications subject to change without notice. For Contact information visit our web site. www.crydom.com ©2008 Crydom, Inc. Specifications subject to change without notice. ANNEX - ENVIROMENTAL INFORMATION For Contact information visit our web site. www.crydom.com ©2008 Crydom, Inc. Specifications subject to change without notice.