CRYDOM CX380D5R

CX Series
• SIP SSR
• Ratings of 5A @ 660 VAC
• SCR output for heavy industrial loads
• AC or DC control
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
PRODUCT SELECTION
Control Voltage
3-15 VDC
4-15 VDC
15-32 VDC
18-36 VAC
90-140 VAC
CX240D5
CX380D5
CXE380D5
CXE240D5
CXE240A5
CX240A5
CX480D5
CXE480D5
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2)
Maximum Load Current [Arms]
Minimum Load Current [Arms]
Maximum Surge Current (16.6ms) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum I²t for fusing (8.3 msec) [A² sec]
Minimum Power Factor (with Maximum Load)
For Contact information visit our web
site.
12-280
600
0.1
500
5
0.06
250
1.4
260
0.5
www.crydom.com
48-530
1200
0.1
500
5
0.06
250
1.4
260
0.5
48-660
1200
0.1
500
5
0.06
250
1.4
260
0.5
©2008 Crydom, Inc.
Specifications subject to change without notice.
INPUT SPECIFICATIONS (1)
Description
CX240Dx
CX380Dx
Nominal Voltage
Control Voltage Range
Minimum Turn-On Voltage
Drop Out Voltage
Typical Input Current
Nominal Input Impedance
Maximum Turn-On Time [msec] (3)
Maximum Turn-Off Time [msec]
5 VDC
3-15 VDC
3.0 VDC
1.0 VDC
15 mAdc
300 Ohm
1/2 Cycle
1/2 Cycle
5 VDC
4-15 VDC
4.0 VDC
1.0 VDC
15 mAdc
240 Ohm
1/2 Cycle
1/2 Cycle
CXExxxDx
24 VDC
15-32 VDC
15.0 VDC
1.0 VDC
15 mAdc
1500 Ohm
1/2 Cycle
1/2 Cycle
CX240A5
120 VAC
90-140 VAC
90.0 Vrms
10.0 Vrms
10 mArms
14.1 Ohm
10
40
CXE240A5
24 VAC
18-36 VAC
18.0 Vrms
2.0 Vrms
10 mArms
2.1 Ohm
10
40
GENERAL SPECIFICATIONS
Description
Parameters
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 VDC)
4000 Vrms
10 9 Ohm
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Encapsulation
10 pF
-30 to 80 °C
-30 to 125 °C
0.4 oz. (11g)
Therminally Conductive Epoxy
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
3) Turn-On time for random turn-on versions is 0.1 msec (DC Control Models).
MECHANICAL SPECIFICATIONS
DC CONTROL.
PIN 1: AC LOAD
PIN 2: AC LOAD
PIN 3: +DC CONTROL
PIN 4: -DC CONTROL
AC CONTROL.
PIN 1: AC LOAD
PIN 2: AC LOAD
PIN 3: AC CONTR OL
PIN 4: AC CONTR OL
AGENCY APPROVALS
UL E116949
CSA LR81689
VD E 70938 UG(240 V, 380V, DC Control Only)
VG (240 V, 380 V, DC Control Only)
Rev. 06132008
For Contact information visit our web
site.
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.
For Contact information visit our web
site.
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.
ANNEX - ENVIROMENTAL INFORMATION
For Contact information visit our web
site.
www.crydom.com
©2008 Crydom, Inc.
Specifications subject to change without notice.