Green Power Solutions srl Via Greto di Cornigliano 6R - 16152 Genova , Italy Phone: +39-010-659 1869 Fax: +39-010-659 1870 Web: www.gpsemi.it E-mail: [email protected] GOX80580 DOUBLE STAR AC-DC CONVERTER Over temperature switches Fan loss detection circuit Snubber for SCR's protections Extractible devices for easy field service LINE VOLTAGE UP TO 50V DC OUTPUT CURRENT 8000 A GOX80580 50 V Line to line voltage Characteristic Conditions Value IDC DC output current 8000 A VINS (rms) Insulation voltage 1000 V THYRISTOR CHARACTERISTICS VGT Gate trigger voltage Tj = 25 °C, VD = 5 V 3 V IGT Gate trigger current Tj = 25 °C, VD = 5 V 400 mA dV/dt Critical rate of rise off-state voltage Tj= 125 °C VRRM Blocking Voltage Tj = 125 °C 1000 V/us 200 V MECHANICAL AND THERMAL CHARACTERISTICS Width 950 mm Depth 470 mm Height 1265 mm Mass 250 kg Ta max Max amb. op. Temp. 40 °C Tstg Storage temperature -40/60 °C Document GOX80580T001 DOUBLE STAR AC-DC CONVERTER GOX80580 The part numbering system is reported at the beginning of the Open Assembly section. Customisations are available on request. Please contact factory. In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet without notice. Document GOX80580T001 GOX80580 DOUBLE STAR AC-DC CONVERTER DC1 T1 DC2 T2 T3 R1 T4 R2 T5 DC3 T6 T7 S1 T8 S2 T9 T10 T1 T11 T12 T2 TH1 TH2 TH3 Thermoswitch Thermoswitch Thermoswitch 61 62 FB1 -+ + Single Phase Fan Single Phase Fan Fan Board NO COMNC ACAC 31 32 U3 P3 V3 Cooling: Fan type: Number of fans: Voltage: Current: Frequency: Noise: single phase radial 2 230 V 1 A (each) 50/60 Hz 77 dBA In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet without notice. Document GOX80580T001