MTU 3250

A tognum Group Brand
DIESEL ENGINE-GENERATOR SET
3250-XC6DT2
3250 ekW 60 Hz Standby
/ / 2800 ekW / 60 Hz / Prime
480 - 13.8kV
System Ratings
Standby
Voltage (L-L) Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
480V
3
0.8
60
3250
4062.5
4887
600V
3
0.8
60
3250
4062.5
3909
4160V
3
0.8
60
3250
4062.5
564
12470V
3
0.8
60
3200
4000
185
13200V
3
0.8
60
3200
4000
175
13800V
3
0.8
60
3200
4000
167
C/F
C/F
130°C/27°C
6 LEAD WYE C/F
C/F
125°C/40°C
6 LEAD WYE C/F
C/F
130°C/27°C
6 LEAD WYE C/F
C/F
130°C/27°C
6 LEAD WYE C/F
C/F
130°C/27°C
6 LEAD WYE C/F
C/F
130°C/27°C
6 LEAD WYE
480V
3
0.8
60
2800
3500
4210
600V**
3
0.8
60
2800
3500
3368
4160V
3
0.8
60
2800
3500
486
12470V
3
0.8
60
2750
3437.5
159
13200V
3
0.8
60
2750
3437.5
150
13800V
3
0.8
60
2750
3437.5
144
C/F
C/F
105°C/40°C
6 LEAD WYE C/F
C/F
105°C/40°C
6 LEAD WYE C/F
C/F
105°C/40°C
6 LEAD WYE C/F
C/F
105°C/40°C
6 LEAD WYE C/F
C/F
105°C/40°C
6 LEAD WYE C/F
C/F
105°C/40°C
6 LEAD WYE
Prime
Voltage (L-L) Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
2
/ // /
3250-XC6DT2
Facts
// // // // // // // // EPA Tier 2 Certified
Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
CSA Listing Offered
All engine-generator sets are prototype and factory tested
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
20V4000 G83L Diesel Engine
- 95.4 Liter Displacement
- Common Rail Injection
- 4-Cycle
// // // // Complete Range of Accessories
Permanent Magnet Generator (PMG)
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
Digital Control Panel(s)
- UL Recognized,
, NFPA 110
- Complete System Metering
- LCD Display
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
STANDARD EQUIPMENT
// Engine
Air Cleaners
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Inter Cooler Water Pump
Thermostats
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electric Isochronous
Base - Structural Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
to 10 seconds
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
2 Bearings, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±.25% Voltage Regulation
3% Maximum Harmonic Content
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible
3
/ // /
3250-XC6DT2
Application data
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
// 103 (390)
54.2 (205)
14.5 (55)
231 (873)
Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
// MTU Detroit Diesel
20V4000 G83L
4-Cycle
20-V
5,822 (95.4)
6.69 (17)
8.27 (21)
16.5:1
1,800
ADEC
4,678 (3,490)
4,035 (3,010)
±.25%
60 Hz
Dry
Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
After Cooler Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
// // 24
3,000
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
// STANDBY
237 (897)
192 (727)
133 (504)
PRIME
200 (757)
149 (564)
103 (390)
Cooling - Radiator System
STANDBY
PRIME
Ambient Capacity of Radiator: °F (°C)
108 (42)
108 (42)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa) 0.5 (0.12)
0.5 (0.12)
Water Pump Capacity: gpm (lit/min)
440 (1,667) 440 (1,667)
After Cooler Pump
Capacity: gpm (lit/min)
163 (617)
163 (617)
Heat Rejection to Coolant: BTUM (kW) 83,030 (1,460) 67,675 (1,190)
Heat Rejection to After Cooler: BTUM (kW) 61,988 (1,090) 51,183 (900)
Heat Radiated to Ambient: BTUM (kW)
13,472 (237) 12,434 (218.6)
// Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
STANDBY
9,111 (258)
PRIME
8,687 (246)
135,369 (3,833) 135,369 (3,833)
30,384 (866) 28,431 (810)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
Fuel System
// Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Fuel Consumption
1” NPT
1” NPT
3 (1)
Diesel #2
349 (1,320)
Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
STANDBY
1,013 (545)
PRIME
914 (490)
26,062 (738) 22,884 (648)
34.1 (8.5)
34.1 (8.5)
4
/ // /
3250-XC6DT2
Weights and dimensions
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
SystemDimensions (L x W x H)
OPU
306.38 x 114.13 x 130.5 in (7,780 x 2,900 x 3,310 mm)
Weight (less tank)
63,264 lb (28,696 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Sound data
Unit Type
OPU w/Critical Grade Muffler (dBA)
Standby Full Load
108
Standby No Load
100
Prime Full Load
106.5
Prime No Load
100
Measurements for sound data are taken at 23 ft (7 m).
NOx + NMHC
4.19
CO
0.82
Rating Definitions and conditions
PM
0.14
All units are in g/hp-hr and are EPA D2 cycle values.
Emission levels of the engine may vary as a function of ambient temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one engine
representing this rating. The data was obtained under controlled environmental conditions with calibrated instrumentation
traceable to the United States National Bureau of Standards
and in compliance with US EPA regulations found within 40 CFR
Part 89. The weighted cycle value from each engine is guaranteed to be below the US EPA Standards at the US EPA defined
conditions.
// // // // Materials and specifications subject to change without notice.
Ambient capability factor at 984 ft (300 m). Consult your
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO-8528/1, overload power in accordance
with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For
limited running time and base load ratings, consult the
factory.
Deration Factor:
Altitude: No power decrease with increased elevation up
to 4,921 ft (1,500 m) at 77°F (25°C). Max permissable
elevation is 5,905 ft (1,800 m). Consult factory for altitudes
between 4,921 ft (1,500 m) and 5,905 ft (1,800 m).
Temperature: No power decrease with increased intake combustion temperature up to 107°F (42°C) at 328 ft (100 m).
Consult factory for performance at higher temperatures.
// Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 /
Fax +49 7541 90 7084 / [email protected] // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore /
Phone + 65 6861 5922 / Fax + 65 6861 3615 / [email protected] // USA / Canada / Mexico / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota
56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / [email protected] // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich /
Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / [email protected] //www.mtu-online.com
© MTU Onsite Energy. Subject to alteration due to technological advances. 2009-05
Emissions data