A tognum Group Brand DIESEL ENGINE-GENERATOR SET 400-XC6DT3 400 ekW 60 Hz Standby / / 340 ekW / 60 Hz / Prime 208 - 4160V System Ratings Standby Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 400 400 1667 208V** 3 0.8 60 400 500 1388 240V** 3 0.8 60 400 500 1203 480V** 3 0.8 60 400 500 601 600V** 3 0.8 60 400 500 481 4160V 3 0.8 60 400 500 69 700 573RSL4035 130°C/27°C 820 433CSL6220 130°C/27°C 820 433CSL6220 130°C/27°C 12 LEAD ZIG-ZAG 12 LEAD LOW WYE 12 LEAD HI DELTA 1100 433CSL6220 130°C/27°C 12 LEAD HI WYE 1100 433PSL6248 125°C/40°C 4 LEAD WYE 1100 573FSM4352 130°C/27°C 6 LEAD WYE 240V 1 1.0 60 340 340 1417 208V 3 0.8 60 340 425 1180 240V 3 0.8 60 340 425 1022 480V 3 0.8 60 340 425 511 600V 3 0.8 60 340 425 409 4160V 3 0.8 60 340 425 59 700 573RSL4035 105°C/40°C 820 433CSL6220 105°C/40°C 820 433CSL6220 105°C/40°C 12 LEAD ZIG-ZAG 12 LEAD LOW WYE 12 LEAD HI DELTA 1100 433CSL6220 105°C/40°C 12 LEAD HI WYE 1100 433PSL6248 105°C/40°C 4 LEAD WYE 1100 573FSM4352 105°C/40°C 6 LEAD WYE Prime Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection * The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered 2 / // / 400-XC6DT3 Facts // // // // // // // // // // EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and factory tested MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty Custom Design for Any Application Series 60 (6063HV35) Diesel Engine - 14.0 Liter Displacement - Electronic Unit Pump Injection - 4-Cycle // // // // Complete Range of Accessories Permanent Magnet Generator (PMG) - Optional - Brushless, Rotating Field - 300% Short Circuit Capability - 2/3 Pitch Windings Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - LCD Display Cooling System - Integral Set-Mounted - Engine Driven Fan STANDARD EQUIPMENT // Engine Air Cleaners Oil Pump Full Flow Oil Filter Jacket Water Pump Thermostat Exhaust Manifold – Dry Blower Fan & Fan Drive Radiator - Unit Mounted Electric Starting Motor - 24V Governor – Electric Isochronous Base - Formed Steel SAE Flywheel & Bell Housing Charging Alternator - 24V Battery Box & Cables Flexible Fuel Connectors Flexible Exhaust Connection EPA Certified Engine // Generator NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130°C Standby Temperature Rise 1 Bearing, Sealed Flexible Coupling Full Amortisseur Windings 125% Rotor Balancing 3-Phase Voltage Sensing ±1% Voltage Regulation 100% of Rated Load - One Step 3% Maximum Harmonic Content // Digital Control Panel(s) Digital Metering Engine Parameters Generator Protection Functions Engine Protection SAE J1939 Engine ECU Communications Windows-Based Software Multilingual Capability Remote Communications to our RDP-110 Remote Annunciator 16 Programmable Contact Inputs 7 Contact Outputs UL Recognized, , CE Approved Event Recording IP 54 Front Panel Rating with Integrated Gasket NFPA110 Level Compatible 3 / // / 400-XC6DT3 Application data // Engine Manufacturer Model Type Arrangement Displacement: Cu In (lit) Bore: in (cm) Stroke: in (cm) Compression Ratio Rated RPM Engine Governor Max Power: Standby: bhp (kWm) Max Power: Prime: bhp (kWm) Regulation Frequency Air Cleaner // MTU Detroit Diesel Series 60 (6063HV35) 4-Cycle 6-Inline 855 (14) 5.24 (13.3) 6.61 (16.8) 16:1 1,800 DDEC 635 (473) 550 (410) ±.25% 60 Hz Dry Liquid Capacity (Lubrication) Total Oil System: gal (lit) Engine Jacket Water Capacity: gal (lit) System Coolant Capacity: gal (lit) // // Electrical Electric Volts DC Cold Cranking Amps Under 0°F (-17.8°C) At 100% of Power Rating: gal/hr (lit/hr) At 75% of Power Rating: gal/hr( lit/hr) At 50% of Power Rating: gal/hr (lit/hr) // 24 1,155 Fuel System Fuel Supply Connection Size Fuel Return Connection Size Maximum Fuel Lift: ft (m) Recommended Fuel Total Fuel Flow: gal/hr (lit/hr) 1/2” NPT 1/2” NPT 6.7 (2.1) Diesel #2 88.3 (334) PRIME 28.6 (108) 21.4 (81) 14.5 (55) STANDBY 122 (50) PRIME 122 (50) 0.5 (0.12) 96 (363) 8,750 (154) 6,250 (110) 5,778 (102) 0.5 (0.12) 96 (363) 8,100 (142) 4,650 (82) 5,100 (89.7) STANDBY 1,290 (37) PRIME 1,232 (35) Air Requirements Aspirating: *SCFM (m3/min) Air Flow Required for Rad. Cooled Unit: *SCFM (m3/min) Air Flow Required for Heat Exchanger/Remote Rad. based on 25°F Rise: *SCFM (m3/min) 24,657 (698) 24,657 (698) 13,030 (371) 11,501 (328) * Air density = 0.0739 lbm/ft3 (1.184 kg/m3) // // STANDBY 31.9 (121) 24.7 (93) 16.7 (63) Cooling - Radiator System Ambient Capacity of Radiator: °F (°C) Max. Restriction of Cooling Air, Intake, and Discharge Side of Rad.: in. H20 (kPa) Water Pump Capacity: gpm (lit/min) Heat Rejection to Coolant: BTUM (kW) Heat Rejection to Air to Air: BTUM (kW) Heat Radiated to Ambient: BTUM (kW) // 9.5 (36) 6 (23) 42 (159) Fuel Consumption Exhaust System Gas Temp. (Stack): °F (°C) Gas Volume at Stack Temp: CFM (m3/min) Maximum Allowable Back Pressure: in. H20 (kPa) STANDBY 1,025 (552) PRIME 953 (512) 3,594 (101.8) 3,258 (92.3) 40.8 (10.2) 40.8 (10.2) 4 / // / 400-XC6DT3 Weights and dimensions Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design. SystemDimensions (L x W x H) OPU 140 x 57 x 79.6 in (3,556 x 1,446 x 2,022 mm) Weight (less tank) 6,396 lb (2,901 kg) Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set. Sound data Unit Type OPU w/Critical Grade Muffler (dBA) Sound Attenuated Enclosure (dBA) Standby Full Load 96.5 88.5 Standby No Load 89 81 Prime Full Load 95 87 Prime No Load 89 81 Emissions data NOx + NMHC 2.66 CO 0.98 Rating Definitions and conditions PM 0.13 All units are in g/hp-hr and are EPA D2 cycle values. Emission levels of the engine may vary as a function of ambient temperature, barometric pressure, humidity, fuel type and quality, installation parameters, measuring instrumentation, etc. The data provided are laboratory results from one engine representing this rating. The data was obtained under controlled environmental conditions with calibrated instrumentation traceable to the United States National Bureau of Standards and in compliance with US EPA regulations found within 40 CFR Part 89. The weighted cycle value from each engine is guaranteed to be below the US EPA Standards at the US EPA defined conditions. // // // // Ambient capability factor at 984 ft (300 m). Consult your local MTU Onsite Energy Power Generation Distributor for other altitudes. Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running time and base load ratings, consult the factory. Deration Factor: Altitude: 1% per 1,000 ft (305 m) above 600 ft (183 m). Temperature: 1% per 10°F (5.5°C) above 77°F (25°C). Materials and specifications subject to change without notice. // Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 / Fax +49 7541 90 7084 / [email protected] // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore / Phone + 65 6861 5922 / Fax + 65 6861 3615 / [email protected] // USA / Canada / Mexico / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota 56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / [email protected] // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich / Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / [email protected] //www.mtu-online.com © MTU Onsite Energy. Subject to alteration due to technological advances. 2009-05 Measurements for sound data are taken at 23 ft (7 m).