MTU 60-GC6NLT1

A tognum Group Brand
GAS Engine-Generator Set
60-GC6NLT1
60 ekW 60 Hz Standby
/ / 208 - 600V
System Ratings
Standby
Voltage (L-L) Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
240V**
1
1.0
60
208V**
3
0.8
60
240V**
3
0.8
60
480V**
3
0.8
60
600V**
3
0.8
60
229
229
208
180
90
72
55/55
55/55
60/75
60/75
60/75
60/75
250
250
208
180
90
72
60/60
60/60
60/75
60/75
60/75
60/75
127
362CSL1606
130°C/27°C
230
362CSL1615
125°C/40°C
148
361CSL1602
130°C/27°C
148
361CSL1602
130°C/27°C
142
361CSL1601
130°C/27°C
140
361PSL1633
125°C/40°C
12 LEAD ZIG-ZAG
4 LEAD
12 LEAD LOW WYE
12 LEAD HI DELTA
12 LEAD HI WYE
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
Facts
// // // // // // // // // // Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
UL2200, CSA Listing Offered
Accepts Rated Load in One Step Per NFPA 110, Level 1
All engine-generator sets are prototype and factory tested
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
Custom Design for Any Application
5.7 L Engine
- 5.7 Liter Displacement
- 4-Cycle
Integral Vibration Isolators
// // // // Complete Range of Accessories
Permanent Magnet Generator (PMG) - Optional
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
Digital Control Panel(s)
- UL Recognized,
, NFPA 110
- Complete System Metering
- LCD Display
Cooling System
- Integral Set-mounted
- Engine Driven Fan
2
/ // /
60-GC6NLT1
STANDARD EQUIPMENT
// Engine
Air Cleaner
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Thermostat
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electric Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
to 10 seconds
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±1% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible
3
/ // /
60-GC6NLT1
Application data
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Speed Regulation
Frequency
Air Cleaner
// GM
5.7L
4-Cycle
8-V
350 (5.7)
4 (10.2)
3.5 (8.8)
9.4:1
1,800
Bosch
113.2 (84.4)
±1%
60 Hz
Dry
Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
// // Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
At 100% of Power Rating: ft3/hr (m3/hr)
At 75% of Power Rating: ft3/hr (m3/hr)
At 50% of Power Rating: ft3/hr (m3/hr)
// 12
600
Fuel Inlet
Fuel Supply Connection Size
Fuel Supply Pressure: in. H20 (mm H20)
1 1/2” NPT
7–11 (178–279)
122 (50)
0.5 (0.12)
30 (113.6)
3,400 (59.8)
993.2 (17.5)
Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
182.3 (5.2)
7,396 (209.4)
2,240 (63.4)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
// // NG
717 (20.3)
541 (15.3)
376 (10.6)
Cooling - Radiator System
Ambient Capacity of Radiator: °F (°C)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
// 1.3 (4.9)
2.3 (8.7)
6 (22.7)
Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
1,300 (704.4)
588.7 (16.7)
40 (10)
LPG
317 (9)
239 (6.8)
166 (4.7)
4
/ // /
60-GC6NLT1
Weights and dimensions
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
SystemDimensions (L x W x H)
OPU
78 x 34 x 50.25 in (1,981 x 864 x 1,276 mm)
Weight (dry)
1,450 lb (658 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Unit Type
OPU (dBA)
WPE - No Sound Attenuation (dBA)
CQE (dBA)
Standby Full Load
C/F
C/F
C/F
Standby No LoadPrime Full LoadPrime No Load
C/F
C/F
C/F
Measurements for sound data are taken at 23 ft (7m).
Emissions data
Fuel TypeTHC + NOx Natural Gas
10.34
Liquid Propane
12.94
Rating Definitions and conditions
CO
35.82
39.68
All units are in g/hp-hr.
Engine meets 40 CFR Part 60/90 specifications.
Ambient capability factor at 984 ft (300 m). Consult your
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
// Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
// Deration Factor:
Altitude: 3% per 1,000 ft (305 m) above 328 ft (100 m).
Temperature: 1% per 10°F (5.5°C) above 77°F (25°C).
// Materials and specifications subject to change without notice.
// Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 /
Fax +49 7541 90 7084 / [email protected] // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore /
Phone + 65 6861 5922 / Fax + 65 6861 3615 / [email protected] // USA / Canada / Mexico / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota
56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / [email protected] // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich /
Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / [email protected] //www.mtu-online.com
© MTU Onsite Energy. Subject to alteration due to technological advances. 2009-05
Sound data