2C 12 SOLID BC FLEX FLEX
Date:
Fire Alarm/Life Safety Cable
A. CONSTRUCTION
Conductor:
Insulation:
Cable:
Jacket:
Print Legend:
DIAMETERS
#12 AWG Solid Bare Copper
0.081” nom.
0.012” Wall FLEXGUARD*
0.105” nom.
2C @ 4.00” LHL
0.214” nom.
0.015” Wall FLEXGUARD* - Red
0.244" +/- 0.012"
CAROL (R) 12 AWG - - E3532S - - 75C TYPE FPLP E66267-8 (UL) - - MADE IN USA (DATE
CODE & SEQUENTIAL FOOTAGE 1000’ TO 0’)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 1424
Article 760
Type FPLP
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
MUTUAL CAPACITANCE:
CHARACTERISTIC IMPEDANCE:
D. COLOR CODE
1
2
10/26/2007
75C
300V
1.6 Ohms/1000 ft nom
40.21 pF/ft @ 1kHz nom
50.5 Ohms @ 1MHz nom
(Listed as Individual Conductors or Pairs of Conductors)
Black
Red
Note: Data are subject to change without notice. Contact your Customer Service representative for latest information.