ETC NH1CG200

NH Fuse Links
Littelfuse European style NH fuse links are designed for the protection of conductors and motors. The gL-gG characteristic fuse links are generally used to protect
cables and installation lines from overload and short circuits. The aM characteristic
fuse links are used for the short circuit protection of motors and switchgear. They
are available in NH00C to NH3 sizes up to 630 amperes.
SPECIFICATIONS
Standards: DIN 43.620, IEC 269-2-1
Approvals: VDE
Example part number: NH1CG25 (size, characteristic and amperage)
Size
00C
00
0
1C
1
2C
2
3C
3
Current
Range
2A up to 100A
2A up to 160A
6A up to 160A
25A up to 160A
40A up to 250A
40A up to 250A
40A up to 400A
100A up to 400A
425A up to 630A
Voltage
(AC/DC)
500V/440V
500V/440V
500V/440V
500V/440V
500V/440V
500V/440V
500V/440V
500V/440V
500V/440V
Interrupting
Rating
120kA/25kA
120kA/25kA
120kA/25kA
120kA/25kA
120kA/25kA
120kA/25kA
120kA/25kA
120kA/25kA
120kA/25kA
Nominal
Frequency
45 - 62 Hz
45 - 62 Hz
45 - 62 Hz
45 - 62 Hz
45 - 62 Hz
45 - 62 Hz
45 - 62 Hz
45 - 62 Hz
45 - 62 Hz
Selectivity
1:1 25
1:1 25
1:1 25
1:1 25
1:1 25
1:1 25
1:1 25
1:1 25
1:1 25
All NH fuse links incorporate a blown fuse indicator.
gL-gG 500V
INTERNATIONAL
PRODUCTS
NEW
Amperage
2
4
6
10
16
20
25
32
35
40
50
63
80
100
125
160
200
224
250
300
315
355
400
425
500
630
120
NH00C/NH00
NH00CG2
NH00CG4
NH00CG6
NH00CG10
NH00CG16
NH00CG20
NH00CG25
NH00CG32
NH00CG35
NH00CG40
NH00CG50
NH00CG63
NH00CG80
NH00CG100
NH00G125
NH00G160
—
—
—
—
—
—
—
—
—
—
NH0
—
—
NH0G6
NH0G10
NH0G16
NH0G20
NH0G25
NH0G32
NH0G35
NH0G40
NH0G50
NH0G63
NH0G80
NH0G100
NH0G125
NH0G160
—
—
—
—
—
—
—
—
—
—
NH1C/NH1
—
—
—
—
—
—
NH1CG25
NH1CG32
NH1CG35
NH1CG40
NH1CG50
NH1CG63
NH1CG80
NH1CG100
NH1CG125
NH1CG160
NH1G200
NH1G224
NH1G250
—
—
—
—
—
—
—
aM 500V
NH2C/NH2
—
—
—
—
—
—
—
—
—
NH2CG40
NH2CG50
NH2CG63
NH2CG80
NH2CG100
NH2CG125
NH2CG160
NH2CG200
NH2CG224
NH2CG250
NH2G300
NH2G315
NH2G355
NH2G400
—
—
—
NH3C/NH3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
NH3CG315
NH3CG355
NH3CG400
NH3G425
NH3G500
NH3G630
NH00M
NH00M2
NH00M4
NH00M6
NH00M10
NH00M16
NH00M20
NH00M25
NH00M32
NH00M35
NH00M40
NH00M50
NH00M63
NH00M80
NH00M100
NH00M125
NH00M160
—
—
—
—
—
—
—
—
—
—
NH1
—
—
—
—
—
—
—
—
—
—
—
NH1M63
NH1M80
NH1M100
NH1M125
NH1M160
NH1M200
NH1M224
NH1M250
NH2
—
—
—
—
—
—
—
—
—
—
—
—
—
—
NH2M125
NH2M160
NH2M200
NH2M224
NH2M250
NH2M300
NH2M315
NH2M355
NH2M400
—
—
—
NH3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
NH3M315
NH3M355
NH3M400
—
NH3M500
NH3M630
NH Fuse Links
NH FUSE LINK DIMENSIONS
C
D
B
A
Size
00C
00
0
1C
1
2C
2
3C
3
Current
Range
2-100A
2-160A
2-160A
25-160A
63-250A
40-250A
125-400A
315-400A
315-630A
Dimensions (mm)
A
78.00
78.00
123.95
135.00
135.00
150.00
150.00
150.00
150.00
B
54.00
54.00
70.11
75.00
75.00
75.00
75.00
75.00
75.00
C
51.30
56.40
53.34
56.40
64.30
64.26
74.20
74.20
87.37
D
20.00
30.00
30.00
30.00
40.00
40.00
50.00
50.00
71.88
NH BASES / DISCONNECTS
FUSE BASES
Part No.
NHB00B
NHB00C
NHB1B
NHB2B
NHB3B
Size
00
00
1
2
3
Rating
690V/160A
690V/160A
690V/250A
690V/400A
690V/630A
Connection
Bolt
V-Clamp
Bolt
Bolt
Bolt
INTERNATIONAL
PRODUCTS
All fuse bases are single pole and gangable.
NEW
FUSE DISCONNECTS
Part No.
NHFC00B
NHFS0B
NHFS1B
NHFS2B
NHFS3B
Size
C00
0
1
2
3
Rating
690V/160A
690V/160A
690V/250A
690V/400A
690V/630A
Connection
Bolt
Bolt
Bolt
Bolt
Bolt
All disconnects are 3 pole.
Contact factory for dimensional information.
121