ETC 8504

Models 8503, 8504
Dual Channel PLC AC and DC Detectors
Models 8503 and 8504 Dual Channel PLC Interface modules
are designed to interface 120 Volt AC line or 24VDC signals
to the PLC 24 Volt, 7mA discrete inputs. The inputs are
isolated from the outputs by an optocoupler and the two
channels are independent. Power is supplied by the input
signal and is a nominal 10mA per channel. The output
transistor is fully floating allowing either source or sink
connection to the PLC.
The modules are housed in a plastic case with a built in Ufoot for mounting on standard DIN rails. The case dimensions,
excluding the U-foot are 1.65"H x 1.06"W x 3.78"L. Connections
are made to screw clamp terminals that accept wire sizes 22
to 16.
MODEL 8503
MODEL 8504
MODEL 8503, 8504
SINK CONNECTION
MODEL 8503, 8504
SOURCE CONNECTION
A
Model
Input Voltage
Current
Output Current
Ripple
Voltage Across Output
8503
8504
120 VAC
24 V D C
10 mA RMS
10 mA
7 mA Minimum
12 mA Typical
7 mA Minimum
12 mA Typical
±1.5 mA
N/A
30 VDC Maximum
30 VDC Maximum
Isolation Voltage
Input to Output Transistor
Environment
700 Volts DC
5 pF
Operating
0°C to +55°C
Storage
-40°C to +80°C
Siz e
1.65"H x 1.06"W x3.78"L (42 x 27 x 96 mm)
Weight
Agency Approvals
3 oz. (85 grams)
UL 508, C22.2 No 14-M91, UL 1604, C22.2 No 213-M1987
2401 Stanwell Drive • Concord, California 94520 • Ph: 925/687-4411 or 800/542-3355 • Fax: 925/687-3333 • www.calex.com • Email: [email protected]
1
3/2001