AD 3B43-00

Isolated AC Sine Wave Input
3B42 / 3B43 / 3B44
FEATURES
AC averaging technique used to rectify, amplify, and filter 50
Hz to 400 Hz sine-wave signals.
Accepts inputs of between 20 mV to 550 V rms to give an rms
output reading.
Module provides simultaneous precision voltage and
current outputs.
Module circuitry can withstand 130v rms at the input screwterminals.
All 3B42, 3B43, & 3B44 series modules are mix-and-match
and Hot Swappable.
APPLICATIONS
Industrial signal conditioning
Industrial signal isolation
Industrial signal filtering
PRODUCT OVERVIEW
The 3B Series of Signal Conditioning I/o Subsystems provide a
low-cost, versatile method of transferring analog transducer
signals to a data acquisition, monitoring or control system
without the inherent noise, non-linearity, drift and extraneous
voltages. The modules are designed to directly accept analog
signals from Thermocouples, RTD’s, AC and DC Strain Gages,
Torque Transducers, Frequency Transducers, LVDTs, millivolt
or process current signals. The modules amplify, isolate,
linearize and convert the transducer output signals to
standardized analog inputs for high-level analog I/O
subsystems. The 3B Series Subsystem consists of a 10” relay
rack with universal mounting backplane and a family of plug-in
(up to 16 per rack) input and output signal conditioning
modules.
Eight and four channel backplanes are also available. Each
backplane incorporates screw terminals for sensor inputs and
current outputs and a 26-pin connector for high-level singleended voltage outputs to the user’s equipment.
The input modules feature complete signal conditioning
circuitry optimized for specific sensors or analog signals and
provide two simultaneous high-level analog outputs: 0 to +10V
(or +10V) and 4-20 mA (or 0-20 mA).
FUNCTIONAL BLOCK DIAGRAM
Figure 1. 3B42, 3B43, & 3B44 Functional Block Diagram
Output modules accept 0 to +10V (or +10V) single-ended
signals and provide an isolated 4-20 mA (or 0-20 mA) process
signal. All modules feature a universal pin-out and may be
readily hot-swapped under full power and interchanged without
disrupting field wiring.
The Analog Devices 3B Series Signal Conditioning Subsystem is
designed to easily handle signal conditioning problems in
measurement and control applications. Some typical uses are in
microcomputer-based data acquisition systems, programmable
controllers, analog recorders, dedicated control systems, and any
other applications where monitoring of temperature, pressure,
flow and analog signals are required. Since each input module
features two simultaneous outputs, the voltage output can be
used to provide an input to a microprocessor-based data
acquisition or control system while the current output can be
used for analog transmission, operator interface, or an analog
backup system.
Each input module is a single-channel signal conditioner which
plugs into a socket on the backplane and accepts its signal from
the input screw terminals. All input modules provide input
protection, amplification and filtering of the input signal,
accuracy of +0.1%, low drift of +1 uV/ oC (low-level input
modules), and feature two high-level analog outputs that are
compatible with most process instrumentation. The isolated
input modules also provide +1500 V peak isolation.
The choice of a specific 3B module depends upon the type of
input signal. Input modules are available to accept millivolt, volt,
process current, thermocouple, RTD, AC and DC strain gage,
frequency and LVDT inputs. The voltage output of each module
is available from the system I/O connector while the current
output is available on the output screw terminals.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable.
However, no responsibility is assumed by Analog Devices for its use, nor for any
infringements of patents or other rights of third parties that may result from its use.
Specifications subject to change without notice. No license is granted by implication
or otherwise under any patent or patent rights of Analog Devices. Trademarks and
registered trademarks are the property of their respective companies.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
www.analog.com
Tel: 781.329.4700
Fax: 781.326.8703
© 2004 Analog Devices, Inc. All rights reserved.
3B42 / 3B43 / 3B44
GENERAL DESCRIPTION
programmable versions, Models 3B42-00, 3B43-00, and 3B4400, enable the user to configure a special input range by using
the optional plug-on AC1310 ranging card, which houses usersupplied resistors to determine zero and span. To facilitate
selecting resistors, a Windows program, 3B-CUSTOM,
calculates resistor values based on the user-desired input/output
ranges.
The 3B42, 3B43, and 3B44 are single-channel AC sine wave
signal conditioning modules which use an AC averaging
technique to rectify, amplify, and filter 50 Hz to 400 Hz sinewave signals ranging from 20 mV to 550 V rms to give an rms
output reading. Simultaneous precision voltage and current
outputs are provided including isolation (+1500 V peak inputto-output and power). The 3B42 and 3B43 modules withstand
220 V rms, and Model 3B44 withstands 550 V rms at its input
terminals without damage, thereby shielding computer-side
circuitry from field-side over-voltage conditions. Each plug-in,
mix-and-match, hot-swappable module is easily field calibrated
via front-panel zero and span adjustments for both voltage and
current outputs.
Signal isolation by transformer coupling uses a proprietary
modulation technique for linear, stable and reliable
performance. The differential input circuit on the field side is
fully floating, eliminating the need for any input grounding. A
demodulator on the computer side of the signal transformer
recovers the original signal, which is then filtered and buffered
to provide a low-noise, low-impedance output signal.
3B Series Custom-Ranging Program – Externally.
.
Figure 2
Rev. 0 | Page 2 of 8
3B42 / 3B43 / 3B44
3B42, 3B43 and 3B44 Models Available
Model
Input Range
Output Ranges1
3B42-00
Externally Programmable2
0 V to +10 V & 0 mA to 20 mA
3B42-01
0 mV to +50 mV rms
0 V to +10 V & 0 mA to 20 mA
3B42-02
0 mV to +100 mV rms
0 V to +10 V & 0 mA to 20 mA
3B42-Custom
*
*
Model
Input Range
Output Ranges1
3B43-00
Externally Programmable2
0 V to +10 V & 0 mA to 20 mA
3B43-01
0 V to +10 V rms
0 V to +10 V & 0 mA to 20 mA
3B43-Custom
*
*
Model
Input Range
Output Ranges1
3B44-00
Externally Programmable2
0 V to +10 V & 0 mA to 20 mA
3B44-01
0 V to +150 V rms
0 V to +10 V & 0 mA to 20 mA
3B44-02
0 V to +250 V rms
0 V to +10 V & 0 mA to 20 mA
3B44-Custom
*
*
1
Output current range may be user programmed to 4 mA to 20 mA using jumper supplied.
Requires AC1310 ranging card.
* Custom Input/Output ranges are available. Refer to configuration guide.
2
3B42, 3B43 and 3B44 Specifications
(typical @ +25°C and ±15 V dc, and +24 V dc Power)
Description
Model 3B42
Model 3B43
Model 3B44
Input Ranges
Standard Ranges, 50 Hz to 400 Hz
Refer to Model Table
Refer to Model Table
Refer to Model Table
Custom Ranges, 50 Hz to 400 Hz
20 mV rms to 1 V rms
1 V rms to 50 V rms
50 V rms to 550 V rms
0 V to +10 V
*
*
4 mA to 20 mA or 0 mA to 20 mA
*
*
Output Ranges
Voltage (RL > 2 kΩ)
Current (RL + 0 to 850 Ω)
1
Accuracy2
Initial @ +25°C
±0.05% Span
*
*
Nonlinearity
±0.02% Span
*
*
Stability vs. Temperature
Voltage Output
Zero
±0.005% of Span/°C
*
*
Span
±0.005% of Reading/°C
*
*
±25 ppm of Span/°C
*
*
±25 ppm of Reading/°C
*
*
±5% of Span
*
*
Current Output3
Zero
Span
4
Zero and Span Adjustment Range
Rev. 0 | Page 3 of 8
3B42 / 3B43 / 3B44
Input Bias Current
+1 nA
+5 nA
+3 nA
Input Resistance
100 MΩ
250 kΩ
1 MΩ
Noise
Input, 0.1 Hz to 10 Hz Bandwidth
5 µV rms
*
*
Output, Ripple and Noise
50 µV rms
*
*
Bandwidth, -3 dB
3 Hz
*
*
Output Rise Time, 10% to 90% Span
200 ms
*
*
Common-Mode Voltage (CMV)
Input-to-Output, Continuous
±1500 V peak, maximum
*
*
Transient
ANSI/IEEE C37.90.1-1989
*
*
*
*
Common Mode Rejection (CMR)
1 kΩ Source Imbalance, 50/60 Hz
100 dB
Input Protection
Continuous
220 V rms, maximum
*
550 V rms, continous
Transient
ANSI/IEEE C37.90.1-1989
*
*
Voltage Output Protection
Continuous Short to Ground
*
*
Current Output Protection
130 V rms, continuous
*
*
Power Supply Voltages
5
±15 V dc Supplies
Rated Operation
±(11.5 V dc to 16.5 V dc)
*
*
Current
±10 mA
*
*
Sensitivity
±0.01% span/V
*
*
Rated Operation
+12 V dc to +30 V dc
*
*
Current
+27 mA @ lout = 20 mA
*
*
Sensitivity
±0.0002% span/V
*
*
3.15" x 3.395" x 0.775"
(80.0 mm x 86.2 mm x 19mm)
*
*
+24 V dc Loop Supply
Mechanical Dimensions
Environmental
Temperature Range
Rated Performance
-25°C to +85°C
*
*
Storage
-55°C to +85°C
*
*
Relative Humidity, 24 hours
0 to 95% @ +60°C noncondensing
*
*
RFI Susceptibility
±0.5% Span error @ 400 MHz,
5 Watt, 3 ft
*
*
* Specifications same as model 3B42.
1
For a 0 to 20 mA range, a typical minimum output current is 10 µA.
2
Includes the combined effects of repeatability, hysteresis, and nonlinearity.
3
With respect to the voltage output.
4
A wide range of custom zero suppression and span is available with Models 3B42-00, 3B43-00 and 3B44-00, using the AC1310 ranging card.
5
+24 V dc loop power is required for driving the current output at loads up to 850Ω. If a current output load of 400Ω or less is applied, +15 V dc is sufficient for loop power. If only
voltage output is used, loop power is not required.
Specifications subject to change without notice. .Bottom of Form
Rev. 0 | Page 4 of 8
3B42 / 3B43 / 3B44
PIN CONFIGURATIONS AND FUNCTIONAL DESCRIPTIONS
Figure 3 3B42, 3B43, & 3B44 Input Field Connections
Table 1. Pin Function Descriptions—
Pin No.
1
2
3
4
Description
N/C
HI
LO
N/C
Figure 4 . Model 3B Series Module, with pin-out assignments.
ESD CAUTION
ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on the human
body and test equipment and can discharge without detection. Although this product features proprietary ESD
protection circuitry, permanent damage may occur on devices subjected to high energy electrostatic discharges.
Therefore, proper ESD precautions are recommended to avoid performance degradation or loss of functionality.
Rev. 0 | Page 5 of 8
3B42 / 3B43 / 3B44
OUTLINE DIMENSIONS
Figure 5. Outline Dimensions
Rev. 0 | Page 6 of 8
3B42 / 3B43 / 3B44
NOTES
Rev. 0 | Page 7 of 8
3B42 / 3B43 / 3B44
NOTES
© 2004 Analog Devices, Inc. All rights reserved. Trademarks and
registered trademarks are the property of their respective companies.
D05160-0-9/04(0)
Rev. 0 | Page 8 of 8