Battery BP1.2-6 Vrla rechargeable battery Datasheet

VRLA Rechargeable Battery
BP1.2-6
Measures
Technology
Values
Innovation
(BP1.2-6FR)
FEATURES
APPLICATION
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity
loss per month.
Can be used in any orientation(excluding used inverted).
UPS
Security
Medical
Lojack
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
6V
Terminals
Internal Resistance
Max. Discharge Current
T1 (Faston Tab 187)
ISO 9001
1.2Ah @ 20 hour rate F.V.(1.75V/cell)
300g(0.66lbs.)
55m
ISO14001
(Fully Charged )
UL
18 A (5 sec.)
Max. Charge Current
0.36 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Operating Temperature Range
Container Material
CE
IEC61056
JIS C 8702
GB/T 19639
ABS(UL94-HB, UL94-V0 is optional)
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
Terminal T1
97±1.5 (3.82±0.06)
Width
Total Height
56±2.0 (2.20±0.08)
56 2(2.20 0.08)
51 1.5(2.01 0.06)
Container Height
51±1.5 (2.01±0.06)
6.35(0.25)
Constant power discharge characteristics at 25 oC/77 oF
F.V.
(V/cell)
Discharge
Time
1.80V
1.75V
1.70V
1.65V
1.60V
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
21.69
15.97
12.80
7.61
4.367
1.749
1.206
0.674
0.355
25.11
17.30
13.39
7.90
4.498
1.784
1.224
0.684
0.360
26.68
17.92
13.80
8.08
4.579
1.800
1.231
0.687
0.360
27.88
18.35
14.12
8.20
4.634
1.813
1.235
0.689
0.360
28.80
18.72
14.40
8.28
4.680
1.823
1.239
0.689
0.360
o
Constant current discharge characteristics at 25 C/77 F
F.V.
(V/cell)
1.80V
1.75V
1.70V
1.65V
1.60V
Unit: W
5 Min
o
Discharge
Time
0.8(0.03)
25 1.5(0.98 0.06)
97 1.5(3.82 0.06)
25±1.5 (0.98±0.06)
4.75(0.19)
3.2(0.13)
Unit: A
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
2.23
1.291
0.734
0.291
0.201
0.112
0.059
2.33
1.340
0.756
0.297
0.204
0.114
0.060
3.16
2.40
1.370
0.770
0.300
0.205
0.115
0.060
5.11
3.23
2.46
1.389
0.779
0.302
0.206
0.115
0.060
5.28
3.30
2.50
1.403
0.787
0.304
0.206
0.115
0.060
5 Min
10 Min
15 Min
3.91
2.81
4.61
3.05
4.89
All data shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/0
REV. Jul. 2009
Powered by
B.B. Battery Co., Ltd.
Similar pages