Omron CJ1W-DRM21 Reference information Datasheet

Reference Information
Dimensions
Note: All dimensions are shown in mm. Divide by 25.4 to convert millimeters into inches.
J CJ1 Product Dimensions
Unit/product
Model number
Width
Power Supply Unit
CJ1W-PA205R
80
Power Supply
pp y Unit
CJ1W-PA202
45
CJ1W-PD025
60
CJ1M-CPU11/12/13
31
CJ1M-CPU21/22/23
49
CJ1H-CPUjjj
CJ1G-CPUjjj
62
CJ1W-TER01
14.7
CPU Unit
End Cover
CJ1M-CPU11/12/13
CJ1M-CPU21/22/23
J Example Rack Widths using CJ1WPA202 Power Supply Unit (AC, 14 W)
No. of Units
mounted
t d with
ith
31-mm width
Rack width (mm)
With CJ1MCPU12/13
With CJ1MCPU22/23
With CJ1G or
CJ1H CPU Unit
1
121.7
139.7
152.7
2
152.7
170.7
183.7
3
183.7
201.7
214.7
4
214.7
232.7
245.7
5
245.7
263.7
276.7
6
276.7
294.7
307.7
7
307.7
325.7
338.7
8
338.7
356.7
369.7
9
369.7
387.7
400.7
10
400.7
418.7
431.7
Programmable Controller
CJ1
B-131
Reference Information
Dimensions
Note: All dimensions are shown in mm. Divide by 25.4 to convert millimeters into inches.
Units of Width 31 mm
J Units of Width 20 mm
Unit
Model number
Width
I/O Control Module
CJ1W-IC101
20
32Basic-point
p
I/O
/ Modules
CJ1W-ID231/232
Unit
Model number
Width
I/O Interface Module
CJ1W-II101
31
8/16-point Basic I/O
Modules
CJ1W-ID201
CJ1W-ID211
CJ1W-IA111/201
CJ1W-OD201/202/203/204
CJ1W-OD211/212
CJ1W-OC201/211
CJ1W-OA201
32-point Basic I/O
Modules
CJ1W-MD231
CJ1W MD232
CJ1W-MD232
CJ1W-MD233
64-point Basic I/O
Modules
CJ1W-ID261
CJ1W-ID262
CJ1W-OD261
CJ1W-OD262
CD1W-MD262
CJ1W-OD263
CD1W-MD261
CD1W-MD263
CD1W-MD563
Interrupt Input Module
CJ1W-INT01
High Speed Input Module
CJ1W-IDP01
Analog I/O Module
CJ1W-ADjjj
CJ1W-DAjjj
CJ1W-MAD42
Temperature Control Units
CJ1W-TCjjj
Position Control Units
CJ1W-NC113/133
CJ1W-NC213/233
CJ1W-NC413/433
High-speed Counter Unit
CJ1W-CT021
ID Sensor Unit
CJ1W-V600C11
CJ1W-V600C12
Controller Link Module
CJ1W-CLK21-V1
Serial Communications Unit
CJ1W-SCU41
Ethernet Module
CJ1W-ETN21
DeviceNet Module
CJ1W-DRM21
ProfiBus-DP Slave
CJ1W-PRT21
ProfiBus-DP Master
CJ1W-PRM21
CJ1W-OD231/232
B7A Interface Unit
CJ1W-B7A22
CJ1W-B7A14
CJ1W-B7A04
CompoBus/S Master Module
CJ1W-SRM21
I/O Control Unit
32-point I/O Units (CJ1W-ID23j/OD23j)
B-132 Programmable Controller
CJ1
Reference Information
Dimensions
I/O Interface Unit
8/16-point Basic I/O Units,
Interrupt Input Unit, and
High-speed Input Unit
J Mounting Height
The mounting height of CJ1 Series CPU Racks and
Expansion Racks is from 81.6 to 89.0 mm, depending on
the Modules that are mounted. Additional height is required
to connect Programming Devices (e.g., CX-Programmer or
Programming Console) and Cables. Be sure to allow sufficient mounting height.
Approx. 100
to 150 mm
64-point Basic I/O Units and
32-point Basic I/O Units (CJ1W-MD23j)
81.6 to
89.0 mm
Note: Consider the following points when expanding the
configuration:
Special I/O Units and CPU Bus Units
•
•
The total length of I/O Connecting Cable must not
exceed 12 m.
I/O Connecting Cables require the bending radius as
indicated in the CS/CJ-series Connecting Cable.
CS/CJ-series Connecting Cable
R ≧ 69 mm
J Mounting Dimensions
Note: Outer diameter of cable: 8.6 mm.
DIN Track model number
A
PFP-100N2
16 mm
PFP-100N
7.3 mm
PFP-50N
7.3 mm
Programmable Controller
CJ1
B-133
Reference Information
CJ1 system Configuration Worksheets
J Worksheet 1
CPU Rack
Required Parts
Qty.
CPU -- Note: CJ1M-CPU1j requires 0.58 A, CJ1M-CPU2j requires 0.64 A, CJ1G
requires 0.91 A, SJ1H requires 0.99 A
Module
Current
Consumption
1
Description
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
9
1
10
CJ1W-IC101
1
0.02 A at 5V
If CJ1 Modules exceed ten per system, an
additional rack is required. The CJ1W will
attach to a CJ1W-II101 in the expansion rack.
TOTALS:
Power Supply:
1
Optional Parts
Memory Card (FLASH)
Programming Cable (Peripheral cable)
CX-Programmer Programming Software
Remote I/O Touch Screens/Cables/Terminal Blocks/Other Software/Etc.
Note: Make copies of this worksheet for system configuration and planning.
B-134 Programmable Controller
CJ1
Part Number(s) Selected
Reference Information
CJ1 system Configuration Worksheets
J Worksheet 2
Expansion Rack #_____
Required Parts
Qty.
Part Number(s) Selected
I/O Expansion Cables (CS1W-CNjj3)
1
CS1W-CN _________
I/O Expansion Module CJ1W-II101 (Current consumption 0.13 A at 5V)
1
CJ1W-II101
Module
Current
Consumption
Description
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
9
1
10
CJ1W-IC101
1
0.02 A at 5V
If CJ1 Modules exceed ten per system, an
additional rack is required. The CJ1W will
attach to a CJ1W-II101 in the expansion rack.
TOTALS:
Power Supply:
Other
Note: Make copies of this worksheet for system configuration and planning.