ETC2 D54B Control/communicator Datasheet

D9412G/D7412G
Control/Communicators
Specifications
Control Features
•
•
•
•
•
•
•
•
Eight programmable areas, each with
perimeter/interior partitioning. Regular, master,
associate, or shared option by area
Real-time clock and test timer
Up to 1000-event log, including time, date and
event with area, point and user number
Battery charging circuit; AC power, voltage and
ground fault supervision
Automatic reset circuit protectors
On-board CPU watchdog warning buzzer and
diagnostic LEDs
Lightning and EMI protection
Power limited external circuits
Communicator
•
•
•
•
•
•
•
Built-in digital communicator with phone line
monitor (loop or ground start)
Multiple telephone numbers, primary and duplicate
paths with main and alternate destinations
All reports within each 4 route groups are
programmable
Optional dual phone line switcher monitors 2 phone
lines
Automatic test and status reports
Time windows for arming and open/close report
suppression
Programmable answering machine work-around for
remote programming on shared phone line
Programmable Outputs
•
•
•
•
•
•
•
2-amp alarm power @ 12 VDC
1.4-amp aux power @ 12 VDC
4 alarm output patterns
Automatic bell test
Programmable bell shut-off timer
D7412G: 67 programmable outputs
D9412G: 131 programmable outputs
User Interface
•
•
•
•
•
•
•
•
•
•
•
•
Access Control
•
•
System Response
•
•
•
•
•
•
•
•
•
•
D7412G: 75 points, 8 on-board, up to 67 off-board
D9412G: 246 points, 8 on-board, up to 238 offboard
31 custom point indexes, including fire supervisory
Selectable point response time
Fire alarm verification
Fire inspector’s local test
Watch mode
Scheduled events (Skeds) arm, disarm, bypass and
unbypass points, control relays, control authority
levels, control door access and more
Supervises up to 8 command centers (up to 32
non-supervised command centers can be used)
Custom command center text
D7412G: 4 custom functions
D9412G: 16 custom functions
Full function command menu including custom
functions
D7412G: 99 Users
D9412G: 249 Users
Each user has authority by area and 16-character
name
14 custom authority levels control user’s authority
to change, add, delete passcodes or access control
tokens/cards, disarm, bypass points, initiate system
tests, and more
Adjustable brightness/loudness for command
center display/ sounder
D7412G: 1 parallel printer
D9412G: 3 parallel printers
•
D7412G: 2 access control doors and 396
tokens/cards
D9412G: 8 access control doors and 996
tokens/cards
Custom door strike, point shunt and auto disarming
response by area
Logging options for: Access Granted, No Entry,
Request to Exit and Request to Enter
14-panel wide access levels with both manual and
scheduled control
D9412G/D7412G
System Description
D9412G/D7412G Control/Communicators provide an
integrated solution to Access Control, Security, and Fire
Alarm System applications.
Control/Communicators are capable of monitoring alarm
points for intruder or fire alarms while operating user
command centers, (access readers, door locks D7412G/ D9412G), and other outputs. Includes a builtin digital communicator, which reports events to
selected destinations via 4 programmable route groups.
Programming and accessory modules offer flexibility
and beneficial features rarely found in other security
control systems.
Area Configurations
D9412G/D7412G area programming offers you a wide
selection of different system configurations. Each area
is assigned an account number to define annunciation,
control, and reporting functions. Multiple areas can be
linked to a shared area which is automatically controlled
(hallway or lobby). Area arming can be conditional on
other areas (master/associate).
User Interface
D9412G/D7412G command centers provide onpremises point and system status annunciation. A fully
selectable user interface can customize command
center displays and simplify operation by creating menu
items and functions, appropriate only to that command
center.
Function Lists can help a user become familiar with the
operation of the control panel.
Each user may have a 16-character customized name
that may be viewed, printed, reported to a central station
in Radionics’ Modem IIIa2 Communications format or
retrieved with Remote Account Manager (RAM).
Security and Fire Detection
D9412G/D7412G provide eight “on-board” detection
points, and up to 238 additional off-board points
(depending on Model and expansion interfaces). Points
may be individually programmed and used to monitor all
types of burglar alarm, fire alarm, and supervision
devices.
Communications
D9412G/D7412G have four route groups, sort reports
by priority and are capable of transmitting reports to up
to four locations. Each group has a programmable
primary and backup destination. Compatible with D6600
NetCom Communications System using a D9133TTL-E
Ethernet Interface Module. Radionics’ Modem IIIa2
Communications Format, available with Radionics’
receiver, adds these reporting capabilities. To name just
a few:
•
Individual point numbers and text
•
Opening/Closing reports by area number
•
Remote programming attempts
•
Diagnostic reports
•
Access control events with user name
Event Log Storage, Viewing and Printing
Custom functions allow users to perform complex
functions with a few keystrokes. Each may be
programmed and identified by 16 characters of custom
text and contain up to 32 keystrokes.
D9412G/D7412G event log automatically stores up to
1000 events. All local and transmitted events are stored
(some access events are selectable). Event log includes
time, date and event, with area, point and user number.
Users may view event log from Alpha Command
Centers. Events may be retrieved remotely using RAM.
D1255 Command Center, D1256 Fire Alarm Command
Center and D1257 Fire Alarm Annunciator use a 16character English language display to show system
status, area status (custom text), and point status
(custom text). D720 8-point LED area command center
provides command functions and annunciation for up to
8 points in a single area. Any combination of these
command centers may be used within the same area.
Events are printed as they are stored in event log.
D9131A Parallel Printer Interfaces can be installed to
record events locally on one, two, or three printers
(depending on model). Each can print opening and
closing, access, alarm, Skeds, or any combination of
events. Each can print information from any combination
of areas. Each can supervise various printer status
conditions.
Easy to remember commands like Command 1,
Command 2, and Command 8 make an easy transition
for seasoned Radionics users.
Event log and local printer are ideally suited for
customers who like to have a record of openings and
closings without having extra communications costs.
Logger and RAM, can suppress reports and then
retrieve events periodically using one phone call, rather
than receiving several calls each day.
User Passcodes
D9412G/D7412G can accommodate:
•
D7412G: 99 user passcodes
D9412G: 249 user passcodes.
(Each passcode individually programs with 3 to 6
digits in length and no fixed digits).
When the panel’s event log reaches its programmed
threshold of stored events, it can send a report to a
receiver to remind central station to retrieve events from
the panel’s event log with RAM.
Each user is assigned one of 14 customized authority
levels in each area. You may restrict passcodes to
operate only during certain times.
© 2001 Radionics
D9412G/D7412G Specifications
Page 2
47487B
D9412G/D7412G
Scheduled Events (Skeds)
D9210B Access Control Interface Module
D9412G/D7412G internal clock and calendar help the
panel operate individual scheduled events (Skeds).
Skeds perform a specific function (such as arm/disarm,
relay control, point bypassing, etc.). Each Sked is
programmed for a time and day-of-week schedule or a
date-of-year schedule.
Access is granted from Wiegand format readers or
Request to Enter/Exit devices when connected to the
D9210B.
Users may change Sked Time if programmed for local
time editing. Holiday schedules can enable or disable
individual Skeds during holiday periods.
•
•
•
64 scheduled events with up to 26 different
functions
•
Day-of-week or date-of-year schedules
•
Four holiday schedules of 366 days each (leap
year)
Fire Test
D9412G/D7412G Fire Test Mode suppresses reports to
the central station receiver so you can test initiating and
indicating devices without transmitting alarms. Initiating
Fire Test Mode, sends “Fire Walk Start” to central
station indicating start of test. Test events become “local
only.” Command center shows how many points are to
be tested.
Each time a device initiates an alarm, programmed point
text displays at command center and the fire bell rings
for 2 seconds. Automatic sensor reset feature allows
continued testing of devices without time consuming
trips to manually reset sensors. At the end of test,
command center displays the number of untested
points. You can also view point text for each untested
point.
Ending Fire Test Mode, sends “Fire Walk End” to the
central station receiver indicating end of test.
Combining Access Control with Security and Fire
Detection (D7412G/D9412G)
D9412G/D7412G combined systems can help prevent
false alarms making it easy to use one system that
controls access, security, and fire functions.
Access control features of D7412G/D9412G can deny
access during armed periods, grant access only to
certain authorized users depending whether an area is
master armed, perimeter armed or disarmed. Alarm
system can automatically disarm when designated
authorized users are granted access.
•
•
Also provided are connections for door point, strike,
buzzer and enclosure tamper. (One D9210B required
per door).
Each access door can be configured independently
Door point controls access door and is part of alarm
system (door does not need double contacts)
•
Door contact can reset strike time when opened
•
Door contact can terminate entry buzzer (if used)
•
Door contact is shunted when valid access is
granted
•
Optional buzzer can trigger prior to end of door
shunt period, warning user a “door left open”
condition is about to occur
•
Door point can be configured to generate alarm or
trouble (or have no response) when door is left
open beyond shunt period
•
In addition to granting access, cards control
whether system will disarm along with granting
access
•
Door strike can release automatically during
disarmed periods, then automatically re-lock when
area is armed
•
Door can generate an alarm, trouble, (or have no
response) depending on area’s armed condition
when door is opened outside authorized access
period
•
REQUEST TO ENTER and REQUEST TO EXIT
can be programmed to shunt door without
activating strike
•
An option determines whether access granted, no
entry, request to enter, or request to exit messages
are sent to event log
RAM IV and RAM IV Lite
These account management and panel-programming
utilities allow computers equipped with the Microsoft®
Windows® operating system and a modem to act as a
remote programming, record storage, remote control
and troubleshooting tool for the D9412G/D7412G
Control/Communicators. To enhance the down/upload
capabilities RAM can be used in a TCP/IP and Dynamic
Host Communication Protocol (DHCP) configuration.
D7412G: Two (2) access doors; 75 detection
points; 396 Token/Users
D9412G: Eight (8) access doors; 246 detection
points; 996 Token/Users
47487B
D9412G/D7412G Specifications
Page 3
© 2001 Radionics
D9412G/D7412G
be equipped with a 16-character alphanumeric display,
distinct fire and burglary tones, and backlighted multikey touchpad.
Specifications
General
Contractor shall furnish and install, where indicated on
plans, a Radionics D9412G/D7412G
Control/Communicator. Panel shall be listed by
Underwriters Laboratories for NFPA 72 Applications.
D9412G/D7412G shall support initiating and indicating
modules and Radionics Command Centers. Power
supply shall provide 1.4-amp @12 VDC for all
processing functions and auxiliary requirements.
Software
D9412G/D7412G programming of all system functions
shall be accomplished on site using Radionics’ Handheld D5200 Programmer or remotely using a RAM
software package. A programmable system passcode
shall be used to prevent unauthorized remote
programming.
Panel shall accommodate up to four separate telephone
numbers for primary, alternate and backup receivers,
automatic test reports, selective relay activation, and
custom text on associated command centers and
annunciators.
When resetting alarms, arming or disarming a
combination fire/burglary and/or access control system,
the user shall be identified by name and number.
D1255, D1256, and D1257 shall have the ability to
display for each detection point: alarm, trouble,
supervisory, or faulted, and custom text. In addition,
expanded, addressable point displays shall include
missing and extra point information. System-wide
displays shall include: local system test, sensor reset,
fire test mode, and user programming prompts.
Fire Test
D9412G/D7412G Fire Test Mode shall support singleperson operation. All reports to central station shall be
suppressed while fire test is being conducted. Fire Test
Mode shall be activated by entering a user passcode at
a command center. All testing data shall be visible on
command center and annunciator displays during
testing.
Hardware
D9412G/D7412G shall provide up to 246 individually
identified addresses, (75 with D7412G). Each shall
accommodate normally open and/or normally closed
devices with end-of-line resistor supervision. Each point
shall be programmable for fire, fire supervisory or
burglary applications. Point output shall be silent or
audible. Audible output shall be steady, pulsed, CA
standard, or temporal code 3.
External Hardware
D7212/D7412G: Up to 99 users
D9112/D9412G: Up to 249 users
Panel’s internal clock shall support Skeds (scheduled
events) feature. User shall have option to alter Sked
activation times using a programmable passcode.
Up to 64 programmable, scheduled event functions shall
be available for controlling relays, enabling passcodes,
windows, and supporting service alert feature.
Other programmable functions shall include fire alarm
reset commands, and day/date/time adjustments.
Event Logger/Clock
D9412G/D7412G event log shall store up to 1000
events. All system events shall include time, date and
event with area, point and user number.
D9412G/D7412G shall allow use of up to three on-site
parallel printers (one with D7412G), using Radionics
D9131A Printer Interface Modules. Events shall print
time, date, and event description with area, account,
point, and user number, including text for points and
users.
Installation, Warranty, and Training
D9412G/D7412G System Installation, wiring of initiating
devices and signaling circuits, shall be the responsibility
of installing company.
Warranty on all components shall be two years, subject
to manufacturer’s limitations. Training on complete
system operation shall be furnished by installing
company upon completion of installation.
Access events (optional) stored shall include: Access
granted, No Entry, Request To Enter, and Request To
Exit. Logger records certain functions entered at
command centers. Stored events in Logger shall be
retrievable with a RAM software package.
Remote Diagnostics and Controls
D9412G/D7412G shall be able to be remote controlled
through use of RAM software. Features shall include:
reset of audible signals, activation/deactivation of D8129
relays, interrogation of battery, point and armed status,
enabling or disabling reporting functions, and shunting
of reporting points during servicing.
Command Centers
D9412G/D7412G command centers shall be Radionics
D1255 Command Center, D1256 Fire Alarm Command
Center and D1257 Fire Alarm Annunciator. Each shall
© 2001 Radionics
D9412G/D7412G Specifications
Page 4
47487B
D9412G/D7412G
Accessories/Ordering Information
Model
Model
Description
Description
Command Centers, Keypads and Accessories:
Fire Alarm Modules and Accessories:
D1255
Command Center
D125B
Dual Class B Powered Loop Interface Module
D1256
Fire Alarm Command Center
D129
Dual Class A Initiation Circuit Module
D1257
Fire Alarm Annunciator
D130
Auxiliary Relay Module, 12/24 VDC
D720
8 Point LED Area Command Center
D184
Auxiliary Local Energy Interface Kit
D268
Independent Point Control Module
D185
Reverse Polarity Interface Module
D269
Independent Point Control Keypad
D192C
N.A.C. Module, Class B, 12/24 VDC, 1.8-amp
D279
Independent Point Control
D192D
N.A.C. Module, Class A/B, 12/24 VDC, 3-amp
D54B
Command Center Flush Mount Kit, Brass
D928
Dual Phone Line Switcher
D54C
Command Center Flush Mount Kit, Stainless
D8130
Release Module
D55
Command Center Desk Stand
D56
Command Center Surface Mnt. Conduit Box
Power Supplies, Transformers, Batteries &
Accessories:
D9142F Auxiliary Power Supply, 24 VDC, 4-amp
Zone Expansion and Interface Modules:
D8125
POPEX Module
D8132
Battery Charger Module, 12 VDC
D9127U/T
POPIT Module, U=No Tamper /
T= Tamper
D1640
16.5 VAC 40 VA Transformer
D113
Battery Lead Supervision Module
D8128C
OctoPOPIT Module
D122/L
Dual Battery Harness/Long Leads
D940
Super Loop Module
D126
Battery, 12 V, 7.5 Ah
D8129
OctoRelay Module
D1218
Battery, 12 V, 17.2 Ah
D127
Reversing Relay
Enclosures, Brackets, and Phone Cords:
D136
Plug-in Relay
D8103
Universal Enclosure
D8121A
Derived Channel S.T.U. Non UL
D8109
Fire Enclosure
D8122
Derived Channel S.T.U. UL Listed
D8108A
Attack Resistant Enclosure
D9131A
Parallel Printer Interface Module
D8004
Transformer Enclosure
D9210B
Access Control Interface Module
D137
Module Mounting Bracket
D101
Lock and Key for D8103
D161/162
Dual Mod. Telephone Phone Cord, 7 ft.
(2.1 m) / 2 ft. (61 cm)
Detection Devices with Built-in POPIT:
ZX835
PIR/Microwave Detector, 35 x 35 ft.
(10.7 x 10.7 m)
ZX970
PIR/Microwave Detector, 60 x 60 ft.
(18.3 x 18.3 m)
ZX935Z
PIR Detector, 35 x 35 ft. (10.7 x 10.7 m)
ZX776Z
PIR Detector, 50 x 50 ft. (15 x 15 m)
ZX794
PIR Detector, 90 x 90 ft. (27 x 27 m)
ZX938Z
PIR Detector, Ceiling Mount, 360° x 60 ft.
(18 m)
D278S
Smoke Detector Base 12 VDC
D298M
Smoke Detector Base, Master, 24 VDC
D298S
Smoke Detector Base, 24 VDC
47487B
Programming Products:
D5200
Hand-held Programmer
D5500####*
Remote Account Manager, RAM IV
D5500####*LTE
RAM IV Lite
* #### represents the version number of the software.
Order Processing has the latest revision information.
D9412G/D7412G Specifications
Page 5
© 2001 Radionics
D9412G/D7412G
Listings and Approvals
Fire
•
UL: Central Station, Local, Auxiliary, Remote
Station, and Household Fire Warning.
•
CSFM: Approved for highrise and non-highrise.
Burglary
•
UL: Central Station, Local, Police Connect, Bank
Safe and Vault, Mercantile Safe and Vault, and
Grade A Household
•
DOD: Approved for installations in Sensitive
Compartmented Information Facilities (SCIF).
Access
•
UL: Access Control Systems.
© 2001 Radionics
D9412G/D7412G Specifications
Page 6
47487B
D9412G/D7412G
Notes
47487B
D9412G/D7412G Specifications
Page 7
© 2001 Radionics
© 2001 Radionics, a division of Detection Systems, Inc.
PO Box 80012, Salinas, CA 93912-0012, USA
Customer Service: (800) 538-5807
47487B
Specifications
7/01