DC Current transducer DK-B5/10 A split core transducer for the electronic measurement DC current, with galvanic isolation between the primary (High power) and the secondary circuits (Electronic circuit) with voltage output. Electrical data Primary Nominal Current IPN (A.t) 50,75,100 100,150,200 150,225,300 200,300,400 50,75,100 100,150,200 150,225,300 200,300,400 Vc RL Vd f Ic Features Analogue Output Signal 1) VOUT (V) 0-5 0-5 0-5 0-5 0-10 0-10 0-10 0-10 Supply voltage Load resistance (max) Isolation voltage Frequency Current consumption (max) Type DK 100 B5 DK 200 B5 DK 300 B5 DK 400 B5 DK 100 B10 DK 200 B10 DK 300 B10 DK 400 B10 22-26 250 3000 DC 100 V AC/ DC kΩ V AC mA Accuracy - Dynamic performance data X εL tr Accuracy @ IPN, TA=25°C Linearity Response time @ 90% of I PN ±1 ± 0.75 < 300 % % mS General data TA TS m IPN = 50..400A Ambient operating temperature (0-95% RH) Ambient storage temperature Mass - 20 .. + 50 - 20 .. + 85 120 °C °C g • DC Measurement • Split core box • Voltage output • Jumper selectable ranges • Panel mounting • Extended measuring range Advantages • Large aperture • High isolation between primary and secondary circuits • Easy to mount • No insertion losses Applications • Battery Banks - Monitors load current. - Monitors charging current. - Verifies operation. • Transportation Measures traction power or auxiliary loads. • Electric Heating Elements Faster response than temperature sensors. Options on request • DIN mounting Note : 1) For 0-3 V output model, no saturation output up to 3.5 V for 0-5 V output model, no saturation output up to 5.75 V and for 0-10 V output model, no saturation output up to 11.5 V LEM Components 040405/5 w w w .lem.com Dimensions DK-B5/10 (unit : mm, 1mm = 0.0394 inch) 3.2 57.2 13 21.7 61 13 30 21.7 89.7 61 4.5 77.3 Mechanical characteristics • General tolerance • Primary aperture • Panel mounting Distance between holes Output output in % ± 1 mm 21.7 mm sq. 2 holes ∅ 4.5mm 77.3 mm 100 - IP + IP Connections 22-38VAC/DC VAC 22-26 • 2 x UNC8 Cylindric Head Range Jumper 1(-) 2(+) 3(-) 4(+) Output Power - Dead front captive screw terminals - 12-22AWG solid or stranded LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.