FC-2224 TWO-ZONE PANEL CONVENTIONAL FIRE ALARM CONTROL DESCRIPTION The FC-2224 Fire Alarm Control panel is a proven, versatile, two-zone control with space to accommodate an optional digital communicator. It meets the requirements of NFPA Standard 72 for Central Station, Protected Premises, and Remote (DACT) Supervising Station Fire Alarm Systems. It is Listed to UL Standard 864, inherently power limited and meets all UL transient immunity requirements. The many features of the FC-2224 control provide a cost effective approach to systems design, and allow a great degree of flexibility in one enclosure. These features include two (2) Class B, Style B initiating circuits and two (2) Class B, Style Y notification appliance circuits, rated at 1.25 amps each. Notification appliance circuits can be configured as silenceable or non-silenceable. DIP switch programming is used throughout, eliminating the need for computers and associated software. A time delay of 30, 60, or 90 seconds is available for waterflow switches. The control is housed in a red steel enclosure with a window offering a view of LEDs displaying the status of vital functions. The surface mounted enclosure, with its slim appearance (3 3/8-inch depth) is designed to blend with any environment. Space is available for two (2) B-7R batteries. Supervision of vital components, plug-in modules, functional switches and standby batteries is provided. The optional digital communicator includes a wide range of selectable transmission formats to communicate to most central stations. Other features of the communicator are: A line-active indicator for each of two phone lines, “Kiss-Off” signal LED, dual “low telephone voltage detect” circuitry and programmable event codes per format. The FC-2224 is programmable for AC power loss delay required for DACT operation. An optional serial annunciator driver allows remote alarm annunciation to as many as four (4) Model FC-2866 remote annunciators. Other optional modules include the FC-2880 I/O module which provides 34 pre-defined open collector outputs that can be used to drive LEDs or relays. FEATURES · · · · · · · · · Inherently Power Limited DIP Switch Programming Choice of Output Patterns Including ANSI S3.41 Programmable Time Delay for Waterflow Switches Periodic Trouble Reminder Walk Test Feature Optional Digital Communicator with Multiple Reporting Formats Serial Annunciator Output (Optional) Surface Mount Technology AGENCY APPROVALS UL CSFM S1869 Approved Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 2000 All Rights Reserved 16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099 An ISO 9001 Certified Company 9020-0483/Ver. 1.5 FC-2880 Annunciator Driver Module FC-2884 Serial Driver Module FC-2866 Remote Zone Annunciator FC-2104 Digital Alarm Communicator Transmitter CHARACTERISTICS AND DIMENSIONS Supervisory current Alarm current Operating temperature Relative humidity Dimensions ` .050 amp. .250 amp. 32 - 120o F (0 - 49o C) 85% (non-condensing) 15 1/8”H x 12 13/16” W x 3 3/8” D (38.4 cm x 33 cm x 8.5 cm) ORDERING INFORMATION Part Number 150-00001 Model FC-2224 Description Two-zone Control, 120 VAC 151-00001 151-00003 151-00004 151-00005 151-00019 151-00017 151-00018 FC-2884 FC-2880Å FC-2866Å FC-2104 2190 5230 7860 Serial Driver Module Annunciator Driver Module Remote Zone Annunciator w/reset and silence switches Digital Alarm Communicator Transmitter Cabinet for FC-2104 DACT (optional) Programmer for FC-2104 DACT Cable w/spade lugs for connection to Telco RJ31X plug. (Optional) Quick connect cable to connect 5230 Programmer to FC-2104 DACT FC-2224PC 7628 Replacement PC board UL Listed EOL resistor 151-00020 151-00007 151-00011 151-00012 Å 120 VAC Transformer (replacement) 230 VAC, 50 Hz Transformer (optional) Requires one (1) FC-2884 FC-2104 DACT reporting formats are: SIA 8 or 20 SK 3/1 1,400 or 2,300 Hz Contact ID SK 4/2 BFSK 1,400 or 2,300 Hz 9020-0483 2 of 2