Bussmann® 5 x 20mm Ferrule Fuses GDB GDB-V Fast Acting, Low Breaking Capacity 38.10mm (±.38) Time-Current Characteristic Curves–Average Melt 21.10mm (±.81) 10mm 20mm (±2.0) (±0.5) 32mA 40mA 50mA 63mA 5.54mm (±.20) 80mA 100mA 125mA 160mA 200mA 250mA 315mA 400mA 500mA 630mA 800mA 1A 1.25A 1.6A 2A 2.5A 3.15A 4A 5A 6.3A Dimensional Data 100 AMPERE RATING 38.10mm (±.38) 5.2mm (+0.1/-0.2) .81mm (REF) 10 TIME IN SECONDS Glass tube - end caps: nickel or silver-plated brass. CATALOG SYMBOL: GDB FAST-ACTING, LOW BREAKING CAPACITY 250 VOLTS AC UL RECOGNIZED: (GUIDE #JDYX2, FILE #E75865) 1 Limits for Pre-arcing Time 1.5 In MIN In 2.1 In MAX 2.75 In MIN MAX 4 In MIN 32mA - 100mA 60 min. 30 min. 10 ms. 500 ms. 3 ms. 125mA - 6.3A 60 min. 30 min. 50 ms. 2 sec. 8A - 10A 60 min. 30 min. 12A - 16A — 30 min. MAX 10 In MAX 100 ms. 20 ms. 10 ms. 300 ms. .1 20 ms. — — — — 40 ms. — — — — 80 ms. 1.1 In: Æt ² 70°C, 125mA - 3A. 1.0 In: Æt ² 70°C, 4A. Product Symbol Lead 100 10 Packaging & Ordering Information: 1 .1 .01 CURRENT IN AMPERES Ampere Rating Package Code Blank (None) V Axial Leads GDB only .0329 x 1.59 Copper Tinned GDB S500† Markings: MFG mark, Rated Current, Rated Voltage, Characteristic Symbol, Breaking Capacity Symbol, Approvals where Applicable. † S500 is an European Designation. In North America use GDB respectively when referencing product. CE logo denotes compliance with European Union Low Voltage Directive (50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. 12-18-98 SB98107 Rev. A Form No. GDB Page 1 of 2 BIF Doc #2015 Bussmann® 5 x 20mm Ferrule Fuses GDB GDB-V Fast Acting, Low Breaking Capacity include ratings Pre-arcing Value (I2t) (A2s) typ. 0.000047 0.00011 0.00020 0.00057 0.0012 0.003 0.005 0.008 0.016 0.028 0.058 0.18 0.18 0.35 0.67 0.60 0.84 1.6 4.2 6.1 13 22 42 69 — — — — • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • UR 10 x In 250V, 50Hz cos ø Å 1.0 Power Dissipation (W) max. 0.90 0.85 0.40 0.40 0.45 0.55 0.65 0.80 0.85 0.95 1.0 1.0 0.30 0.40 0.45 0.67 0.92 1.1 1.1 1.2 1.3 1.6 1.7 2.3 — — — — IMQ 35A at 250V, 50Hz cos ø Å 1.0 Voltage Drop (mV) max. 10000 8000 3200 2500 2200 2100 2000 1950 1600 1400 1150 950 220 220 180 200 200 190 160 145 130 120 115 110 — — — — above 6.3 amps. SEMKO Breaking Capacity VDE Current Rated Rating Voltage (In) (V) 32mA 40mA 50mA 63mA 80mA 100mA 125mA 160mA 200mA 250mA 315mA 400mA 500mA 250 630mA 800mA 1A 1.25A 1.6A 2A 2.5A 3.15A 4A 5A 6.3A 8A* 10A* 12A* 16A* * IEC Standard 127 Sheet II does not BSI Electrical Characteristics • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 12-18-98 SB98107 Rev. A Form No. GDB Page 2 of 2 BIF Doc #2015