TDK HWS1500-5 Single output industrial power supply Datasheet

HWS300-1500 Series
Single Output Industrial Power Supplies
Features
 Limited Lifetime Warranty
 UL508 approved
 SEMI F47 Compliant (high line AC)
 Universal Input (85 - 265VAC)
 High Efficiency
 Class 1 Div 2 option (/RY suffix)
 Wide Range AC Input
Key Market Segments & Applications
Specifications
Model
Input Voltage range (47-63Hz)
Input Current (Typ)
(1)
A
HWS300
Inrush Current
(1)
Power Factor
Temperature Coefficient
Overcurrent Protection
Overvoltage Protection
Hold Up Time (Typ)
Leakage Curr. (at 240VAC, 60Hz)
Remote Sense
Indicator
Remote on/off
Parallel operation
DC Good
Remote Adjust (PV)
Operating Temperature
Storage Temperature
Humidity (non condensing)
Cooling
Withstand Voltage
(4)
Isolation Resistance
Vibration (non operating)
Shock
Safety Agency Certifications (5)
Line Dip
Conducted & Radiated EMI
Immunity
Weight (Typ)
Size (WxHxD)
Warranty
A
V
ms
mA
°C
g
in
yrs
HWS600
HWS1000
HWS1500
85 - 265VAC or 120 - 330VDC (6)
5V: 3.8/1.9;
5V: 7.5/3.6;
3.3V: 9.6/5.0;
3.3V: 15.0/8.0;
12-48V: 4.2/2.1
12-48V: 8.1/3.9
5-60V: 13.5/7.0
5-60V: 19.5/10.0
20 / 40
Meets EN61000-3-2
<0.02%/°C
>105% (>101% of peak current for peak current capable models)
See table on page 2 (Recycle AC or remote on/off to reset)
20
<0.75mA
<1.2mA
<1.5mA
Yes
Green LED = ON
Yes (Isolated from output)
Single wire connection (up to 5 units)
Yes
External voltage adjusts output, see options table
-10°C to +70°C, derate linearly to 50% load from 50C to 70C (2, 3)
-30 to +85°C
Operating: 10 - 90%RH, Non operating 10 - 95%RH
Internal fan
Input to Ground 2.5kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
>100M at 25°C & 70%RH, Output to Ground 500VDC
10 - 55Hz (1 minute sweep), 19.6m/s2 constant X, Y, Z 1 hour
< 196.1 m/s2
UL60950-1, CSA60950-1, EN60950-1, EN50178, UL508, CE Mark
Complies with SEMI F47 (200VAC line only)
EN55011 / EN55022, FCC VCCI (HWS300, 600 & 1000: Class B, HWS1500: Class A)
IEC61000-4-2, -3, -4, -6 (Level 3), -5, -8 (Level 4), -11
1,000
1,600
3,200
3.3-7.5V: 4000; 12V+: 3800
2.4 x 3.23 x 6.5”
3.94 x 3.23 x 6.5”
5 x 3.25 x 9.45”
5 x 3.25 x 11”
Limited lifetime warranty (See TDK-Lambda’s terms and conditions)
(1) 100/200VAC
(2) HWS start up -20°C. (-40°C see options table)
(3) HWS1000/1500 with 85VAC input: See installation manual
(4) 2kVAC HWS1000/1500 Input to ground
HWS1000: -10 to +71°C. HWS1000-5, HWS1500-3, -5 derate linearly above 40°C
1-800-526-2324 • www.us.tdk-lambda.com/lp/
61
(5) UL60601-1, EN60601-1, see options.
UL508; HWS300/600 5V, 12V, 24V & 48V models
(6) Not on HWS1500/ME, /HD or /RY versions
(*) Class 1 Div 2 option (/RY suffix)
Disclaimer: us.tdk-lambda.com/lp/legal.htm
HWS300-1500 Series
Output Ratings
Model
HWS300-3
HWS600-3
HWS1000-3
HWS1500-3
HWS300-5
HWS600-5
HWS1000-5
HWS1500-5
HWS1000-6
HWS1500-6
HWS1000-7
HWS1500-7
HWS300-12
HWS600-12
HWS1000-12
HWS1500-12
HWS300-15
HWS600-15
HWS1000-15
HWS1500-15
HWS300-24
HWS600-24
HWS1000-24
HWS1500-24
HWS1000-36
HWS1500-36
HWS300-48
HWS600-48
HWS1000-48
HWS1500-48
HWS1000-60
HWS1500-60
Voltage
V
3.3V
3.3V
3.3V
3.3V
5V
5V
5V
5V
6V
6V
7.5V
7.5V
12V
12V
12V
12V
15V
15V
15V
15V
24V
24V
24V
24V
36V
36V
48V
48V
48V
48V
60V
60V
Adjust
Range
V(3)
2.64 - 3.96
2.64 - 3.96
2.64 - 3.96
2.64 - 3.96
4-6
4-6
4-6
4-6
4.8 - 7.2
4.8 - 7.2
6 - 9V
6 - 9V
9.6 - 14.4
9.6 - 14.4
9.6 - 14.4
9.6 - 14.4
12 - 18
12 - 18
12 - 18
12 - 18
19.2 - 28.8
19.2 - 28.8
19.2 - 28.8
19.2 - 28.8
28.8 - 43.2
28.8 - 43.2
38.4 - 52.8
38.4 - 52.8
38.4 - 52.8
38.4 - 52.8
48 - 66
48 - 66
Max
Curr.
A
60
120
200
300
60
120
200
300
167
250
134
200
27
53
88
125
22
43
70
100
14
27
44
65/70 (1)
29.3
42/46.5 (1)
7
13
22
32
17.6
25.6/28 (1)
Peak
Curr.
A(2)
300
160
240
100
80
16.5
31
50
105
33.3
70
25
20
42
Max.
Pwr.
W
198
396
660
990
300
600
1000
1500
1002
1500
1005
1500
324
648
1056
1500
330
645
1050
1500
336
648
1056
1560
1055
1512
336
624
1056
1536
1056
1536
Load
Reg
mV
30
30
40
60
30
30
40
60
60
60
60
60
96
96
100
72
120
120
120
90
192
192
150
144
150
150
384
384
300
288
360
360
Line
Reg
mV
20
20
20
36
20
20
20
36
36
36
36
40
48
48
48
48
60
60
60
60
96
96
96
96
144
144
192
192
192
192
240
240
Ripple
Noise
mV
120
120
120
150
120
120
120
150
150
150
150
150
120
120
150
150
150
150
150
150
150
150
150
200
200
200
200
200
200
200
400
400
Overvoltage
V
4.13 - 4.95
4.13 - 4.95
4.13 - 4.62
4.12 - 4.62
6.25 -7.25
6.25 -7.25
6.25 - 7.0
6.25 - 7.0
7.5 - 8.4
7.5 - 8.4
9.38 - 10.5
9.37 - 10.5
15 - 17.4
15 - 17.4
15 - 17.4
15 - 17.4
18.8 - 21.8
18.8 - 21.8
18.8 - 21.8
18.7 - 21.8
30 - 34.8
30 - 34.8
30 - 34.8
30 - 34.8
45 - 49.7
45 - 49.7
55.2 - 64.8
55.2 - 64.8
55.2 - 64.8
55.2 - 64.8
69 - 75
69 - 75
Eff.
typ
% (1)
74/77
75/78
71/73
72/75
79/82
80/83
76/78
77/81
79/81
79/82
80/82
81/83
80/83
80/83
83/85
82/85
82/85
82/85
83/85
83/87
82/85
82/85
85/87
84/88
85/88
84/88
82/85
82/85
86/88
86/90
85/88
86/90
Notes
(1) 100/200VAC
(2) 200-265VAC Input, 10s maximum on time with 35% duty cycle
(3) Use program input (PV) to adjust from 20-120% of nominal (20-110% for 48V & 60V models)
Options
Other Industrial Products
Suffix
Blank
/A
HWS
LZSA
SWS
DPP, DLP & DSP
/PV
/HD
/ME
/RY
Description
HWS300-1500 the cover is fitted as standard
Not Applicable
HWS300-1500 the cover is fitted as standard
HWS300, 600 (Standard on HWS1000 & 1500):
1-6V program voltage input to adjust output 20-120% of nominal
(20-110% for 48V) (12V-48V models only)
See HWS50-1500/HD Datasheet for details.-40 to +71(74)°C
operation, conformally coated PCBs
See HWS30-1500/ME Datasheet for details. UL60601-1,
EN60950-1 medical certification
ISA 12.12.01 (UL1604) - Class 1 Div 2 with dry contact relay DC
Good signal (300W, 600W and 1500W 24V output models only,
no UL508 certification, no remote on/off function.)
1-800-526-2324 • www.us.tdk-lambda.com/lp/
15W to 150W single output
500W to 1500W Single output
50W to 1000W, low cost
10W to 480W DIN Rail Mount
For Additional Information, please visit
us.tdk-lambda.com/lp/products/hws-series.htm
62
Revision C5: Nov 2013
Similar pages