LITTELFUSE KLK1

Axial Lead and Cartridge Fuses
Midget
AC Fast-Acting Type KLK Series
U® L
Fast-acting fuses designed for use in circuits with high AC fault current
capacity or where military approval is required.
ELECTRICAL CHARACTERISTICS:
% of Ampere
Rating
135%
200
Ampere
Rating
1/10 –30
1/10–30
Opening
Time
1 hour, Maximum
2 minutes, Maximum
AGENCY APPROVALS: Listed by Underwriters Laboratories and
Certified by CSA from 3/10 through 30 amperes.
INTERRUPTING RATING:
100,000 amperes (capable of 200,000) at 600VAC.
MILITARY TYPE F60C INTERRUPTING RATINGS:
200,000 amperes at 500VAC
150,000 amperes at 500VDC
FUSES TO MIL SPEC: See F60C type in Military Section.
PATENTED
®
QPL
ORDERING INFORMATION:
Cartridge
Catalog
Number
KLK 1/10
KLK 1/8
KLK 2/10
KLK 1/4
KLK 3/10
KLK 1/2
KLK 3/4
KLK 1
KLK 11/2
KLK 2
KLK 21/2
KLK 3
KLK 31/2
KLK 4
KLK 5
KLK 6
KLK 7
KLK 8
KLK 9
KLK 10
KLK 12
KLK 15
KLK 20
KLK 25
KLK 30
Ampere
Rating
.100
.125
.200
.250
.300
.500
.750
1
1.5
2
2.5
3
3.5
4
5
6
7
8
9
10
12
15
20
25
30
Nominal
Resistance
Cold Ohms
85.5
65.0
30.9
22.0
16.2
7.99
.398
.249
.132
.129
.0989
.0773
.0613
.0511
.0357
.0261
.0205
.0194
.0166
.0128
.0103
.0073
.00421
.00302
.002816
Voltage
Rating
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
1/8A
2/10A
1/4A
3/10A
1/2A
3/4A
1A
1 1/2A
2A
2 1/2A
3A
3 1/2A
4A
5A
6A
7A
8A
9A
10A
12A
15A
20A
25A
30A
Average Time Current Curves
1000
38.1
(1.50")
10.31
(.406")
TIME IN SECONDS
100
10
1
0.1
0.01
.1
1
10
CURRENT IN AMPERES
440
w w w. l i t t e l f u s e . c o m
100
1000