COMMANDER CLASS - CHASSIS MOUNT WITH LEAD WIRES POWER TRANSFORMER 1. Standard 6” Lead Length 2. 3. Electrical Specifications A. Maximum Power: 100VA B. Input Voltage and Frequency: 115V, 115/230V or 230V 50/60Hz C. Voltage Regulation: 8% TYP @ full load to no load D. Temperature Rise: 45C TYP E. Insulation Resistance: < 1 MEG ohm F. Hi-Pot: 2500Vrms 1 minute @ Pri to Sec 2500Vrms 1 minute @ Pri to Core 1500Vrms 1 minute @ Sec to Core Marking: Ensign Corp, part number (see table), date code Safety: UL/cUL 5085-2 Recognized (File E47299) UL 1446 Recognized Insulation System (File E95662) Part Number Primary Schematics Single Input (Specify 115V or 120V Single Input (Specify 230V or 240V) Single Input (277V) Tapped Input WHT=COM BLK=120 VIO=277V Dual Input (Specify 115/230V or 120/240V) 115V 115/230V 230V Secondary L100-1-510X L100-2-510X L100-3-510X 10VCT @ 10A L100-1-512X L100-2-512X L100-3-512X 12.6VCT @ 8.0A L100-1-516X L100-2-516X L100-3-516X 16VCT @ 6.25A L100-1-520X L100-2-520X L100-3-520X 20VCT @ 5.0A L100-1-524X L100-2-524X L100-3-524X 24VCT @ 4.0A L100-1-528X L100-2-528X L100-3-528X 28VCT @ 3.6A L100-1-536X L100-2-536X L100-3-536X 36VCT @ 2.8A L100-1-548X L100-2-548X L100-3-548X 48VCT @ 2.0A L100-1-556X L100-2-556X L100-3-556X 56VCT @ 1.8A L100-1-620X L100-2-620X L100-3-620X 120VCT @ 850mA Secondary Schematics POWER TRANSFORMER COMMANDER CLASS Single Output Center-Tapped Output Dual Output CONTENTS OF THIS DRAWING ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE Ensign Corporation L100-1-XXXX L100-2-XXXX L100-3-XXXX Dim: Inches Sheet 1 of 1 201 ENSIGN RD., BELLEVUE, IA 52031 PROPRIETARY NOTICE: THIS DRAWING PRINT OR DOCUMENT AND SUBJECT MATTER DISCLOSED HEREIN ARE PROPRIETARY ITEMS TO WHICH ENSIGN RETAINS THE EXCLUSIVE RIGHT OF DISSEMINATION, MANUFACTURE AND SALE. THIS DRAWING, PRINT OR DOCUMENT IS SUBMITTED IN CONFIDENCE FOR CONSIDERATION BY THE RECIPIENT ALONE UNLESS PERMISSION FOR FURTHER DISCLOSURE IS EXPRESSLY GRANTED IN WRITING