Littelfuse LPS1T60R2KGN2AF3U Lps series powr-switch Datasheet

LPS Series POWR-SWITCH
STANDARD FEATURES
NEW
■
600V 3-pole fuse power switch
■
200,000 RMS interrupting rating
■
Shunt trip 120V
■
Control power terminal block
■
Ground lug per NEC
■
Class J fuse block
■
NEMA 1 enclosures
OPTIONAL FEATURES
The Littelfuse POWR-Switch provides a simple and economical solution for applications that require selective coordination and shunt trip capabilities. Common applications include
elevator circuits, data processing rooms, and building emergency systems.
By utilizing Class J time delay fuses, the POWR-Switch is
easily coordinated with other system overcurrent devices.
The shunt trip capability allows the POWR-Switch to meet
the ANSI/ASME standard that requires power to be automatically disconnected before water is turned on by the fire safety system. The POWR-Switch also features pre-wired control
circuits that can help reduce installation costs.
148
■
Control power transformer with fuses and blocks
■
Fire safety interface relay
■
Key to test switch
■
Pilot light ”On”
■
Isolated neutral lug
■
Mechanical interlock auxilliary contact for hydraulic elevators with automatic recall (5 amp 120 VAC rated)
■
Fire alarm voltage monitoring relay
■
NEMA 3R, 4, and 12 enclosures
BENEFITS
■
Optional features offer flexibility for a variety of applications
■
UL Listed package
■
Lower installation costs than systems with many separate
components
■
Pre-wired control circuits lower installation time
■
Lockable Operating handle meets all code and safety
requirements
■
No confusion over which building trade is supplying the
components
■
POWR-Switch is a single unit...which makes procurement
easier than systems with multiple components
LPS Series POWR-SWITCH
ORDERING INFORMATION
Complete catalog numbers consist of switch catalog numbers and the desired options. See example below.
Example Catalog Number:
LPS
Littelfuse
Switch Catalog
Number
Control Power
Transformer
Std. 100VA with
PRI & SEC
Fuse (120V
Sec.)
Catalog
T8
R1
K
Fire Safety
Interface Relay
(3PDT, 10amp,
120V)
Option
N1
U = Littelfuse Catalog Number LPS1T48R1KN1U
Key to Test
Switch
Option
Pilot Light
“ON”
Option
Isolated Neutral
Lug
Option
Mechanical Interlock
Auxilliary Contact
forHydraulic
Elevators w/
Automatic Recall (5
amp 120 VAC rated)
Option
Fire Alarm
Voltage
Monitoring Relay
(Tp Monitor
Shunt Trip
Voltage)
Option
Optional
Enclosures
Option
Option
No
Rating
Rating
Code
Rating
Code
Rating
Code
Rating
Code
Rating
Code
Rating
Code
Rating
Code
Rating
Code
LPS3
30A
208V
T20
24 VDC Coil
R2
120V
K
Red
R
30–60A
N6
1 NO & 1 NC
A
Single Pole
F1
NEMA 3R
U
LPS6
60A
240V
T24
120 VAC Coil
R1
Green
G
100A
N1
2 NO & 2 NC
B
Three Pole
F3
NEMA 4
Y
LPS1
100A
480V
T48
White
W
NEMA 12
Z
LPS2
200A
600V
T60
LPS4
400A
200A
N2
400A
N4
Note: Desired options must appear in the order shown above. Typical options include Control Power Transformer, Fire Safety Interface
Relay, Mechanical Interlock Auxiliary Contact and Fire Alarm Voltage Monitoring Relay.
SPECIFICATIONS
Approvals: UL Listed and CSA Certified
Rating: 30A, 60A, 100A, 200A, 400A
Shunt Trip Ratings:
Amp
Rating
30–400
Voltage
Rating
120V, 60Hz
Max
Inrush
4A
Max
Ontime
1.5 cycles
Momentary
Inrush
140VA
ENCLOSURE DIMENSIONS
Catalog
Series
Amp
Rating
NEMA 1
Dimensions
NEMA 3R
Dimensions
NEMA 4, 12
Dimensions
Lug
Size
LPS3
30
24”H x 20”W x 9”D
24”H* x 20”W x 8”D
24”H x 20”W x 10”D
#14 - #8 AL or CU
LPS6
60
24”H x 20”W x 9”D
24”H* x 20”W x 8”D
24”H x 20”W x 10”D
#14 - #8 AL or CU
LPS1
100
24”H x 20”W x 9”D
24”H* x 20”W x 8”D
24”H x 20”W x 10”D
#8 - 1/0 AL or CU
LPS2
200
30”H x 20”W x 9”D
30”H* x 20”W x 8”D
24”H x 20”W x 10”D
#6 - 250kcmil AL or CU
LPS4
400
48”H x 36”W x 12”D
Contact Factory
Contact Factory
Contact Factory
Note: Over-size enclosures used to accomodate control power transformer, interface relay and terminal blocks.
*For NEMA 3R enclosures add 2 inches to height for mounting tabs.