Littelfuse M23301.6 Axial lead and cartridge fuses - designed to ul/csa standard Datasheet

Axial Lead and Cartridge Fuses
Designed to UL/CSA Standards
RoHS
Pb
5 x 20 mm Medium-Acting Fuse 233 Series
U® L
®
• Designed to UL/ CSA/ANCE 248 Standard.
• Available in Cartridge, Axial and Radial Lead Format.
• Available in ratings of 1A to 10A.
• RoHS compliant and Lead-Free version available, add XP suffix to
standard catalog number
ELECTRICAL CHARACTERISTICS:
% of Ampere
Rating
100%
135%
200%
Ampere
Rating
1–3.5
4–10
1–10
1–10
Opening
Time
4 hours, Minimum
1 hour, Minimum
3 sec., Min.; 1 hour Max.
0.4 sec., Min.; 4 sec., Max.
INTERRUPTING RATING:
10,000 amperes at 125 VAC, 0.7-0.8 power factor
ORDERING INFORMATION:
RoHS compliant and Lead-Free version available, add XP suffix to
standard catalog number
Catalog
Number
0233 001
0233 1.25
0233 01.6
0233 002.
0233 02.5
0233 003.
0233 3.15
0233 03.5
0233 004.
0233 005.
0233 006.
0233 06.3
426
Ampere
Rating
1
1.25
1.6
2
2.5
3
3.15
3.5
4
5
6
6.3
Voltage
Rating
125
125
125
125
125
125
125
125
125
125
125
125
Nominal
Resistance
Cold Ohms
0.18
0.13
0.088
0.068
0.052
0.043
0.038
0.034
0.032
0.022
0.018
0.017
Nominal
Melting
I2t A2Sec
2.03
3.48
6.31
10.2
17.5
27.0
30.6
37.3
53.0
92.4
135
156
ENVIRONMENTAL SPECIFICATIONS:
Operating temperature: -55˚C to 125˚C
Thermal Shock: MIL-STD-202F Method 107G, Test Condition B: (5
cycles –65°C to +125°C)
Vibration: MIL-STD-202F Method 201A
Humidity: MIL-STD-202F Method 103B, Test Condition A. high relative
humidity (95%) and elevated temperature (40°C) for 240 hours.
Salt Spray: MIL-STD-202F Method 101D, Test Condition B
PHYSICAL SPECIFICATIONS:
Material: Body: Glass
Cap: Nickel Plated Brass
Leads: Tin Plated Copper
Terminal Strength: MIL-STD-202F Method 211A,
Test Condition A
Solderability: Reference IEC 60127 Second Edition 2003-01 Annex A
Product Marking: Cap 1: current and voltage rating.
Cap 2: Agency approval markings.
Packaging: Available in Bulk (v=5, H=100, M=1000 pcs/pkg) or on
Tape/Reel (MRET1=1000 pcs/reel).
w w w. l i t t e l f u s e . c o m
Axial Lead and Cartridge Fuses
Designed to UL/CSA Standards
RoHS
Pb
5 x 20 mm Medium-Acting Fuse 233 Series
U® L
®
Agency Approvals
Agency Approvals
Certificate No. Cartridge
NBK280602-E10480
NBK290502-E10480
Leaded
NBK280602-E10480
NBK290502-E10480
Ampere Range
C
I
1A – 5A 125V 10000A
6A & 6.3A 125V 500A
D
J
1A – 5A 125V 10000A
6A & 6.3A 125V 500A
20+0.5
0233 0001
5.2+0.1
-0.2
5.1+0.6
40
0233000XE2
Certificate No. SU05001-2010
5.1+0.6
22.5 MAX
5.8 MAX
.65*
Notes:
* Ratings above 6.3A
have 0.8 mm dia lead
1 For RoHS compliant parts
add suffix 'XP'
2 For RoHS compliant parts
add suffix 'P'
Average Time Current Curves
10000
1000
100
11
10
AXIAL LEAD AND
CARTRIDGE FUSES
029862
LR1422-01
All dimensions in mm
2A
2.5A
3A
3.15A
3.5A
4A
5A
6A
6.3A
File No.
Cert. Class No.
1A – 6.3A
1.25A
1.6A
E10480
JDYX
1A
®
Listed File No.
Guide No.
TIME IN SECONDS
U® L
1
0.1
0.01
0.001
1
10
100
1000
CURRENT IN AMPERES
w w w. l i t t e l f u s e . c o m
427