Omron MKS2PI1-D General-purpose relay Datasheet

General-purpose Relays
MK-S (New Models)
CSM_MK-S_DS_E_4_1
New Super MK Relays.
Models with Latching Lever Added to
the Series.
• Same mounting and internal wiring as the previous Super
MK Relays
• Built-in mechanical indicator enables checking contact
operation.
• Two modes can be used to check circuits for models with
latching lever.
• Nameplate provided on models with latching lever.
• All materials are RoHS compliant.
• UL and IEC (TÜV) certification.
Features
Models with Latching Lever
Operating Method for Latching Lever
Operation indicator *
Relay in
Normal Operation
Nameplate
For Momentary
Operation
For Lock
Operation
Slide the latching lever
to the first position,
then press the yellow
button with an
insulated tool to
operate the contact.
Slide the latching
lever to the second
position.
(The contact is now in
the locked position.)
Mechanical indicator
Latching lever
DC: Blue
AC: Red
Yellow
button
* The operation indicator is built in only on specified models.
Example of Applications of Models with Latching
Levers
Operation checks in relay sequence circuits
Model Number Structure
Model Number Legend
MKS@@@@@-@-@
1 2 3 4 5
6
7
1. Contact Form
2: DPDT
3: 3PDT
5. Coil Polarity
Blank: Standard
1:
Reverse polarity (DC coil only)
2. Terminals
P: Plug-in
6. Surge Absorption
Blank: Standard
D:
Surge absorber diode (DC coil only)
V:
Surge absorber varistor (AC coil only)
3. Mechanical Indicator/Test Button
Blank: Mechanical indicator
I:
Mechanical indicator and lockable test button
4. LED Indicator
Blank: Standard
N:
LED indicator
7. Internal Connections
Blank: Standard
2 or 5: Non-standard connections (Refer to “Terminal
Arrangement and Internal Connection (Bottom View)”.)
8. Rated Voltage
(Refer to “Coil Ratings”.)
1
MK-S
Ordering Information
List of Models
Type
Contact
form
Terminals
DPDT
Standard
Models
Internal connections
(See note 3.)
DPDT
Models with
LED Indicator
(See note 2.)
3PDT
DPDT
Models with
Diode
(See note 2.)
3PDT
Plug-in
DPDT
Models with
LED Indicator
and Diode
3PDT
DPDT
Models with
Varistor
3PDT
DPDT
Models with
LED Indicator
and Varistor
3PDT
With mechanical indicator
Coil ratings
and lockable test button
Standard
MKS2P
MKS2PI
Non-standard
MKS2P-2
MKS2PI-2
Standard
3PDT
With mechanical indicator
Non-Standard
MKS3P
MKS3PI
MKS3P-2
MKS3PI-2
MKS3P-5
MKS3PI-5
Standard
MKS2PN(1)
MKS2PIN(1)
Non-standard
MKS2PN(1)-2
MKS2PIN(1)-2
Standard
MKS3PN(1)
MKS3PIN(1)
MKS3PN(1)-2
MKS3PIN(1)-2
Non-Standard
MKS3PN(1)-5
MKS3PIN(1)-5
Standard
MKS2P(1)-D
MKS2PI(1)-D
Non-standard
MKS2P(1)-D-2
MKS2PI(1)-D-2
Standard
MKS3P(1)-D
MKS3PI(1)-D
MKS3P(1)-D-2
MKS3PI(1)-D-2
Non-Standard
MKS3P(1)-D-5
MKS3PI(1)-D-5
Standard
MKS2PN-D
MKS2PIN-D
Non-standard
MKS2PN-D-2
MKS2PIN-D-2
Standard
MKS3PN-D
MKS3PIN-D
MKS3PN-D-2
MKS3PIN-D-2
MKS3PN-D-5
MKS3PIN-D-5
Standard
MKS2P-V
MKS2PI-V
Non-standard
MKS2P-V-2
MKS2PI-V-2
Standard
MKS3P-V
MKS3PI-V
MKS3P-V-2
MKS3PI-V-2
Non-Standard
Non-Standard
Standard
MKS3P-V-5
MKS3PI-V-5
MKS2PN-V
MKS2PIN-V
Non-standard
MKS2PN-V-2
MKS2PIN-V-2
Standard
MKS3PN-V
MKS3PIN-V
MKS3PN-V-2
MKS3PIN-V-2
MKS3PN-V-5
MKS3PIN-V-5
Non-Standard
AC/DC
AC/DC
DC
DC
AC
AC
Note: 1. When ordering, add the rated voltage to the model number. Rated voltages are given in the coil ratings table in the specifications.
Example: MKS3P 24 VDC
Rated voltage
2. The DC coil comes in two types: standard coil polarity and reverse coil polarity.
Refer to Terminal Arrangement and Internal Connections (Bottom View).
Example: MKS2PIN1-2 24 VDC
Reverse coil polarity
3. Refer to Terminal Arrangement and Internal Connections (Bottom View) for non-standard internal connections.
List of Models (Order Separately)
Item
Track-mounted
Socket
Type
Model
8-pin
PF083A-E
11-pin
PF113A-E
8-pin
PF083A-D
11-pin
PF113A-D
Hold-down Clip
(For PF083A-E and PF113A-E)
PFC-A1
2
MK-S
Specifications
Ratings
Coil Ratings
Rated current
Rated voltage
AC
DC
Note: 1.
2.
3.
4.
50 Hz
60 Hz
Coil resistance
6V
443 mA
385 mA
3.1 Ω
12 V
221 mA
193 mA
13.7 Ω
24 V
110 mA
96.3 mA
48.4 Ω
100 V
26.6 mA
23.1 mA
760 Ω
110 V
24.2 mA
21.0 mA
932 Ω
200 V
13.3 mA
11.6 mA
3,160 Ω
220 V
12.1 mA
10.5 mA
3,550 Ω
230 V
10.0 mA
11.5 mA
4,250 Ω
240 V
11.0 mA
9.6 mA
4,480 Ω
6V
224 mA
26.7 Ω
12 V
112 mA
107 Ω
24 V
55.8 mA
430 Ω
48 V
28.1 mA
1,710 Ω
100 V
13.5 mA
7,390 Ω
Must operate
voltage
Must release
voltage
Max. voltage
Power
consumption
Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz
30% min. of rated
voltage at 60 Hz
25% min. of rated
voltage at 50 Hz
110% of rated
voltage
80% max. of
rated voltage
15% min. of rated
voltage
Approx. 1.4 W
110 V
12.3 mA
8,960 Ω
The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/−20% for AC rated current and
±15% for DC coil resistance.
Performance characteristic data are measured at a coil temperature of 23°C.
The maximum voltage is one that is applicable instantaneously to the Relay coil at 23°C and not continuously.
For DC-operated Relays with the LED indicator built-in, add an LED current of approx. 5 mA to the rated current.
Contact Ratings
Load
Resistive load
(cosφ = 1)
Contact mechanism
Single
Contact material
AgSnIn
NO
10 A, 250 VAC
10A, 30 VDC
NC
5 A, 250 VAC
5 A, 30 VDC
Rated load
Rated carry current
10 A
Max. switching voltage
250 VAC, 250 VDC
Max. switching current
Max. switching power
Inductive load
(cosφ = 0.4)
7 A, 250 VAC
10 A
NO
2,500 VA/300 W
NC
1,250 VA/150 W
3
MK-S
Characteristics
Contact resistance
100 mΩ max.
Operate time
AC: 20 ms max.
DC: 30 ms max.
Release time
20 ms max. (40 ms max. for built-in Diode Relays)
Max. operating frequency
Mechanical: 18,000 operations/h
Electrical: 1,800 operations/h (under rated load)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC 50/60 Hz for 1 min between coil and contacts
1,000 VAC 50/60 Hz for 1 min between contacts of same polarity and terminals of the same polarity
2,500 VAC 50/60 Hz for 1 min between current-carrying parts, non-current-carrying parts, and opposite polarity
Insulation method
Basic insulation
Impulse withstand voltage
4.5 kV between coil and contacts (with 1.2 × 50 μs impulse wave)
3.0 kV between contacts of different polarity (with 1.2 × 50 μs impulse wave)
Pollution degree
3
Rated insulation voltage
250 V
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock resistance
Destruction: 1,000 m/s2 (approx. 100 G)
Malfunction: 100 m/s2 (approx. 10 G)
Endurance
Mechanical: 5,000,000 operations min. (at 18,000 operations/h under rated load)
Electrical: 100,000 operations h. (at 1,800 operations/h under rated load)
Failure rate P level (reference value) 10 mA at 1 VDC
Ambient temperature
Operating: –40 to 60°C (with no icing or condensation)
Ambient humidity
Operating: 5% to 85%
Weight
Approx. 90 g
Note: 1. The values given above are initial values.
2. P level: λ60 = 0.1 × 10-6/operation
3. Ambient temperature of models with LED indicator is −25 to 60°C.
Approved Standards
IEC Standard/TUV Certification: IEC61810-1
(Certification No. R50104853)
UL508 (File No. E41515)
Coil ratings
Contact ratings
Operations
Coil ratings
10 A, 250 V AC 50/60 Hz (Resistive)
N.O.
10 A, 30 V DC (Resistive)
100,000
contact
7 A, 250 V AC 50/60 Hz (General Use)
6 to 110 VDC
6 to 240 VAC
Contact ratings
6, 12, 24, 48,
100, 110 VDC
6, 12, 24, 100,
110, 200, 220,
240 VAC
10 A, 250 V AC 50/60 Hz (Resistive)
N.C.
10 A, 30 V DC (Resistive)
100,000
contact
7 A, 250 V AC 50/60 Hz (General Use)
CSA Standard: CSA Certification by
: CSA C22.2 No. 14
Operations
N.O.
contact
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
100,000
7 A, 250 V AC 50/60 Hz (General Use)
N.C.
contact
5 A, 250 V AC 50/60 Hz (Resistive)
5 A, 30 V DC (Resistive)
100,000
7 A, 250 V AC 50/60 Hz (General Use)
Note: When Relays are mounted on the PF083A-E or PF113A-E, the
maximum carrying current is 9 A.
Engineering Data
Maximum Switching Power
Rated Carry Current vs. Ambient Rated Temperature
Switching current (A)
Rated carry current (A)
Reference Data
100
50
30
DC resistive load
with NO contact
AC resistive load
with NO contact
10
UL derating curve
10
5
AC inductive
load
(cosφ = 0.4)
5
3
DC resistive
load with
NC contact
1
10
30
AC resistive load
with NC contact
50
100
300
500 1.000
Switching voltage (V)
0
−40
−20
0
20
40
60
80
Ambient temperature (°C)
Note: The lower limit of the ambient operating temperature for models with built-in operation
indicators is −25°C.
4
MK-S
Dimensions
(Unit: mm)
Models without Latching Lever
Models with Latching Lever
34.5 max.
34.5 max.
34.5 max.
0.8
52.5 max.
34.5 max.
0.8
52.5 max.
Sockets
See below for Socket dimensions.
Socket
Maximum carry
current
Surface-mounting Socket (for track or screw mounting)
Finger-protection models
10 A
--5A
PF083A-E
PF083A-D
PF083A
PF113A-E
PF113A-E-D
PF113A
2 poles
3 poles
Note: Use the Surface-mounting Sockets (i.e., finger-protection models) with “-E” at the end of the model number. When using the PF083A and
PF113A, be sure not to exceed the Socket's maximum carry current of 5 A. Using at a current exceeding 5 A may lead to burning. Round
terminals cannot be used for finger-protection models. Use Y-shaped terminals.
PF083A-E (Conforming to EN 50022)
PF113A-E (Conforming to EN 50022)
Terminal Arrangement
Eight, M3.5 × 7 sems
7
Terminal Arrangement
Eleven, M3.5 × 7 sems
4
7
52 max.
4
35.4
52 max.
33
41 max.
3.5
35.4
2
21 max.
Mounting Holes
Two, M4 or two 4.5-dia. holes
33±0.2
4
34
42.8 max.
3.5
2
31 max.
Mounting Holes
Two, M4 or two 4.5-dia. holes
33±0.2
5
MK-S
PF113A-D
PF083A-D
8
Terminal Arrangement
24
6
5.5
22
5
12
4
8
Terminal Arrangement
14
3
32 24 21 22 12
8 7 6 5 4
5.5
27
4
27
4
Eight, M4 screws
7
A2
8
21
1
11
Eight, M4 screws
2
A1
9 10
2 3
34 A2 11 1 A1 14
31 11
Mounting Holes
65
65
Mounting Holes
Two, M4 or two 4.5-dia. hole
Two, M4 or two 4.5-dia. hole
30
30
38
38
Hold-down Clips
PFC-A1
(2 pieces per set)
4.6
60.8
6
62
4.5
Mounting Tracks
PFP-100N, PFP-50N
(Conforming to EN 50022)
PFP-100N2
(Conforming to EN 50022)
16
7.3±0.15
4.5
4.5
35±0.3
15
25
25
10
25
10
1000 (500)*
25 *
35±0.3 27
27±0.15
1
15
25
25
10
25
1000±4
25 15
10
24
29.2
1
1.5
* A total of twelve 25 × 4.5 elliptic holes is provided with six
holes cut from each track end at a pitch of 10 mm.
* This dimension applies to the PFP-50N Mounting Track.
Mounting Height with Sockets
Surface-mounting Sockets
77.8
(See
note.)
Three
poles
Two
poles
74.3
PF083A(-E)
87.8
(See
note.)
84.3
PF113A(-E)
Note: PF083A(-E) and PF113A(-E) allow either track or screw mounting.
6
MK-S
Terminal Arrangement and Internal Connection (Bottom View)
Standard Models
(AC/DC Coil)
MKS2P(I)
4
5
3
4
6
2
7
1
MKS2P(I)-2
5
3
6
2
8
7
1
MKS3P(I)
6
5
10
2
MKS2P(I)N
4
MKS2P(I)N-2
5
4
6
3
6
2
7
2
7
1
8
1
6
5
MKS2P(I)N
4
MKS2P(I)N-2
5
4
9
3
6
3
6
2
7
2
7
1
8
1
6
MKS2P(I)N1
4
MKS2P(I)N1-2
5
4
6
3
6
2
7
2
7
1
8
1
6
9
3
Standard Models
(DC Coil:
Standard Polarity)
MKS2P(I)-D
4
MKS2P(I)-D-2
5
4
5
3
6
3
6
2
7
2
7
1
8
1
6
5
3
9
MKS2P(I)1-D
4
MKS2P(I)1-D-2
5
4
6
3
6
2
7
2
7
1
8
1
6
5
3
9
Models with
LED indicator
(DC Coil)
MKS2P(I)N-D
4
5
3
4
6
2
7
1
MKS2P(I)N-D-2
8
5
3
6
2
7
1
8
3
6
5
3
9
2
10
11
9
2
10
1
9
3
2
10
11
11
MKS3P(I)-D-5
6
7
4
8
3
9
2
10
11
MKS3P(I)1-D-5
6
7
8
4
9
3
2
10
11
MKS3P(I)N-D-5
6
5
8
1
8
1
7
4
7
3
11
6
5
8
6
4
10
MKS3P(I)N-D-2
7
4
1
2
11
MKS3P(I)N1-5
5
9
1
MKS3P(I)N-D
10
1
8
11
9
2
7
4
10
1
6
5
8
11
MKS3P(I)1-D-2
7
3
10
1
8
2
8
9
2
6
4
5
7
3
7
4
6
8
11
MKS3P(I)1-D
5
3
MKS3P(I)-D-2
10
MKS3P(I)N-5
11
4
11
1
10
5
8
1
Models with Diode
(DC Coil:
Reverse Polarity)
2
7
4
2
8
9
1
MKS3P(I)-D
9
10
2
5
8
11
8
1
7
3
10
1
6
4
7
3
11
MKS3P(I)N1-2
5
8
6
4
10
2
7
4
2
8
9
1
MKS3P(I)N1
5
8
11
MKS3P(I)N-5
5
7
3
10
5
3
6
4
11
10
1
10
5
9
3
9
2
11
MKS3P(I)N-2
8
1
Models with
LED Indicator and Diode
(DC Coil:
Reverse Polarity)
2
7
4
2
8
9
3
1
MKS3P(I)N
5
8
11
8
5
7
4
10
5
3
6
5
8
1
Models with Diode
(DC Coil:
Standard Polarity)
MKS3P(I)N-2
7
3
11
1
6
4
10
2
7
4
2
8
9
11
MKS3P(I)N
5
3
8
3
MKS3P(I)-5
5
7
4
9
3
6
5
8
1
Models with
LED Indicator
(AC Coil)
7
4
8
MKS3P(I)-2
7
8
4
9
3
2
10
1
11
7
MK-S
Models with Varistor
(AC Coil)
MKS2P(I)-V
4
MKS2P(I)-V-2
5
4
5
3
6
3
6
2
7
2
7
1
8
1
MKS3P(I)-V
6
5
3
9
2
MKS2P(I)N-V
4
MKS2P(I)N-V-2
5
4
6
3
6
2
7
2
7
1
8
1
8
6
2
3
9
2
10
11
6
8
9
3
2
10
1
8
9
2
10
11
11
1
MKS3P(I)N-V-5
6
5
7
4
7
3
11
MKS3P(I)N-V-2
5
8
6
4
10
1
7
4
1
9
11
MKS3P(I)N-V
5
8
3
MKS3P(I)-V-5
5
7
4
10
5
3
6
5
8
1
Models with
LED indicator and
Varistor
(AC Coil)
7
4
8
MKS3P(I)-V-2
7
4
8
3
9
2
10
1
11
Safety Precautions
Refer to Safety Precautions for All Relays.
Safety Precautions for Correct Use
Installation
Mount the MK-S with the marking at the bottom.
Handling
Check the coil polarity of models with built-in operation indicator (DC operation coil) and wire them correctly .
Test Button
Do not use the test button for any purpose other than testing. Be sure not to touch the test button accidentally as this will turn the contacts ON.
Before using the test button, confirm that circuits, the load, and any other connected item will operate safely.
Check that the test button is released before turning ON relay circuits.
If the test button is pulled out too forcefully, it may bypass the momentary testing position and go straight into the locked position.
Use an insulated tool when you operate the test button.
Models with test buttons or LED indicators fulfill the requirements for reinforced insulation between live parts and the front of cover only when the
Relay is in a complete condition, i.e. with the nameplate, nameplate frame, test button, and slider in place. If any of these parts are removed, only
the requirements for basic insulation are fulfilled.
8
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2010.2
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2010 All Right Reserved.
Similar pages