EPCOS V13

Surge Arrester
2-Electrode-Arrester
V13-A500XN
Ordering code: B88069X6940C251
DC spark-over voltage 1) 2)
400 ... 750
V
Impulse spark-over voltage
at 5 kV/µs
- for 99 % of measured values
(wave 1.2/50 µs; 6 kV)
< 1500
V
Insulation resistance at 100 Vdc
>1
GΩ
< 2.5
pF
40
6
15
30
45
60
kA
kA
kA
kA
kA
kA
1 operation
10/350 µs
+ 1 operation
10/350 µs
+ 1 operation
10/350 µs
Nominal alternating discharge current (50 Hz, 0.2 s)
1.2
3
6
300
kA
kA
kA
A
Max. follow-on current at 250 VRMS; 20 times
140
Apeak
Weight
~ 6,5
g
Operation and storage temperature
-40 ... +90
°C
Climatic category (IEC 60068-1)
40/ 90/ 21
Capacitance at 1 MHz
2)
Impulse discharge current
15 operations
+ 1 operation
+ 1 operation
+ 1 operation
+ 1 operation
+ 1 operation
8/20 µs
8/20 µs
8/20 µs
8/20 µs
8/20 µs
8/20 µs
500 YY O
Marking, black
500
YY
O
1)
2)
- Nominal voltage
- Year of production
- Non radioactive
At delivery AQL 0.65 level II, DIN ISO 2859
In ionized mode
AB E / AB PM
Issue 03, 26.04.2002
Page 1 of 2
Surge Arrester
2-Electrode-Arrester
V13-A500XN
Ordering code: B88069X6940C251
Not to scale
Dimensions in mm
Non controlled document
 EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless
otherwise agreed.
AB E / AB PM