EXTECH VT10

User's Guide
Multifunction Voltage Tester
Model VT10
Introduction
Congratulations on your purchase of the Extech VT10 Multifunction Voltage Tester. The
VT10 measures AC Voltage to 600V and DC Voltage to 400V with LED indicators, and
LEDs for positive and negative polarity. Additional features include audible continuity
beeper, low impedance mode for eliminating phantom voltages, and a built-in flashlight
to illuminate test connections during measurements. This meter is shipped fully tested
and with proper use will provide years of reliable service.
Safety
International Safety Symbols
This symbol, adjacent to another symbol or terminal, indicates the user
must refer to the manual for further information.
This symbol, adjacent to a terminal, indicates that, under normal use,
hazardous voltages may be present
Double insulation
Safety Precautions
1.
Improper use of this meter can cause damage, shock, injury or death. Read and
understand this manual before use.
2.
Ensure that any covers or battery doors are properly closed and secured before use.
3.
Inspect the condition of the test leads and the meter itself for any damage before
use.
4.
Do not exceed the rated input limits.
5.
Use great care when taking measurements greater than 25VAC rms or 35VDC.
These voltages are considered a shock hazard.
6.
Discharge capacitors and remove power from the DUT before Continuity tests.
7.
Remove the batteries from the meter if the meter is to be stored for long periods.
8.
Voltage measurement results on electrical outlets can be misleading because of the
difficulty in making a proper connection to the electrical contacts.
9.
NEVER apply voltage to the meter that exceeds the specified maximum:
Function
VAC, VDC,
Continuity
Input Protection Limits
Maximum Input
600VAC: 30 second max
400VDC: 30 second max
10.
USE EXTREME CAUTION when working with high voltages.
11.
ALWAYS discharge filter capacitors in power supplies and disconnect the power
when making continuity tests.
12.
ALWAYS disconnect the test leads before opening the cover to replace the battery.
13.
NEVER operate the meter unless the battery cover is in place and fastened
securely.
2
VT10 V2.0 08/06
Warranty
EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects
in parts and workmanship for one year from date of shipment (a six month limited warranty
applies on sensors and cables). If it should become necessary to return the instrument for
service during or beyond the warranty period, contact the Customer Service Department at
(781) 890-7440 ext. 210 for authorization or visit our website at www.extech.com for
contact information. A Return Authorization (RA) number must be issued before any
product is returned to Extech. The sender is responsible for shipping charges, freight,
insurance and proper packaging to prevent damage in transit. This warranty does not
apply to defects resulting from action of the user such as misuse, improper wiring,
operation outside of specification, improper maintenance or repair, or unauthorized
modification. Extech specifically disclaims any implied warranties or merchantability or
fitness for a specific purpose and will not be liable for any direct, indirect, incidental or
consequential damages. Extech's total liability is limited to repair or replacement of the
product. The warranty set forth above is inclusive and no other warranty, whether written or
oral, is expressed or implied.
Description
1
2
1.
Test Probe (-)
2.
Test Probe (+)
3.
Flashlight
4.
LED voltage level indicators
5.
LED (AC voltage indicator)
4
6.
LED (low impedance test indicator)
5
7.
LED (DC +V/-V polarity indicators)
8.
LED (continuity indicator)
9.
LED (AC/DC voltage indicators)
3
13
6
7
8
9
10. Low impedance button (+)
11. Flashlight button
10
12. Battery cover
11
13. Low impedance button (-)
12
3
VT10 V2.0 08/06
Operation
Always test the meter on a known live circuit before taking measurements
Voltage Measurement
1. Note: The voltage tester will turn on automatically when voltages
higher than 4.5V AC/DC are detected.
2. Touch the positive (+) and negative (-) test leads to the device or
circuit under test.
3. If the voltage is higher than 4.5V AC/DC, the voltage level LEDs will
light and display the reading.
For AC voltages, the LED and the “AC” LED will light in the display.
For DC voltages, the “DC” LED will light and the “+V” or “-V“ LED will
light to indicate polarity.
Note: The measurement time should not exceed 30 seconds. After 30
seconds the meter should be allowed to cool for 10 minutes.
4.
Single Lead AC Voltage Detection
To check for the presence of voltage (between 100V and 600V) using
only the positive test lead (+), touch the lead to the device or circuit
under test. If voltage is present, the LEDs will light.
Note: In this mode, the actual voltage is not displayed; only the
presence of voltage is detected.
Low Impedance Voltage Measurement
Due to the lowered internal impedance, capacitive voltage is
suppressed so that the reading shows the actual voltage
applied. This can be used to quickly identify phantom voltages.
1.
2.
3.
Hold the two test tips on the measuring points to be
tested.
Press the two low impedance test buttons
simultaneously.
The Low Impedance LED will light and the applied
voltage will be displayed on the LEDs.
Note: The maximum duty cycle in this mode is 5 seconds
for voltages up to 250V. Allow 10 minutes between each reading.
Note: Measuring from hot to ground may trip any GFCI equipped circuits.
Continuity Test
The tester can measure resistance and alert the user if the resistance value is less than
400kΩ.
1. Before taking a continuity test, make sure that power to the device or circuit under
test is off and that all capacitors are discharged.
2. Touch the test tips to the device under test.
3. If the resistance is less than 400kΩ., the tester will sound an audible alert and
the continuity LED will light.
Flashlight
Press and hold the
button to turn the flashlight on. Release the button to turn the flashlight off.
4
VT10 V2.0 08/06
Maintenance
Battery replacement
1. Disconnect the meter from any test device or circuit before
opening the tester.
2. Loosen the recessed Phillips head screw at the bottom of the
tester. Do not remove the screw.
3. Hold the meter and pull the lower portion of the meter off until
the batteries are exposed.
4. Replace the two ‘AAA’ batteries observing polarity and dispose
of the old batteries properly.
5. Slide the meter back together and replace the screw.
Cleaning and Storage
Before cleaning the tester, ensure that the test leads are not connected to any circuit or
device. Wipe the meter only with a damp cloth as needed. Do not apply abrasives, solvents,
or other cleaners to the surface of the meter. Store with the battery removed and avoid
extreme temperature and humidity.
Specifications
Voltage LED steps
AC: 24, 48, 120, 208, 240, 277, 480, 600
DC: 6, 12, 24, 36, 48, 110, 220, 400
ACV frequency range
50/60Hz
LED enable input voltage
>4.5V AC/DC
Accuracy
-30% to 0% of the indication
Range selection
Automatic
Max measuring current
≤1.2mA (600VAC); ≤1.0mA (400VDC)
Display delay
LED indication <0.1s
Input Impedance
1MΩ (approx)
Continuity test
Range 0 to 400kΩ, guaranteed on < 50kΩ; <10µA test
current;
Low impedance test
12-250VAC/DC; impedance <6kΩ;
Operation time:
30 seconds on/10 minute off duty cycle
Power supply
2 x “AAA” 1.5V alkaline batteries, 50mA max
Battery life
Approx. 8 hours continuous use typical
Operating Temperature
14 to 131 F (-10 to 55 C)
o
o
o
o
Storage Temperature
-22 to 140 F (-30 to 60 C)
Operating Humidity
10 to 85% RH (non-condensing)
Operating Altitude
7000 ft. (2000 meters) maximum
Safety
This meter is intended for origin of installation use and
protected, against the users, by double insulation per
EN61243-3 and IEC61243-3 to Category IV 600V and
Category III 1000V; Pollution Degree 2.
Approvals
CE, IP64
Dimensions
9.4 x 3 x 1.6” (240 x 78 x 40mm)
Weight
9.2oz (260g)
5
VT10 V2.0 08/06
Calibration and Repair Services
Extech offers repair and calibration services for the products we sell. Extech also provides
NIST certification for most products. Call the Customer Service Department for information
on calibration services available for this product. Extech recommends that annual
calibrations be performed to verify meter performance and accuracy.
Support Hotline (781) 890-7440
Tech support: Ext. 200; Email: [email protected]
Repair/Returns: Ext. 210; Email: [email protected]
Product specifications subject to change without notice
For the latest version of this User’s Guide, Software updates, and other
up-to-the-minute product information, visit our website: www.extech.com
Extech Instruments Corporation, 285 Bear Hill Rd., Waltham, MA 02451
Copyright © 2006 Extech Instruments Corporation
All rights reserved including the right of reproduction in whole or in part in any form.