SYSTEMSENSOR ZCK-1EG

INSTALLATION AND MAINTENANCE INSTRUCTIONS
ZCK-1, ZCK-1E, ZCK-1EG, ZCK-1EN and ZCK-50
Zonecheck Keyswitch for Control and Monitoring
of the Zonecheck Flow Switch Tester
Electrical Specifications
Operating Voltage:
Operating Temperature:
Operating Humidity:
Mounting Options:
Operation Modes:
LED Operation:
Tested to EN 61010-1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
ZCK-1: 120V, 60Hz; ZCK-1E, ZCK-1EG, ZCK-1EN and ZCK-50: 220VAC, 50Hz, 3w Max.
0°C to 49°C (32°F to 120°F)
5% to 95% RH (non-condensing)
Includes back box for surface or flush mounting.
For pre-wiring, use a 411/16˝ x 411/16˝ back box
Self-test: Wired locally
Group test: Interconnected
Ready state: No LED
Test initiation: Green LED
Flow switch activation: Red LED (ZCK-1), Green LED (ZCK-1E, ZCK-1EG, ZCK-1EN and ZCK-50)
FOR INTERCONNECTING MULTIPLE ZONECHECK UNITS
WIRING DIAGRAM FOR STAND ALONE APPLICATION
WARNING
GND. as specified, it may become impaired.
If this product TO
is EARTH
not used
OR ATTACH TO
JUNCTION BOX
WIRING
}
}
GND
AC
AC
PUMP
DIAGRAM
PUMP
AC POWER
PUMP
TO EARTH GND.
OR ATTACH TO
JUNCTION BOX
}
}
FOR
FOR STAND ALONE APPLICATION
WF INPUT
INTER-CONNECT
TO EARTH GND.
OR ATTACH TO
JUNCTION BOX
AC GROUND
GND
AC
AC
WATERFLOW
PUMP
DETECTOR
PUMP
GND
AC
AC
PUMP
INTERCONNECTING
PUMP
}
}
AC GROUND
INTER-CONNECT
WATERFLOW
DETECTOR
PUMP
INTER-CONNECT
WATERFLOW
DETECTOR
AC POWER
MULTIPLE ZONECHECK UNIT
TO EARTH GND.
OR ATTACH TO
JUNCTION BOX
WF INPUT
AC POWER
WF INPUT
AC GROUND
}
}
GND
AC
AC
PUMP
PUMP
AC POWE
WF INPUT
INTER-CONNECT
WATERFLOW
DETECTOR
TO EARTH GND.
OR ATTACH TO
JUNCTION BOX
GND
AC
AC
PUMP
PUMP
PUMP
AC GROUND
AC GROUND
PUMP
AC POWER
W0158-00
}
}
NOTE: WF input not required for keyswitch operation if
waterflow detector is connected to panel or other monitoring device.
TO EARTH GND.
OR ATTACH TO
JUNCTION BOX
WF INPUT
INTER-CONNECT
AC power and pump wiring must conform to NEC or your
local codes.
PUMP
TO NEXT
ZONECHECK
SWITCH FOR
INTERCONNECT
}
}
AC GROUND
GND
AC
AC
WATERFLOW PUMP
DETECTOR
PUMP
AC POWE
WF INPUT
INTER-CONNECT
W0158-00
WATERFLOW
DETECTOR
D770-31-00
1
I56-1610-007R
PUMP
ZCK-1E, ZCK-1EG, ZCK-1EN and ZCK-50
ZCK-1E, ZCK-1EG, ZCK-1EN and ZCK-50
If the pump used in this application is grounded, it must
share the same input/output earth ground as the device.
To activate the Zonecheck wired locally to the key switch insert key and turn to the right. Green LEDs will illuminate when
either the pump or the waterflow detector are activated.
An overcurrent protection device such as a switch or circuit
breaker is required. The protection device must be clearly
marked and have a maximum rating of 16 A.
NOTE: The LED for the waterflow detector will not illuminate if the detector is not wired to the key switch. When
testing has been completed, turn the key back to the
standby position.
There are no ventilation requirements.
Pre-operation Guidelines
Zonecheck Testing: Group-Test Mode
Contact central monitoring station or appropriate fire safety
personnel prior to testing Zonecheck.
All Zonecheck systems whose key switches are interconnected (refer to interconnecting wiring diagram), may be
activated from any key switch. To initiate the group test,
insert key and turn to the left.
WARNING
Only activate the Zonecheck key switch when the valves
are opened and the sprinkler system is full.
The LEDs on the key switch used to initiate the group test
indicate the activity for the Zonecheck unit and waterflow
detector connected to that key switch only.
Zonecheck Testing: Self-Test Mode
When testing has been completed, turn the key back to the
standby position.
ZCK-1
To activate the Zonecheck wired locally to the key switch insert key and turn to the right. The green LED will illuminate
to show that the pump has been activated. The red LED will
illuminate once the waterflow detector has been activated.
NOTE: The red LED will not illuminate if the waterflow
detector is not wired to the key switch. When testing has
been completed, turn the key back to the standby position.
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years
from date of manufacture. System Sensor makes no other express warranty
for the enclosed product. No agent, representative, dealer, or employee of the
Company has the authority to increase or alter the obligations or limitations
of this Warranty. The Company’s obligation of this Warranty shall be limited
to the replacement of any part of the product which is found to be defective
in materials or workmanship under normal use and service during the three
year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns
D770-31-00
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to replace units which are found to be
defective because of damage, unreasonable use, modifications, or alterations
occurring after the date of manufacture. In no case shall the Company be
liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage
is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you specific
legal rights, and you may also have other rights which vary from state to state.
2
I56-1610-007R
©2005 System Sensor