PHOENIX ETD-SL-1T-DTF Multifunctional timer relay with one adjustable time Datasheet

ETD-SL-1T-DTF
Multifunctional timer relay with one adjustable time
Data sheet
102571_en_06
1
© PHOENIX CONTACT - 2013-05-31
Description
Increasingly higher demands are being placed on safety and
system availability – across all sectors. Processes are
becoming more and more complex, not only in mechanical
engineering and the chemical industry, but also in plant and
automation technology. Demands on power engineering are
also increasing constantly.
The timer relays in the ETD series can be used to control time
sequences in production and process technology.
Features
–
–
–
–
–
–
–
–
One adjustable time
Time range of 50 ms to 100 hours (seven setting ranges)
Non-floating control input
Delay functions
Wiper functions
Flashing function
Wide-range power supply unit
Two floating PDTs
WARNING: Risk of electric shock
Never carry out work when voltage is present.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
ETD-SL-1T-DTF
2
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Multifunctional timer relay with one adjustable time
ETD-SL-1T-DTF
2866161
1
3
Technical data
Input data
Input voltage range
24 V DC ... 240 V DC -20 % ... +25 %
24 V AC ... 240 V AC -15 % ... +10 %
Nominal frequency
48 Hz ... 63 Hz
Temperature coefficient, typical
≤ 0.01 %/K
Recovery time
500 ms
Time setting range
50 ms ... 100 h (7 time end ranges)
Function
E: With switch-on delay
R: With release delay and control contact
Es: With switch-on delay and control contact
Wu: With single shot leading edge, voltage controlled
Ws: With single shot leading edge and control contact
Wa: With single shot trailing edge and control contact
Bi: Flashing beginning with pulse
Bp: Flashing beginning with pause
Basic accuracy
± 1 % (of scale end value)
Setting accuracy
≤ 5 % (of scale end value)
Repeat accuracy
≤ 0.5 % ±5 ms
Nominal power consumption
2.5 VA (1 W)
Output data
Contact type
2 floating PDT contacts
Nominal insulation voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse
5 A (fast-blow)
Control contact
Control contact
Non-floating, terminals A1-B1
Load capacity
Parallel switched minimum load current 1 VA (0.5 W), terminals A2-B1
Control pulse length
min. 70 ms
General data
Mechanical service life
Approx. 2 x 107 cycles
Service life, electrical
Approx. 2 x 105 cycles at ohmic load, 1000 VA
Switching frequency
max. 60 (per minute at 100 VA ohmic load)
max. 6 (per minute at 1000 VA ohmic load)
Operating mode
100% operating factor
Degree of protection
IP40 (housing) / IP20 (connection terminal blocks)
Pollution degree
2 (according to EN 50178)
Surge voltage category
III, basic insulation (as per EN 50178)
Rated insulation voltage
300 V (According to EN 50178)
Inflammability class according to UL 94
V0
Mounting
on standard DIN rail NS 35 in accordance with EN 60715
Mounting position
Any
Width
22.5 mm
102571_en_06
PHOENIX CONTACT
2
ETD-SL-1T-DTF
General data [...]
Height
90 mm
Depth
113 mm
Type of housing
Polyamide PA, self-extinguishing
Color
green
Weight
160 g
Connection data
Conductor cross section, solid
0.5 mm² ... 2.5 mm²
Conductor cross section, stranded
0.5 mm² ... 2.5 mm²
Stripping length
8 mm
Connection method
Screw connection
Tightening torque
1 Nm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
15 % ... 85 %
Climatic class
3K3 (in acc. with EN 60721)
Conformance / approvals
Conformance
CE-compliant
UL, USA / Canada
UL/C-UL listed UL 508
Conformance with EMC Directive 2004/108/EC
Noise immunity according to
EN 61000-6-2
Noise emission according to
EN 61000-6-4
Conformance with LV directive 2006/95/EC
Industrial timer relays according to
4
EN 61812-1/A11
DC breaking capacity
20
Switching current [A]
10
1
5
2
1
2
0,5
0,2
0,1
10
20
30
50
70
100
200
300 400 500
Switching voltage [V]
1 DC, ohmic load, 2 contacts in series
2 DC, ohmic load, 1 contact
102571_en_06
PHOENIX CONTACT
3
ETD-SL-1T-DTF
5
Block diagram
B1
16
18
26
28
A1
t
A2
6
25
15
U = 24...240 V AC/DC
Safety notes
WARNING: Risk of electric shock
Never carry out work when voltage is present.
7
Structure
1
2
3
4
5
6
1
"U/t" LED: Supply and adjustable time TIME
"REL" LED: Output relay
"FUNCTION" rotary switch: Function selection
Rotary switch "TIME": Time end range
"TIME" potentiometer: Preset value
Universal snap-on foot for EN DIN rails
A1
B1
.6
.05
s
.8
m T IM 1
10
1
1 1
0
E
1 h
10
100
Timer
U/t
15
.4
.2
25
16
W
Es u E
Wa
R
Wa
E
Bi
FU
NC Bp
TIO
N
26
18 28
A2
ETD-SL-1T-DTF
2
REL
6
4
5
3
102571_en_06
PHOENIX CONTACT
4
ETD-SL-1T-DTF
8
Installation
WARNING: Risk of electric shock
Never carry out work when voltage is present.
The module can be snapped onto all 35 mm DIN rails according to EN 60715.
An integrated wide-range power supply unit enables the connection of a supply voltage in the range from 24 V AC/DC to
240 V AC/DC.
9
Time setting
Example:
B1
.8
.05
1
1
m
REL
s
.6
.2
TIME
2
Set time: 0.4 x 10 minutes = 4 minutes
h
1 10 1
10
100
10
1
Wu EWa
Wa
Es
Bi
R
Bp
E
FUNCTION
25
16
10
2
Specification of the time end range using a rotary switch,
e.g. 10 m (10 minutes)
Fine setting of the time using a potentiometer, e.g. 0.4
26
18
ETD-SL-1T-DTF
U/t
.4
1
15
Timer
A1
28
A2
Diagnostics
The LEDs indicate the following error states:
"U/t" LED (Green)
–
–
LED flashes: Voltage present, set time running
LED ON: Voltage present, set time has elapsed
"REL" LED (Yellow)
–
–
LED ON: Output relay has picked up
LED OFF: Output relay has dropped out
102571_en_06
PHOENIX CONTACT
5
ETD-SL-1T-DTF
11
Connection examples
NOTE:
When the control input is connected to a parallel load, ensure that the minimum load connected in parallel is >
1 VA.
S
A1
B1
15
A1
B1
15
15
25
15
25
16 18
26 28
16 18
26 28
25
26
28
25
26
16
18 A2
16
18 A2
Connection without control contact
28
Connection with control contact
S
A1
B1
15
15
25
16 18
26 28
28
25
26
16
18 A2
Connection with control contact and parallel load (e.g., relay)
102571_en_06
PHOENIX CONTACT
6
ETD-SL-1T-DTF
12
Function
NOTE: Module can become damaged
Only set the functions when the module is switched off.
Bi: Flashing Beginning With Pulse
U
LED U/t
LED REL, R
t
t
t
t
t
When supply voltage U is applied, the output relay picks up
(yellow "REL" LED is ON) and set time t starts running (green
"U/t" LED flashes). Once time t has elapsed, the output relay
drops out (yellow "REL" LED is OFF) and set time t starts
running again. The output relay is controlled at a ratio of 1:1,
until the supply voltage is interrupted.
For the flashing function the pulse and pause times are the
same, as it is only possible to set one time.
Bp: Flashing Beginning With Pause
U
LED U/t
LED REL, R
t
t
t
t
t
When supply voltage U is applied, set time t starts running
(green "U/t" LED flashes). Once time t has elapsed, the output
relay picks up (yellow "REL" LED is ON) and set time t starts
running again. Once time t has elapsed, the output relay
drops out (yellow "REL" LED is OFF). The output relay is
controlled at a ratio of 1:1, until the supply voltage is
interrupted.
For the flashing function the pulse and pause times are the
same, as it is only possible to set one time.
E: With Switch-On Delay
U
LED U/t
LED REL, R
t
102571_en_06
<t
When supply voltage U is applied, set time t starts running
(green "U/t" LED flashes). Once time t has elapsed (green "U/
t" LED is ON), the output relay picks up (yellow "REL" LED is
ON). This state is maintained until supply voltage U is
interrupted. If supply voltage U is interrupted before time t has
elapsed, the elapsed time is deleted (relay does not pick up).
The next time supply voltage U is applied, the time is
restarted.
PHOENIX CONTACT
7
ETD-SL-1T-DTF
Es: With Switch-On Delay and Control Contact
U
LED U/t
A1 - B1
LED REL, R
t
<t
Supply voltage U must be applied permanently at the device
(green "U/t" LED is ON). When control contact A1-B1 is
closed, set time t starts running (green "U/t" LED flashes).
Once time t has elapsed (green "U/t" LED is ON), the output
relay picks up (yellow "REL" LED is ON). This state is
maintained until the control contact is opened. If the control
contact is opened before time t has elapsed, the elapsed time
is deleted (relay does not pick up) and restarted with the next
cycle.
R: With Release Delay and Control Contact
U
LED U/t
A1 - B1
LED REL, R
t
<t
Supply voltage U must be applied permanently at the device
(green "U/t" LED is ON). When control contact A1-B1 is
closed, the output relay picks up (yellow "REL" LED is ON). If
control contact A1-B1 is opened, set time t starts running
(green "U/t" LED flashes). Once time t has elapsed (green "U/
t" LED is ON), the output relay drops out (yellow "REL" LED is
OFF). If the control contact is closed again before time t has
elapsed, the elapsed time is deleted and restarted with the
next cycle.
Wu: With single shot leading edge, voltage controlled
U
LED U/t
LED REL, R
t
<t
When supply voltage U is applied, the output relay picks up
(yellow "REL" LED is ON) and set time t starts running (green
"U/t" LED flashes). Once time t has elapsed (green "U/t" LED
is ON), the output relay drops out (yellow "REL" LED is OFF).
This state is maintained until supply voltage U is interrupted.
If the supply voltage is interrupted before time t has elapsed,
the output relay drops out. The elapsed time is deleted and
restarted the next time the supply voltage is applied again.
Ws: With single shot leading edge and control contact
U
LED U/t
A1 - B1
LED REL, R
t
102571_en_06
t
Supply voltage U must be applied permanently at the device
(green "U/t" LED is ON). When control contact A1-B1 is
closed, the output relay picks up (yellow "REL" LED is ON)
and set time t starts running (green "U/t" LED flashes). Once
time t has elapsed (green "U/t" LED is ON), the output relay
drops out (yellow "REL" LED is OFF).
The control contact can be freely switched during this time.
Another cycle cannot be started until the current cycle has
been completed.
PHOENIX CONTACT
8
ETD-SL-1T-DTF
Wa: With single shot trailing edge and control contact
U
LED U/t
A1 - B1
LED REL, R
t
102571_en_06
t
Supply voltage U must be applied permanently at the device
(green "U/t" LED is ON). Control contact A1-B1 closing has
no influence on the position of the output relay. When control
contact A1-B1 is opened, the output relay picks up (yellow
"REL" LED is ON) and set time t starts running (green "U/t"
LED flashes). Once time t has elapsed (green "U/t" LED is
ON), the output relay drops out (yellow "REL" LED is OFF).
The control contact can be freely switched during this time.
Another cycle cannot be started until the current cycle has
been completed.
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
9