ETD-SL-1T-DTF Multifunctional timer relay with one adjustable time Data sheet 102571_en_06 1 © PHOENIX CONTACT - 2013-05-31 Description Increasingly higher demands are being placed on safety and system availability – across all sectors. Processes are becoming more and more complex, not only in mechanical engineering and the chemical industry, but also in plant and automation technology. Demands on power engineering are also increasing constantly. The timer relays in the ETD series can be used to control time sequences in production and process technology. Features – – – – – – – – One adjustable time Time range of 50 ms to 100 hours (seven setting ranges) Non-floating control input Delay functions Wiper functions Flashing function Wide-range power supply unit Two floating PDTs WARNING: Risk of electric shock Never carry out work when voltage is present. Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. ETD-SL-1T-DTF 2 Ordering data Description Type Order No. Pcs. / Pkt. Multifunctional timer relay with one adjustable time ETD-SL-1T-DTF 2866161 1 3 Technical data Input data Input voltage range 24 V DC ... 240 V DC -20 % ... +25 % 24 V AC ... 240 V AC -15 % ... +10 % Nominal frequency 48 Hz ... 63 Hz Temperature coefficient, typical ≤ 0.01 %/K Recovery time 500 ms Time setting range 50 ms ... 100 h (7 time end ranges) Function E: With switch-on delay R: With release delay and control contact Es: With switch-on delay and control contact Wu: With single shot leading edge, voltage controlled Ws: With single shot leading edge and control contact Wa: With single shot trailing edge and control contact Bi: Flashing beginning with pulse Bp: Flashing beginning with pause Basic accuracy ± 1 % (of scale end value) Setting accuracy ≤ 5 % (of scale end value) Repeat accuracy ≤ 0.5 % ±5 ms Nominal power consumption 2.5 VA (1 W) Output data Contact type 2 floating PDT contacts Nominal insulation voltage 250 V AC (in acc. with IEC 60664-1) Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) Output fuse 5 A (fast-blow) Control contact Control contact Non-floating, terminals A1-B1 Load capacity Parallel switched minimum load current 1 VA (0.5 W), terminals A2-B1 Control pulse length min. 70 ms General data Mechanical service life Approx. 2 x 107 cycles Service life, electrical Approx. 2 x 105 cycles at ohmic load, 1000 VA Switching frequency max. 60 (per minute at 100 VA ohmic load) max. 6 (per minute at 1000 VA ohmic load) Operating mode 100% operating factor Degree of protection IP40 (housing) / IP20 (connection terminal blocks) Pollution degree 2 (according to EN 50178) Surge voltage category III, basic insulation (as per EN 50178) Rated insulation voltage 300 V (According to EN 50178) Inflammability class according to UL 94 V0 Mounting on standard DIN rail NS 35 in accordance with EN 60715 Mounting position Any Width 22.5 mm 102571_en_06 PHOENIX CONTACT 2 ETD-SL-1T-DTF General data [...] Height 90 mm Depth 113 mm Type of housing Polyamide PA, self-extinguishing Color green Weight 160 g Connection data Conductor cross section, solid 0.5 mm² ... 2.5 mm² Conductor cross section, stranded 0.5 mm² ... 2.5 mm² Stripping length 8 mm Connection method Screw connection Tightening torque 1 Nm Ambient conditions Ambient temperature (operation) -25 °C ... 55 °C -25 °C ... 40 °C (corresponds to UL 508) Ambient temperature (storage/transport) -25 °C ... 70 °C Permissible humidity (operation) 15 % ... 85 % Climatic class 3K3 (in acc. with EN 60721) Conformance / approvals Conformance CE-compliant UL, USA / Canada UL/C-UL listed UL 508 Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 Noise emission according to EN 61000-6-4 Conformance with LV directive 2006/95/EC Industrial timer relays according to 4 EN 61812-1/A11 DC breaking capacity 20 Switching current [A] 10 1 5 2 1 2 0,5 0,2 0,1 10 20 30 50 70 100 200 300 400 500 Switching voltage [V] 1 DC, ohmic load, 2 contacts in series 2 DC, ohmic load, 1 contact 102571_en_06 PHOENIX CONTACT 3 ETD-SL-1T-DTF 5 Block diagram B1 16 18 26 28 A1 t A2 6 25 15 U = 24...240 V AC/DC Safety notes WARNING: Risk of electric shock Never carry out work when voltage is present. 7 Structure 1 2 3 4 5 6 1 "U/t" LED: Supply and adjustable time TIME "REL" LED: Output relay "FUNCTION" rotary switch: Function selection Rotary switch "TIME": Time end range "TIME" potentiometer: Preset value Universal snap-on foot for EN DIN rails A1 B1 .6 .05 s .8 m T IM 1 10 1 1 1 0 E 1 h 10 100 Timer U/t 15 .4 .2 25 16 W Es u E Wa R Wa E Bi FU NC Bp TIO N 26 18 28 A2 ETD-SL-1T-DTF 2 REL 6 4 5 3 102571_en_06 PHOENIX CONTACT 4 ETD-SL-1T-DTF 8 Installation WARNING: Risk of electric shock Never carry out work when voltage is present. The module can be snapped onto all 35 mm DIN rails according to EN 60715. An integrated wide-range power supply unit enables the connection of a supply voltage in the range from 24 V AC/DC to 240 V AC/DC. 9 Time setting Example: B1 .8 .05 1 1 m REL s .6 .2 TIME 2 Set time: 0.4 x 10 minutes = 4 minutes h 1 10 1 10 100 10 1 Wu EWa Wa Es Bi R Bp E FUNCTION 25 16 10 2 Specification of the time end range using a rotary switch, e.g. 10 m (10 minutes) Fine setting of the time using a potentiometer, e.g. 0.4 26 18 ETD-SL-1T-DTF U/t .4 1 15 Timer A1 28 A2 Diagnostics The LEDs indicate the following error states: "U/t" LED (Green) – – LED flashes: Voltage present, set time running LED ON: Voltage present, set time has elapsed "REL" LED (Yellow) – – LED ON: Output relay has picked up LED OFF: Output relay has dropped out 102571_en_06 PHOENIX CONTACT 5 ETD-SL-1T-DTF 11 Connection examples NOTE: When the control input is connected to a parallel load, ensure that the minimum load connected in parallel is > 1 VA. S A1 B1 15 A1 B1 15 15 25 15 25 16 18 26 28 16 18 26 28 25 26 28 25 26 16 18 A2 16 18 A2 Connection without control contact 28 Connection with control contact S A1 B1 15 15 25 16 18 26 28 28 25 26 16 18 A2 Connection with control contact and parallel load (e.g., relay) 102571_en_06 PHOENIX CONTACT 6 ETD-SL-1T-DTF 12 Function NOTE: Module can become damaged Only set the functions when the module is switched off. Bi: Flashing Beginning With Pulse U LED U/t LED REL, R t t t t t When supply voltage U is applied, the output relay picks up (yellow "REL" LED is ON) and set time t starts running (green "U/t" LED flashes). Once time t has elapsed, the output relay drops out (yellow "REL" LED is OFF) and set time t starts running again. The output relay is controlled at a ratio of 1:1, until the supply voltage is interrupted. For the flashing function the pulse and pause times are the same, as it is only possible to set one time. Bp: Flashing Beginning With Pause U LED U/t LED REL, R t t t t t When supply voltage U is applied, set time t starts running (green "U/t" LED flashes). Once time t has elapsed, the output relay picks up (yellow "REL" LED is ON) and set time t starts running again. Once time t has elapsed, the output relay drops out (yellow "REL" LED is OFF). The output relay is controlled at a ratio of 1:1, until the supply voltage is interrupted. For the flashing function the pulse and pause times are the same, as it is only possible to set one time. E: With Switch-On Delay U LED U/t LED REL, R t 102571_en_06 <t When supply voltage U is applied, set time t starts running (green "U/t" LED flashes). Once time t has elapsed (green "U/ t" LED is ON), the output relay picks up (yellow "REL" LED is ON). This state is maintained until supply voltage U is interrupted. If supply voltage U is interrupted before time t has elapsed, the elapsed time is deleted (relay does not pick up). The next time supply voltage U is applied, the time is restarted. PHOENIX CONTACT 7 ETD-SL-1T-DTF Es: With Switch-On Delay and Control Contact U LED U/t A1 - B1 LED REL, R t <t Supply voltage U must be applied permanently at the device (green "U/t" LED is ON). When control contact A1-B1 is closed, set time t starts running (green "U/t" LED flashes). Once time t has elapsed (green "U/t" LED is ON), the output relay picks up (yellow "REL" LED is ON). This state is maintained until the control contact is opened. If the control contact is opened before time t has elapsed, the elapsed time is deleted (relay does not pick up) and restarted with the next cycle. R: With Release Delay and Control Contact U LED U/t A1 - B1 LED REL, R t <t Supply voltage U must be applied permanently at the device (green "U/t" LED is ON). When control contact A1-B1 is closed, the output relay picks up (yellow "REL" LED is ON). If control contact A1-B1 is opened, set time t starts running (green "U/t" LED flashes). Once time t has elapsed (green "U/ t" LED is ON), the output relay drops out (yellow "REL" LED is OFF). If the control contact is closed again before time t has elapsed, the elapsed time is deleted and restarted with the next cycle. Wu: With single shot leading edge, voltage controlled U LED U/t LED REL, R t <t When supply voltage U is applied, the output relay picks up (yellow "REL" LED is ON) and set time t starts running (green "U/t" LED flashes). Once time t has elapsed (green "U/t" LED is ON), the output relay drops out (yellow "REL" LED is OFF). This state is maintained until supply voltage U is interrupted. If the supply voltage is interrupted before time t has elapsed, the output relay drops out. The elapsed time is deleted and restarted the next time the supply voltage is applied again. Ws: With single shot leading edge and control contact U LED U/t A1 - B1 LED REL, R t 102571_en_06 t Supply voltage U must be applied permanently at the device (green "U/t" LED is ON). When control contact A1-B1 is closed, the output relay picks up (yellow "REL" LED is ON) and set time t starts running (green "U/t" LED flashes). Once time t has elapsed (green "U/t" LED is ON), the output relay drops out (yellow "REL" LED is OFF). The control contact can be freely switched during this time. Another cycle cannot be started until the current cycle has been completed. PHOENIX CONTACT 8 ETD-SL-1T-DTF Wa: With single shot trailing edge and control contact U LED U/t A1 - B1 LED REL, R t 102571_en_06 t Supply voltage U must be applied permanently at the device (green "U/t" LED is ON). Control contact A1-B1 closing has no influence on the position of the output relay. When control contact A1-B1 is opened, the output relay picks up (yellow "REL" LED is ON) and set time t starts running (green "U/t" LED flashes). Once time t has elapsed (green "U/t" LED is ON), the output relay drops out (yellow "REL" LED is OFF). The control contact can be freely switched during this time. Another cycle cannot be started until the current cycle has been completed. PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com 9