Gamewell-FCI IPENC Ip fire alarm communicator Datasheet

IPDACT-2
IP Fire Alarm Communicator
Description
The IPDACT-2 is a compact Internet Protocol Digital
Alarm Communicator/Transmitter Module. It is
designed to transmit status communication to a Central Station via the Internet. During an alarm, a supervisory, or a trouble event, the IPDACT-2, using the
Contact-ID protocol from the fire alarm control panel,
converts the standard DACT phone communication
to a protocol that can be transmitted and received via
the Internet. It can also test the connectivity between
the fire alarm control panel and the Central Station.
The IPDACT-2 operates in conjunction with the
VisorALARM PLUS™ IP receiver located at the Central Station.
The IPDACT-2 is designed to operate with the
DACT-equipped panels used in the Gamewell-FCI's,
E3 Series® and GF505/GF510 Flex Series Systems.
The IP Communicator provides faster and more economic digital alarm transmissions, improving
response times and decreasing costs found with traditional analog systems. The IPDACT-2 offers valueadded features such as supervised line functionality,
which allows a Central Station to detect any off-line
alarm panels within seconds. No backup analog
phone line is necessary. However; customers can
still use a traditional backup phone line from the
panel's second phone port if desired.
The panel operates normally during an alarm, a
supervisory, or a trouble event and sends the Contact-ID formatted analog information from the telephone ports to the IP Communicator. The IP
Communicator then reformats the data into highly
encrypted Ethernet UDP packets for transmission to
a compatible receiver at the Central Station. This
feature allows seamless integration into existing conventional Central Station architectures.
IPDACT-2
Features
• Listed under UL® Standard 864, 9th Edition.
• Operates with the Gamewell-FCI's E3 Series panels
equipped with DACT-E3 units and GF505/GF510 Flex
Series Systems.
• Saves the cost of two dedicated phone lines. Only the
customer's shared IP equipment is required.
• Provides compatibility to newer low-cost, non-analog,
digital telephone services such as cable, or fiber optics.
• Increases connection supervision to the Central Station
from the once-a-day test signal to once every 90
seconds.
• Requires no change to the existing panel configuration.
The IP Communicator connects directly to the primary
and secondary analog panel telephone ports.
• Produces fast alarm transmission (less than 10 second
transmission time).
• Performs over any type of customer-provided Ethernet
10/100Base network connection (LAN or WAN), DSL
modem or cable modem.
• Transmits data over standard Contact-ID protocol but is
secured with the industry's highest level of encryption
(AES 512 bit).
• Supports both dynamic (DHCP) or Public and Private
Static IP addressing.
• Maintains dual-destination IP receiver address for high
redundancy configurations: all signals are sent to a secondary address should the primary become unavailable.
• Offers user programmable UDP ports for flexibility and
compatibility with firewalls and other network security
components.
SIGNALING
®
E3 Series is a registered trademark of Honeywell International Inc.
®
®
Microsoft and Windows are registered trademarks of Microsoft Corporation.
VisorALARM PLUS™ is a trademark of Teldat Corporation.
UL® is a registered trademark of Underwriters Laboratories Inc.
MEA
Approved
S1869
FDNY: 7165-1703:0125
COA #6077
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60504 Rev. E page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Programming Options:
To configure the IPDACT-2, the following three (3) options
are available:
• Use a HyperTerminal or TeraTerm software program
• Local or Remote Telnet session via an Ethernet
connection.
• Windows®-based configuration software (shipped with
the IP Communicator).
Note: It is possible to pre-program the IP Communicator at
the panel before the installation. To pre-program the IP
Communicator, the following is done:
1. An auto-registration password is entered (along with
all other Central Station information) and saved in the
unit's flash memory.
2. When the IP Communicator is installed at the site and
connected to the Internet/Intranet, it auto-registers
with the Central Station receiver.
3. This feature eliminates the need to program from a PC
at the remote site.
4. The IP Receiver at the monitoring station will automatically configure other parameters during registration.
For most installations, the only parameters required are as
follows:
• Selection of either DHCP or Static IP
• Destination primary and secondary receiver IP
addresses
• Account identification number (CID)
• Port number
• Installation password
Specifications
Operating Voltage:
Operating Temperature:
Relativity Humidity:
24VDC
Not to exceed the range of
32°C to 120°C (0 to 49°C)
Not to exceed 93% non-condensing at 90°F (32°C)
Ordering Information
Part Number Description
IPDACT-2
IP communicator. Includes configuration
software, manuals, and prepared 30" telephone cable for connection to panel's
DACT telco ports.
IPENC
External mounting enclosure consisting of
mounting bracket IPBRKT, and screws.
Enclosure must be "close-nipple" to a
panel no further than 6 in. (15 cm) via
conduit. (Red)
IPSPLT
Y adapter option to allow connection of
both panel dialer outputs to one cable
input to IPDACT.
Note: The IPSPLT is not required if the second dialer output is used for the phone backup.
ALMSC119
Serial programming cable and DB9
adapter.
VisorALARM- IP Receiver with LCD display and keypad
PLUS
Installation Requirements
To install the IDPDACT-2, the following criteria are
required:
• Mounted locally next to the supported fire alarm control
panel.
• The Central Station must be equipped with a compatible
VisorALARM PLUS™ IP receiver
• At least 136mA of electrical power available from the
power supply to use for the IPDACT-2 unit.
• Ethernet network connection (ITE-listed router/gateway).
• It is recommended to use a small UPS, to provide
backup power for customer-provided router/switch/
modem.
• Dynamic or static IP address (dynamic addressing
requires DHCP server present on the local network.
Note: DSL and cable modems typically use dynamic
addressing as supplied by network providers).
• UDP port for IP communication with the monitoring station (default port: 80 may be changed by the Central
Station).
• Destination IP addresses of the IP receivers where the
IP Communicator will be sending alarms and other
events (If installed on a private Intranet, the gateway
address of the public router will be required to allow the
IP card to access the Internet and the public router at
the Central Station).
• Panel account ID number (CID).
• Installer password (provided by the monitoring station
managing the IP receiver).