HDR-60 60W Ultra Slim Step Shape DIN Rail series Bauar t gepruft Sicherheit egel ma ge od o s be wac g UL508 Ultra slim design with 52.5mm( ‧ ‧ ‧ass LPS (Limited power source) ‧ ‧ / ‧ooling by free air convection (working temperature:-30~+70°C) ‧DIN rail TS-35/7.5 or 15 mountable ‧ED indicator for power on ‧ UL60950-1 www. tuv.com ID 2000000000 EN61558 IEC60950-1 ■ ‧ ‧ ‧ ‧ ‧ ■ ■ File Name:HDR-60-SPEC 2016-10-28 HDR-60 60W Ultra Slim Step Shape DIN Rail series SPECIFICATION MODEL HDR-60-5 HDR-60-12 HDR-60-15 HDR-60-24 HDR-60-48 DC VOLTAGE 5V 12V 15V 24V 48V RATED CURRENT 6.5A 4.5A 4A 2.5A 1.25A CURRENT RANGE 0 ~6.5A 32.5W 0 ~ 4.5A 0 ~ 4A 0 ~ 2.5A 0 ~ 1.25A 54W 60W 60W 60W RIPPLE & NOISE (max.) Note.2 80mVp-p 120mVp-p 120mVp-p 150mVp-p 240mVp-p VOLTAGE ADJ. RANGE 10.8 ~ 13.8V 13.5 ~ 18V 21.6 ~ 29V 43.2 ~ 55.2V RATED POWER OUTPUT VOLTAGE TOLERANCE Note.3 2.0% 1.0% 1.0% 1.0% 1.0% LINE REGULATION 1.0% 1.0% 1.0% 1.0% 1.0% 1.0% 1.0% 1.0% 1.0% LOAD REGULATION INPUT 5.0 ~ 5.5V 1.0% SETUP, RISE TIME 500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load HOLD UP TIME (Typ.) 30ms/230VAC VOLTAGE RANGE 85 ~ 264VAC (277VAC available ) FREQUENCY RANGE 47 ~ 63Hz 12ms/115VAC at full load EFFICIENCY (Typ.) 85% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 1.2A/115VAC 0.8A/230VAC COLD START 30A/115VAC 60A/230VAC OVERLOAD Note.4 PROTECTION OVER VOLTAGE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY & OPERATING ALTITUDE SAFETY STANDARDS WITHSTAND VOLTAGE EMC ISOLATION RESISTANCE (Note 5) 88% MTBF DIMENSION PACKING 91% 90% 56.5 ~ 64.8V Protection type : Shut down o/p voltage, re-power on to recover -30 ~ +70 (Refer to "Derating Curve") 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH non-condensing 0.03%/ (0 ~ 50 ) RH non-condensing 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 2000 meters UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved; Design refer to EN50178,TUV EN60950-1 I/P-O/P:3KVAC I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH Standard Radiated Harmonic Current Test Level / Note EN55032(CISPR32) EN55032(CISPR32) Class B EN61000-3-2 Class A Class B ------- Voltage Flicker EN61000-3-3 EN55024, EN55035, EN61000-6-2, EN61204-3 Parameter Standard Test Level /Note ESD Level 3, 8KV air; Level 2, 4KV contact, criteria A Radiated Susceptibility EMC IMMUNITY 89% 105 ~ 160% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 5.75 ~ 6.75V 14.2 ~ 16.2V 18.8 ~ 22.5V 30 ~ 36V Parameter Conducted EMC EMISSION OTHERS 120 ~ 370VDC (390VDC available ) EFT/Burest Surge EN61000-4-2 EN61000-4-3 EN61000-4-4 Conducted Magnetic Field EN61000-4-5 EN61000-4-6 EN61000-4-8 Voltage Dips and interruptions EN61000-4-11 Level 3, criteria A Level 3, criteria A Level 4,2KV/L-N, criteria A Level 3, criteria A Level 4, criteria A >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods 927.6K hrs min. MIL-HDBK-217F (25 ) 52.5*90*54.5mm (W*H*D) 190g;60pcs/12.4Kg/0.97CUFT ℃ NOTE File Name:HDR-60-SPEC 2016-10-28 HDR-60 60W Ultra Slim Step Shape DIN Rail series Block Diagram RECTIFIERS & FILTER EMI FILTER I/P RECTIFIERS & FILTER POWER SWITCHING O.L.P. +V -V DETECTION CIRCUIT PWM CONTROL O.V.P. Derating Curve Output Derating VS Input Voltage 100 100 90 80 80 70 50 LOAD (%) LOAD (%) 60 40 20 -30 0 10 20 30 40 50 AMBIENT TEMPERATURE ( ) 60 70 (VERTICAL) 60 50 40 85 95 100 115 120 140 160 180 200 220 240 264 277 (available) INPUT VOLTAGE (VAC) 60Hz File Name:HDR-60-SPEC 2016-10-28 HDR-60 60W Ultra Slim Step Shape DIN Rail series Mechanical Specification (Unit: mm , tolerance ± 0.5mm) 58.4 54.5 52.5 4 5 45.15 3 63.65 2 90 1 6 35 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Terminal Pin No. Assignment Pin No. Assignment Pin No. Assignment 1,2 -V 5 AC/L 3,4 +V 6 AC/N Installation Manual Please refer to : http://www.meanwell.com/manual.html File Name:HDR-60-SPEC 2016-10-28