Nova J60K60-240 Rugged single & three phase inverter Datasheet

JUPITER SERIES
RUGGED SINGLE & THREE PHASE INVERTERS
120, 240 and 350 VDC Nominal Input
Pure Sine-Wave Output
GALVANIC ISOLATED
APPLICATIONS
Nova inverters are high-reliability power
sources specifically designed for demanding
applications in high shock, vibration,
humidity, and EMI environments. They can
be built to meet MIL-STD-810, MIL-STD1399, MIL-STD-1472, MIL-STD-461, and
other standards optionally.
Military programs, vehicular, shipboard
AC Power from battery
Communications
Shelters
Utility Applications
Emergency Lighting
FEATURES
• Complete input to output ‘Galvanic’ isolation.
• Almost silent high frequency operation
• Push button starting and stopping
• Diagnostic panel with LCD and LED display
• Soft start on inverter
• Overload and short circuit protection
• Optional solid state transfer switch built in
• Optional maintenance bypass switch built in
• Optional DC input circuit breaker
• Remote isolated dry relay contacts
• Available options to meet military specs
including MIL-STD-461, MIL-STD-167,
MIL-STD-810
• All electronics are built in modular front
access and front removable sub assemblies
for easy service and maintenance
NOVA
VA ELECTRIC
www.novaelectric.com
[email protected]
A Leader in Inverter Technology since 1966 - 500VA-500+KVA
JUPITER SERIES DC-AC INVERTERS
MONITORING FEATURES
The Inverter includes an RS232 communication option called UPSCOM. This
is an RS232 connection to a PC that can monitor the information related to
the inverter output and any abnormal conditions that have occurred in real time.
Standard commercially available software is provided. The RS232 Feature
is included at no additional charge.
FRONT PANEL LCD DISPLAY AND LED INDICATORS - These will report all
Inverter parameters, including input and output voltages, currents, frequency,
DC voltage and many other functions.
LCD DISPLAY - Real time status, data, and historical events are displayed via
the LCD display. The Inverter parameters, real time clock, and buzzer alarm
also can be set through this LCD. The LCD is backlit by LEDs for easy visuals.
STATUS LEDs - A series of LEDs representing all the important status information
of the Inverter provide information to the user. These LEDs are especially
important when abnormal conditions occur. Since these LEDs are located
behind the transparent window, the user can see them clearly without opening
the door. LED descriptions are as follows:
• INVERTER ON – Inverter is running normally.
• INVERTER SS – Inverter static switch is on while the reserve static switch is opened (off).
• SHORT CIRCUIT – Inverter output is in short circuit state.
• FUSE / OVERTEMP SD – Inverter has shut down due to either open fuse open or
overtemperature.
• INVERTER FAIL SHUT DOWN – Inverter has shut down due to low inverter AC output.
• BYPASS ON SHUT DOWN – Inverter shut down due closed bypass breaker (while inverter running).
• HIGH DC SHUT DOWN – Inverter shut down due to high DC bus.
• OVERLOAD SHUT DOWN – Inverter shut down due to overload of the inverter for a period
greater than the inverter can accept. The inverter will start after 7 seconds.
• 70% LOAD – load connected to the output is over 70% of the inverter rating.
• 110% LOAD – load connected to the output is over 110% of the inverter rating.
• 125% LOAD – load connected to the output is over 125% of the inverter rating.
• 150% LOAD – load connected to the output is over 150% of the inverter rating.
• RESERVE AC FAIL – reserve AC magnitude is out of range.
• RESERVE FREQ FAIL – reserve frequency is out of range.
• BATTERY LOW - DC bus (or battery) is lower than specified range. Low battery shut down
will occur soon.
BATTERY LOW SHUT DOWN – Inverter shut down due to DC bus (or battery)
lower than the acceptable DC voltage of the inverter.
COMMUNICATIONS OPTIONS
Some popular communications options available at additional cost include the
following:
UPSCAN: This is a hand held remote display and control module with LCD and
LED display that can monitor up to 99 inverter units via RS-485 at a remote
distance of up to 3,000 feet.
UPSCALL: This is a modem that will automatically dial out to a specified
number when an abnormal situation occurs.
NETAGENT: This provides capability to monitor the inverter over the internet.
It includes the appropriate additional SNMP card and microprocessor. The
software required is provided separately.
HIGH DC – DC voltage over the acceptable DC voltage of the inverter.
EMERGENCY STOP – Inverter shutdown activated by emergency stop
switch.
DATA LINE – Blinks when data is transmitted to or received from the
communication port.
WARNING LEDs – When abnormal condition occurs, these LEDs will light to
warn the user of the cause of the fault condition. Therefore all these LEDs are
off under normal condition. These LEDs are:
RECT AC FAIL – Rectifier AC input is abnormal either due to AC magnitude out of the range or
phase rotation error; rectifier shut down.
RESERVE FAIL – Reserve AC input is abnormal either due to AC magnitude out of range or
frequency out of range.
FUSE/TEMP - Either inverter fuse is open or over temperature has occurred.
OVERLOAD – Output is overloaded by over 110%, 125% or 150%
HIGH DC – This LED will light as long as the DC voltage is over 430VDC.
BAT LOW – This LED will light when the DC voltage is lower than 320VDC.
BAT LOW STOP – This LED will light when the DC voltage is lower than 295VDC, inverter on
is inhibited.
FAULT – The inverter is off due to abnormal conditions such as overload, short circuit, high DC,
fuse over temperature, bypass breaker on emergency stop.
AUDIBLE ALARM – The audible alarm will beep under one of the following
conditions:
• INVERTER IS OVERLOADED:
• 110% beep once every 3 seconds
• 125% beep once every second
• 150% beep twice every second
• INVERTER IS SHORT CIRCUITED – Beeps continuously
• FUSE OPEN – Beeps continuously
• HEAT SINK OVER TEMPERATURE – Beeps continuously
• HIGH DC SHUTDOWN – Beeps continuously
• BYPASS ON STOP – Beeps continuously
• EMERGENCY ON STOP – Beeps continuously. The buzzer will also beep once every time
the inverter is switched on or off to acknowledge to the user that his key entry is valid and
accepted.
OTHER OPTIONS
DC INPUT BREAKER OPTION – The optional DC Input breaker disconnect is
offered to provide protection for the input.
SHOCK MOUNT OPTION – The cabinet can be shock mounted using optional
rubber or coil type isolators. This will enable the unit to withstand shock
levels as specified in MIL-S-901
RUGGEDIZING OPTION – This option will add conformal coating and other
additional internal structural members to allow the unit to meet many portions
of MIL-STD-810 including shock, vibration, and humidity.
TURN ON SERVICE OPTION – We offer a turn on service that will ensure the
Inverter has been properly installed and the full warranty is in effect (failures
caused by incorrect installation are not covered by the warranty.) If this option
is selected, the customer will also automatically receive an additional 3 months
added to the warranty at no additional charge.
SPARE PARTS KIT OPTION – We offer a spare parts package that includes
one of each board, spare fuses, spare semiconductors, and spare fans. These
spare part kits are priced lower when ordered with the initial order than if they
are ordered later on.
DRIP SHIELD OPTIONS – This option offers protection against falling or
dripping liquids.
CUSTOMIZED EPO – This feature can be customized to trip off current
breakers or perform other inhibits depending customer needs.
JUPITER SERIES DC-AC INVERTERS
SPECIFICATIONS FOR JUPITER 120 VDC
SINGLE & 3-PHASE INVERTER SERIES
PHASE INVERTER
Input Frequency Range
Overload
Output Voltage (VAC)
DC INPUT / SINGLE OR 3-PHASE OUTPUT
+/- 5% (wider ranges offered, please consult factory)
3-Phase Models
Please Specify | 120/208 | 220/380 | 230/400 | 240/415 | 277/480 | 120
delta | 220 delta | 240 delta | 380 delta | 480 delta
OR
Single Phase
Please Specify | 120 VAC | 220 VAC | 240 VAC | 480 VAC
Wave Form
Output Power Factor
Frequency Lock Range
Pure Sinewave
0.7 lead to 0.7 lag
+/- 5% (alternate ranges offered on special order)
Output Frequency
(Free Running)
Please Specify: 50 Hz or 60 Hz or 400 Hz (crystal controlled)
Phase Shi Under 100%
Unbalanced Load
THD (Linear Load)
<110%
110-125%
125-150%
>150%
Efficiency (100% Load)
STATIC SWITCH
Voltage Range
Mains <-> Inverter
Audible Noise
Temperature
Humidity
Al tude
EN50091-1,-2
Short Circuit Protec on
Lightning / EMC Filter
Galvanic Isola on
LED, LCD, Audible Alarm
Remote Control /
Communica on Interface
<0.5% (3-Phase Models)
2% typical 3% max
Con nuous
15 minutes
10 minutes
1 minute
89 - 90%
Op onal
Same as AC output. (Different voltages are available upon request)
0 ms (True Online)
<65 dBA (at 1m)
-10°C to +50°C (Extended ranges available)
0%-95% (Non-condensing)
Up to 1500 m Above Sea Level
Yes
Yes
MOV / Input & Output ( FCC CLASS A)
Output True Galvanic Isola on
Yes
Monitoring 1~99 Units simultaneously /
Dry Contact, RS-232, RS-485 (Op onal)
STANDARD PRODUCT LISTING - 120 VDC
OUTPUT
CONTINOUS
SIZE
VAC
OUTPUT
FREQ.
J10K60- 120
120
60 Hz
10 KVA/ 8 KW
770Lbs.
63 x 22 x 31.5
J15K60- 120
120
60 Hz
15 KVA/ 12KW
880Lbs.
63 x 22 x 31.5
J20K60- 120
120
60 Hz
20 KVA/ 16 KW
880Lbs.
63 x 22 x 31.5
J30K60- 120
120
60 Hz
30 KVA/ 24 KW
1650Lbs.
63 x 43.5 x 31.5
J40K60- 120
120
60 Hz
40 KVA/ 32 KW
1760Lbs.
63 x 43.5 x 31.5
J50K60- 120
120
60 Hz
50 KVA/ 40 KW
1870Lbs.
63 x 43.5 x 31.5
J60K60- 120
120
60 Hz
60 KVA/ 48 KW
2420Lbs.
63 x 87 x 31.5
J80K60- 120
120
60 Hz
80 KVA/ 64 KW
3080Lbs.
63 x 87 x 31.5
J100K60- 120
120
60 Hz
100 KVA/ 80 KW
3520Lbs.
63 x 87 x 31.5
OUTPUT
FREQ.
OUTPUT POWER
MODELS
60HZ SINGLE PHASE MODELS OUTPUTVAC
OUTPUT POWER
CONTINOUS
WEIGHT
WEIGHT
(H"x W"x L")
SIZE
(H"x W"x L")
J10K60-120(220)
220
50 Hz
10 KVA/ 8 KW
770Lbs.
63 x 22 x 31.5
J15K60-120(220)
220
50 Hz
15 KVA/ 12KW
880Lbs.
63 x 22 x 31.5
J20K60-120(220)
220
50 Hz
20 KVA/ 16 KW
880Lbs.
63 x 22 x 31.5
J30K60-120(220)
220
50 Hz
30 KVA/ 24 KW
1650Lbs.
63 x 43.5 x 31.5
J40K60-120(220)
220
50 Hz
40 KVA/ 32 KW
1760Lbs.
63 x 43.5 x 31.5
J50K60-120(220)
220
50 Hz
50 KVA/ 40 KW
1870Lbs.
63 x 43.5 x 31.5
J60K60-120(220)
220
50 Hz
60 KVA/ 48 KW
2420Lbs.
63 x 87 x 31.5
J80K60-120(220)
220
50 Hz
80 KVA/ 64 KW
3080Lbs.
63 x 87 x 31.5
J100K60-120(220)
220
50 Hz
100 KVA/ 80 KW
3520Lbs.
63 x 87 x 31.5
400 HZ MODELS
OUTPUTVAC
OUTPUT
FREQ.
OUTPUT POWER
CONTINOUS
WEIGHT
SIZE
(H"x W"x L")
J10K400-120
115
400Hz
10 KVA/ 8 KW
770Lbs.
63 x 22 x 31.5
J15K400-120
115
400Hz
15 KVA/ 12KW
880Lbs.
63 x 22 x 31.5
J20K400-120
115
400Hz
20 KVA/ 16 KW
880Lbs.
63 x 22 x 31.5
J30K400-120
115
400Hz
30 KVA/ 24 KW
1650Lbs.
63 x 43.5 x 31.5
J40K400-120
115
400Hz
40 KVA/ 32 KW
1760Lbs.
63 x 43.5 x 31.5
J50K400-120
115
400Hz
50 KVA/ 40 KW
1870Lbs.
63 x 43.5 x 31.5
J60K400-120
115
400Hz
60 KVA/ 48 KW
2420Lbs.
63 x 87 x 31.5
J80K400-120
115
400Hz
80 KVA/ 64 KW
3080Lbs.
63 x 87 x 31.5
J100K400-120
115
400Hz
100 KVA/ 80 KW
3520Lbs.
63 x 87 x 31.5
3-PHASE MODELS
OUTPUT VAC
APPROX.
WEIGHT (LB)
SIZE (H x W x L)
(INCHES)
J10K3/6-120 (120/208)
120/208
60
10KVA / 8KW
770
63x22x31.5
J10K3/5-120 (220/380)
220/380
50
10KVA / 8KW
770
63x22x31.5
J10K3/4-120 (115/200)
115/200
400
10KVA / 8KW
770
63x22x31.5
J20K3/6-120 (120/208)
120/208
60
20KVA / 16KW
880
63x22x31.5
J20K3/5-120 (220/380)
220/380
50
20KVA / 16KW
880
63x22x31.5
J20K3/4-120 (115/200)
115/200
400
20KVA / 16KW
880
63x22x31.5
J30K3/6-120 (120/208)
120/208
60
30KVA / 24KW
1650
63x43.5x31.5
J30K3/5-120 (220/380)
220/380
50
30KVA / 24KW
1650
63x43.5x31.5
J30K3/4-120 (115/200)
115/200
400
30KVA / 24KW
1650
63x43.5x31.5
J40K3/6-120(120/208)
120/208
60
40KVA / 32KW
1760
63x43.5x31.5
J40K3/5-120(220/380)
220/380
50
40KVA/ 32KW
1760
63x43.5x31.5
J40K3/4-120 (115/200)
115/200
400
40KVA/ 32KW
1760
63x43.5x31.5
J50K3/6-120 (120/208)
120/208
60
50KVA / 40KW
1870
63x43.5x31.5
J50K3/5-120 (220/380)
220/380
50
50KVA / 40KW
1870
63x43.5x31.5
J50K3/4-120 (115/200)
115/200
400
50KVA / 40KW
1870
63x43.5x31.5
J60K3/6-120 (120/208)
120/208
60
60KVA / 48KW
2420
63x87x31.5
J60K3/5-120 (220/380)
220/380
50
60KVA / 48KW
2420
63x87x31.5
J60K3/4-120 (115/200)
115/200
400
60KVA / 48KW
2420
63x87x31.5
J80K3/6-120 (120/208)
120/208
60
80KVA / 64KW
3080
63x87x31.5
J80K3/5-120 (220/380)
220/380
50
80KVA / 64KW
3080
63x87x31.5
J80K3/4-120 (115/200)
115/200
400
80KVA / 64KW
3080
63x22x31.5
J100K3/6-120 (120/208)
120/208
60
100KVA / 80KW
3520
63x87x31.5
J100K3/5-120 (220/380)
220/380
50
100KVA / 80KW
3520
63x87x31.5
J100K3/4-120 (115/200)
115/200
400
100KVA / 80KW
3520
63x87x31.5
OUTPUT FREQ CONTINUOUS OUTPUT
(Hz)
POWER
*For Input CIrcuit Breaker, add “B1” suffix to part number
For Solid State Transfer Switch, add “Y11” suffix to part number
JUPITER SERIES DC-AC INVERTERS
STANDARD PRODUCT LISTING - 240 VDC
Overload
SPECIFICATIONS FOR JUPITER 240 VDC
SINGLE & 3-PHASE INVERTER SERIES
PHASE INVERTER
Input Frequency Range
DC INPUT / SINGLE OR 3-PHASE OUTPUT
+/- 5% (wider ranges offered, please consult factory)
Output Voltage (VAC)
3-Phase Models
Please Specify | 120/208 | 220/380 | 230/400 | 240/415 | 277/480 | 120
delta | 220 delta | 240 delta | 380 delta | 480 delta
OR
Single Phase
Please Specify | 120 VAC | 220 VAC | 240 VAC | 480 VAC
Wave Form
Output Power Factor
Frequency Lock Range
Sinewave
0.7 lead to 0.7 lag
+/- 5% (alternate ranges offered on special order)
Output Frequency
(Free Running)
Please Specify: 50 Hz or 60 Hz or 400 Hz (crystal controlled)
Phase Shi Under 100%
Unbalanced Load
THD (Linear Load)
<110%
110-125%
125-150%
>150%
Efficiency (100% Load)
STATIC SWITCH
Voltage Range
Mains <-> Inverter
Audible Noise
Temperature
Humidity
Al tude
EN50091-1,-2
Short Circuit Protec on
Lightning / EMC Filter
Galvanic Isola on
OUTPUT
2% typical 3% max
Con nuous
15 minutes
10 minutes
1 minute
90 - 91% typical
Op onal
Same as AC output. (Different voltages are available upon request)
0 ms (True Online)
<65 dBA (at 1m)
<67 dBA (at 1m)
-10°C to +50°C (Extended ranges available)
0%-95% (Non-condensing)
Up to 1500 m Above Sea Level
Yes
Yes
MOV / Input & Output ( FCC CLASS A)
Input and Output True Galvanic Isola on
LED, LCD, Audible
Alarm
Yes
Remote Control /
Communica on Interface
Monitoring 1~99 Units simultaneously /
Dry Contact, RS-232, RS-485 (Op onal)
SIZE
OUTPUT
FREQ.
J10K60-240
120
60 Hz
10 KVA/ 8 KW
638Lbs.
63 x 22 x 31.5
J20K60-240
120
60 Hz
20 KVA/ 16 KW
770Lbs.
63 x 22 x 31.5
J30K60-240
120
60 Hz
30 KVA/ 24 KW
990Lbs.
63 x 22 x 31.5
J40K60-240
120
60 Hz
40 KVA/ 32 KW
1210Lbs.
63 x 22 x 31.5
J50K60-240
120
60 Hz
50 KVA/ 40 KW
1650Lbs.
63 x 43.5 x 31.5
J60K60-240
120
60 Hz
60 KVA/ 48 KW
1870Lbs.
63 x 43.5 x 31.5
J80K60-240
120
60 Hz
80 KVA/ 64 KW
2090Lbs.
63 x 87 x 31.5
J100K60-240
120
60 Hz
100 KVA/ 80 KW
2420Lbs.
63 x 87 x 31.5
J120K60 240
120
60 Hz
120 KVA/ 96 KW
3300Lbs.
63 x 87 x 31.5
J160K60-240
120
60 Hz
160 KVA/ 128 KW
3960Lbs.
63 x 87 x 31.5
J200K60-240
120
60 Hz
200 KVA/ 160 KW
4840Lbs.
63 x 87 x 31.5
OUTPUT
VAC
OUTPUT
FREQ.
OUTPUT POWER
J10K50- 240(220)
220
50Hz
10 KVA/ 8 KW
638Lbs.
63 x 22 x 31.5
J20K50- 240(220)
220
50Hz
20 KVA/ 16 KW
770Lbs.
63 x 22 x 31.5
J30K50- 240(220)
220
50Hz
30 KVA/ 24 KW
990Lbs.
63 x 22 x 31.5
J40K50- 240(220)
220
50Hz
40 KVA/ 32 KW
1210Lbs.
63 x 22 x 31.5
J50K50- 240(220)
220
50Hz
50 KVA/ 40 KW
1650Lbs.
63 x 43.5 x 31.5
J60K50- 240 (220)
220
50Hz
60 KVA/ 48 KW
1870Lbs.
63 x 43.5 x 31.5
J80K50- 240(220)
220
50Hz
80 KVA/ 64 KW
2090Lbs.
63 x 43.5 x 31.5
J100K50- 240(220)
220
50Hz
100 KVA/ 80 KW
2420Lbs.
63 x 43.5 x 31.5
J120K50- 240(220)
220
50Hz
120 KVA/ 96 KW
3300Lbs.
63 x 87 x 31.5
J160K50- 240(220)
220
50Hz
160KVA/ 128 KW
3960Lbs.
63 x 87 x 31.5
J200K50- 240(220)
220
50Hz
200 KVA/ 160 KW
4840Lbs.
63 x 87 x 31.5
OUTPUT
VAC
OUTPUT
FREQ.
OUTPUT POWER
J10K400- 240
115
400Hz
10 KVA/ 8 KW
638Lbs.
63 x 22 x 31.5
J20K400- 240
115
400Hz
20 KVA/ 16 KW
770Lbs.
63 x 22 x 31.5
J30K400- 240
115
400Hz
30 KVA/ 24 KW
990Lbs.
63 x 22 x 31.5
J40K400- 240
115
400Hz
40 KVA/ 32 KW
1210Lbs.
63 x 22 x 31.5
J50K400- 240
115
400Hz
50 KVA/ 40 KW
1650Lbs.
63 x 43.5 x 31.5
J60K400- 240
115
400Hz
60 KVA/ 48 KW
1870Lbs.
63 x 43.5 x 31.5
J80K400- 240
115
400Hz
80 KVA/ 64 KW
2090Lbs.
63 x 43.5 x 31.5
J100K400- 240
115
400Hz
100 KVA/ 80 KW
2420Lbs.
63 x 43.5 x 31.5
J120K400- 240
115
400Hz
120 KVA/ 96 KW
3300Lbs.
63 x 87 x 31.5
J160K400- 240
115
400Hz
160KVA/ 128 KW
3960Lbs.
63 x 87 x 31.5
J200K400- 240
115
400Hz
200 KVA/ 160 KW
4840Lbs.
63 x 87 x 31.5
50 HZ MODELS
<0.5%
CONTINOUS
VAC
60HZ MODELS
400HZ MODELS
OUTPUT POWER
CONTINOUS
CONTINOUS
WEIGHT
WEIGHT
WEIGHT
(H"x W"x L")
SIZE
(H"x W"x L")
SIZE
(H"x W"x L")
3-PHASE
OUTPUT
OUTPUT
CONTINUOUS
APPROX.
SIZE
MODELS*
VAC
FREQ
OUTPUT
WEIGHT
(H x W x D)
(Hz)
POWER
(LB)
(INCHES)
J10K3/6-240(120/208)
120/208
60
10KVA
638
63x22x31.5
J10K3/5-240(220/380)
220/380
50
10KVA
638
63x22x31.5
J20K3/6-240(120/208)
120/208
60
20KVA
770
63x22x31.5
J20K3/5-240(220/380)
220/380
60
20KVA
770
63x22x31.5
J30K3/6-240(120/208)
120/208
60
30KVA
990
63x22x31.5
J30K3/5-240 (220/380)
220/380
50
30KVA
990
63x22x31.5
J40K3/6-240(120/208)
120/208
60
40KVA
1210
63x22x31.5
J40K3/5-240(220/380)
220/380
50
40KVA
1210
63x22x31.5
J50K3/6-240(120/208)
120/208
60
50KVA
1650
63x44x31.5
J50K3/5-240(220/380)
220/380
50
50KVA
1650
63x44x31.5
J60K3/6-240(120/208)
120/208
60
60KVA
1870
63x43.5x31.5
J60K3/5-240(220/380)
220/380
50
60KVA
1870
63x43.5x31.5
J80K3/6-240(120/208)
120/208
60
80KVA
2090
63x43.5x31.5
J80K3/5-240(220/380)
220/380
50
80KVA
2090
63x43.5x31.5
J100K3/6-240(120/208)
120/208
60
100KVA
2420
63x43.5x31.5
J100K3/5-240(220/380)
220/380
50
100KVA
2420
63x43.5x31.5
J120K3/6-240(120/208)
120/208
60
120KVA
3300
63x87x31.5
J120K3/5-240(220/380)
220/380
50
120KVA
3300
63x87x31.5
J160K3/6-240(120/208)
120/208
60
160KVA
3960
63x87x31.5
J160K3/5-240(220/380)
220/380
50
160KVA
3960
63x87x31.5
J200K3/6-240(120/208)
120/208
60
200KVA
4840
63x87x31.5
J200K3/5-240(220/380)
220/380
50
200KVA
4840
63x87x31.5
JUPITER SERIES DC-AC INVERTERS
SPECIFICATIONS FOR JUPITER 350 VDC
SINGLE & 3-PHASE INVERTER SERIES
PHASE INVERTER
Input Frequency Range
Overload
Output Voltage (VAC)
DC INPUT / SINGLE OR 3-PHASE OUTPUT
+/- 5% (wider ranges offered, please consult factory)
3-Phase Models
Please Specify | 120/208 | 220/380 | 230/400 | 240/415 | 277/480 | 120
delta | 220 delta | 240 delta | 380 delta | 480 delta
OR
Single Phase
Please Specify | 120 VAC | 220 VAC | 240 VAC | 480 VAC
STANDARD PRODUCT LISTING - 350 VDC
3-PHASE
OUTPUT
OUTPUT
CONTINUOUS
APPROX.
SIZE
MODELS*
VAC
FREQ
OUTPUT
WEIGHT
(H x W x D)
(Hz)
POWER
(LB)
(INCHES)
J10K3/5-350(220/380)
220/380
50
10KVA
660
63x22x31.5
J10K3/6-350(120/208)
120/208
60
10KVA
640
63x22x31.5
J10K3/4-350(115/200)
115/200
400
10KVA
640
63x22x31.5
J20K3/5-350(220/380)
220/380
50
20KVA
790
63x22x31.5
J20K3/6-350(120/208)
120/208
60
20KVA
770
63x22x31.5
Wave Form
Output Power Factor
Frequency Lock Range
Sinewave
0.7 lead to 0.7 lag
+/- 5% (alternate ranges offered on special order)
J20K3/4-350(115/200)
115/200
400
20KVA
770
63x22x31.5
Output Frequency
(Free Running)
Please Specify: 50 Hz or 60 Hz or 400 Hz (crystal controlled)
Phase Shi Under 100%
Unbalanced Load
THD (Linear Load)
<110%
110-125%
125-150%
>150%
Efficiency (100% Load)
STATIC SWITCH
Voltage Range
Mains <-> Inverter
Audible Noise
Temperature
Humidity
Al tude
EN50091-1,-2
Short Circuit Protec on
Lightning / EMC Filter
Galvanic Isola on
LED, LCD, Audible Alarm
Remote Control /
Communica on Interface
<0.5%
2% typical 3% max
Con nuous
15 minutes
10 minutes
1 minute
90 - 91% typical
Op onal
Same as AC output. (Different voltages are available upon request)
0 ms (True Online)
<65 dBA (at 1m)
<67 dBA (at 1m)
0-50ºC (32-122ºF) (Other ranges available)
0%-95% (Non-condensing)
Up to 1500 m Above Sea Level
Yes
Yes
MOV / Input & Output ( FCC CLASS A)
Input and Output True Galvanic Isola on
Yes
Monitoring 1~99 Units simultaneously /
Dry Contact, RS-232, RS-485 (Op onal)
J30K3/5-350(220/380)
220/380
50
30KVA
1010
63x22x31.5
J30K3/6-350(120/208)
120/208
60
30KVA
990
63x22x31.5
J30K3/4-350(115/200)
115/200
400
30KVA
990
63x22x31.5
J40K3/5-350(220/380)
220/380
50
40KVA
1230
63x22x31.5
J40K3/6-350(120/208)
120/208
60
40KVA
1210
63x22x31.5
J40K3/4-350(115/200)
115/200
400
40KVA
1210
63x22x31.5
J50K3/5-350(220/380)
220/380
50
50KVA
1580
63x22x31.5
J50K3/6-350(120/208)
120/208
60
50KVA
1540
63x22x31.5
J50K3/4-350(115/200)
115/200
400
50KVA
1540
63x22x31.5
J60K3/5-350(220/380)
220/380
50
60KVA
1800
63x22x31.5
J60K3/6-350(120/208)
120/208
60
60KVA
1760
63x22x31.5
J60K3/4-350(115/200)
115/200
400
60KVA
1760
63x22x31.5
J80K3/5-350(220/380)
220/380
50
80KVA
2040
63x43.5x31.5
J80K3/6-350(120/208)
120/208
60
80KVA
1980
63x43.5x31.5
J80K3/4-350(115/200)
115/200
400
80KVA
1980
63x43.5x31.5
J100K3/5-350(220/380)
220/380
50
100KVA
2490
63x43.5x31.5
J100K3/6-350(120/208)
120/208
60
100KVA
2420
63x43.5x31.5
J100K3/4-350(115/200)
115/200
400
100KVA
2420
63x43.5x31.5
J120K3/5-350(220/380)
220/380
50
120KVA
3410
63x43.5x31.5
J120K3/6-350(120/208)
120/208
60
120KVA
3300
63x43.5x31.5
J120K3/4-350(115/200)
115/200
400
120KVA
3300
63x43.5x31.5
J160K3/5-350(220/380)
220/380
50
160KVA
4100
63x43.5x31.5
J160K3/6-350(120/208)
120/208
60
160KVA
3960
63x43.5x31.5
J160K3/4-350(115/200)
115/200
400
160KVA
3960
63x43.5x31.5
J200K3/5-350(220/380)
220/380
50
200KVA
4900
63x87x31.5
J200K3/6-350(120/208)
120/208
60
200KVA
4840
63x87x31.5
J200K3/4-350(115/200)
115/200
400
200KVA
4840
63x87x31.5
J240K3/5-350(220/380)
220/380
50
240KVA
5760
63x87x31.5
J240K3/6-350(120/208)
120/208
60
240KVA
5760
63x87x31.5
J240K3/4-350(115/200)
115/200
400
240KVA
5760
63x87x31.5
J300K3/5-350(220/380)
220/380
50
300KVA
6160
63x87x31.5
J300K3/6-350(120/208)
120/208
60
300KVA
6160
63x87x31.5
J300K3/4-350(115/200)
115/200
400
300KVA
6160
63x87x31.5
J320K3/5-350(220/380)
220/380
50
320KVA
6510
63x87x31.5
J320K3/6-350(120/208)
120/208
60
320KVA
6510
63x87x31.5
J320K3/4-350(115/200)
115/200
400
320KVA
6510
63x87x31.5
*For Input CIrcuit Breaker, add “B1” suffix to part number
For Solid State Transfer Switch, add “Y11” suffix to part number
JUPITER SERIES DC-AC INVERTERS
TYPICAL DIMENSION DRAWINGS (22” WIDE)
JUPITER SERIES DC-AC INVERTERS
TYPICAL DIMENSION DRAWINGS (43.5” WIDE)
JUPITER SERIES DC-AC INVERTERS
TYPICAL DIMENSION DRAWINGS (87” WIDE)
JUPITER SERIES DC-AC INVERTERS
RELIABILITY AND SERVICEABILITY (MTBF & MTTR)
Reliability is a feature that is designed and integrated into every piece of equipment that carries the Nova Electric name. This is accomplished by utilizing
state of the art circuitry which substantially reduces the total number of components (especially heat producing components). The result is greater
efficiency, high reliability and low cost.
A study of installed units has indicated an MTBF of over 100,000 hours! MTBF figures are based upon ground fixed normal 25-degree ambient
temperature and proper and preventive maintenance.
The MTTR for all items offered is approximately 30 minutes. Part of the maintenance and repair philosophy of the units is to use the BIT equipment to
aid in fault isolation. At that point, a decision is made to either replace an LRU or a component within the power supply with a spare. The construction
methods used throughout the JUPITER Series provide for user friendly service. All circuit boards are plug in and are easily accessed from the front of
the system. Power modules are designed on slide out trays for easy access to all power semiconductors and similar power components. The MTTR
value specified is based upon proper training of local maintenance technicians and engineers.
QUALITY CONTROL
Nova Electric operates under a program of Continuous Quality Improvement (CQI,) as evidenced by its ISO-9001 Qualify Management Systems Standard
Certification and decades of compliance to formal Quality Control systems and procedures that remain in compliance with MIL-I-45208A inspection and
MIL-STD-45662A calibration requirements. ISO registration was granted in 1997 by Underwriters Laboratories (UL) after first assessment. Operators are
certified to J-STD-001A and IPC-A-610B Class 2 (formerly MIL-STD-2000) for soldered assemblies. Instructors certified by the DOD to MIL-STD-2000
Category C are on staff. Our COTS products benefit from the same rigorous QC procedures as original developed for our military customers.
Copies of our current ISO Certificate and Factory Quality Control Manual are available upon request.
MILITARY AND RUGGED COMMERCIAL (COTS) DESIGNS
All of Nova Electric’s products feature robust construction quality and rugged designs. They are suitable for demanding military, industrial, and commercial
applications. Most products can be equipped to meet MIL-STD-461, MIL-STD-810, MIL-S-901, MIL-STD-167, MIL-STD-1399, MIL-STD-1472, and other
important specifications as required. Please consult the factory about your specific application.
GOVERNMENT QUALITY ASSURANCE
Our Quality Assurance Department will be glad to work with the designated Government Quality Assurance Representative (GQAR) on government or
military projects.
WARRANTY
All Nova Electric products are warranted against defects in material and workmanship for a period of one year from shipping
date. Our obligation includes replacing, repairing, or adjusting products (excluding fuses) that prove to be defective during the
warranty period. This warranty is fully transferable. If a product is sold to a manufacturer for use in a product for resale, the
complete warranty is in force, providing the power system is sold as original equipment. Nova Electric assumes no liabilities for
consequential damages of any kind through the use of misuse of its products by the purchaser or others. No other obligations are
expressed or implied. Batteries used with or contained within Uninterruptible Power Supply Systems are sold with a “pass-along”
battery warranty from the battery manufacturer. On site warranty repair is available at extra cost to cover the cost of travel to the
work location. Extended warranties are also available - please consult the factory for details.
Similar pages