MTU DS450D6S Diesel generator set Datasheet

DIESEL GENERATOR SET
DS450D6S
450 kWe /60 Hz /Standby
208 - 600V
(Reference DP400D6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
DS450D6SPA
DS450D6SJA
DS450D6SVA
DS450D6SWA
DS450D6SRA
DS450D6SNA
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
208V**
3
0.8
60
450
563
1561
240V**
3
0.8
60
450
563
1353
380V
3
0.8
60
450
563
855
440V
3
0.8
60
450
563
738
480V**
3
0.8
60
450
563
677
600V**
3
0.8
60
450
563
541
900
572RSL4027
130 °C/40 °C
900
572RSL4027
130 °C/40 °C
12 LEAD LOW WYE
12 LEAD HI DELTA
850
572RSL4029
130 °C/40 °C
12 LEAD HI WYE
900
572RSL4025
130 °C/40 °C
12 LEAD HI WYE
1090
572RSL4025
130 °C/40 °C
4 LEAD WYE
1040
572RSS4270
130 °C/40 °C
4 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//
Emissions – EPA Tier 3 Certified
//
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//
UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality, and performance integrity
- All engine systems are prototype and factory tested
//
Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.
2
/ // / DS450D6S
STANDARD FEATURES*
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
10V 1600 Diesel Engine
- 17.5 Liter Displacement
- Common Rail Fuel Injection
- 4-Cycle
// Engine-generator resilient mounted
// Complete Range of Accessories
//
//
//
//
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- PMG (Permanent Magnet Generator) supply to regulator
- 300% Short Circuit Capability
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
//
STANDARD EQUIPMENT*
//
Engine
Air Cleaners
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filters
Closed Crankcase Ventilation
Jacket Water Pump
Thermostats
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electronic Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
//
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for
up to 10 seconds
Self-Ventilated
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±0.25% Voltage Regulation
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
//
Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
CAN Bus ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
16 Programmable Contact Inputs
Up to 11 Contact Outputs
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // / DS450D6S
APPLICATION DATA
//
Engine
//
Manufacturer
Model
Type
Arrangement
Displacement: L (Cu In)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Max Power: kWm (bhp)
Speed Regulation
Air Cleaner
//
MTU
10V 1600 G70S
4-Cycle
10-V
17.5 (1,068)
12.2 (4.8)
15 (5.91)
17.5:1
1,800
Electronic Isochronous (ADEC)
511 (685)
±0.25%
Dry
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
//
61 (16)
60 (15.9)
99.3 (26.2)
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
//
24
1,050
Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
Total Fuel Flow: L/hr (gal/hr)
#10 JIC 37° Female
M20 x 1.5 Male Adapter Provided
#6 JIC 37° Female
M14 x 1.5 Male Adapter Provided
5 (16)
Diesel #2
401.3 (106)
Fuel Consumption
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
//
Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Rejection to After Cooler: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
//
STANDBY
112 (29.6)
90 (23.7)
65 (17.2)
STANDBY
50 (122)
0.125 (0.5)
466 (123)
235 (13,364)
118 (6,710)
58.6 (3,332)
17.9 (24)
Air Requirements
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
STANDBY
35 (1,250)
642 (22,672)
213 (7,516)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
//
Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
STANDBY
461 (862)
103 (3,623)
15 (60.2)
4
/ // / DS450D6S
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
3,416 x 1,873 x 2,032 mm (134.50 x 73.75 x 80 in)
Weight (dry/less tank)
4,525 kg (9,975 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load
93.4
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
NOx + NMHC
3.31
CO
0.37
RATING DEFINITIONS AND CONDITIONS
PM
0.03
All units are in g/hp-hr and at 100% load.
Emission levels of the engine may vary as a function of ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one
engine representing this rating. The data was obtained
under controlled environmental conditions with calibrated
instrumentation traceable to the United States National Bureau
of Standards and in compliance with US EPA regulations found
within 40 CFR Part 89. The weighted cycle value (not shown)
from each engine is guaranteed to be below the US EPA
Standards at the US EPA defined conditions.
Materials and specifications subject to change without notice.
C/F = Consult Factory/MTU Onsite Energy Distributor
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 8528-1, ISO-3046-1, BS 5514, AS 2789, and DIN 6271.
// Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
//
© MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 559 (77 3E) 2014-01
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Similar pages