Bel LDT481-48 Process control Datasheet

LDT481 Series is a high power switching mode power supplies with
three phase input voltage 400 – 500 VAC, delivering 480 W of output
power, covering output voltages from 24 to 72 V (model dependent).
Their compact size, high efficiency and excellent reliability together
with easy installation make them fit demanding applications where
compactness and high power are needed.
LDT481 Series are suitable for SELV and PELV circuitry (up to 48 VDC
models) and are designed to be mounted on DIN rail and installed
inside a protective enclosure.

3 phase AC input 400 – 500 VAC

Overload 150%

High Efficiency and compact size

Up to 50°C operating temperature with no derating

User settable current limitation (Hiccup or Constant mode)

Easy parallelable for power increase

Natural convection cooling

72 V output model as standard

Automation

Process Control

Communication

Instrumentation Equipment
LDT481 Series
2
LDT481-12
400 - 500 VAC / 520 - 725 VDC
3
12 VDC
40 A
LDT481-24
400 - 500 VAC / 520 - 725 VDC
3
24 VDC
20 A
LDT481-48
400 - 500 VAC / 520 - 725 VDC
3
48 VDC
10 A
LDT481-72
400 - 500 VAC / 520 - 725 VDC
3
72 VDC
6.7 A
Technical parameters are typical, measured in laboratory environment at 25°C and 400 VAC / 50 Hz, at nominal values, after minimum
5 minutes of operation.
Input AC Voltage Range1
Rated, three phase (UL certified)
Operating
400 – 500 VAC
340 – 550 VAC
Input DC Voltage Range
520 – 725 VDC
Input Frequency
47 - 63 Hz
Input AC Current
Input DC Current
Vin = 400 VAC
1.3 A
Vin = 500 VAC
1.1 A
Vin = 520 VAC
1.2 A
Vin = 725 VAC
0.9 A
≤ 50 A
Inrush Peak Current
≤ 0.15 mA
Touch (Leakage) Current
Internal Protection Fuse
None, external fuse must be provided
Recommended External Protection
It is strongly recommended to provide external surge
arresters (SPD) according to local regulations
1
Fuse 3x 10 AT or 3x MCB 10 A C curve
In case of 2 phase operation, reduce the output load to 50% of the nominal value.
Output Power
Rated Voltage (Adjustable Voltage Range)
Continuous Current
Overload Limit (Constant Current Mode)
Overload Limit (Hiccup Mode) (max. 5s)
Load Regulation
Ripple & Noise2
Hold up Time
LDT481-12
LDT481-24
LDT481-48
LDT481-72
LDT481-12
LDT481-24
LDT481-48
LDT481-72
LDT481-12
LDT481-24
LDT481-48
LDT481-72
LDT481-12
LDT481-24
LDT481-48
LDT481-72
LDT481-12
LDT481-24
LDT481-48 / LDT481-72
LDT481-12
LDT481-24 / LDT481-48 / LDT481-72
480 W
12 VDC (12 – 15 VDC)
24 VDC (23 – 28 VDC)
48 VDC (45 – 55 VDC)
72 VDC (72 – 85 VDC)
40 A
20 A
10 A
6.7 A
44 A
22 A
11 A
7.5 A
60 A
30 A
15 A
10 A
≤ 2.5%
≤ 1.0%
≤ 0.5%
≤ 150 mVpp
≤ 100 mVpp
≥ 20 ms
[email protected]
LDT481 Series
Protections
Output Over Voltage Protection
Status Signals
Parallel Connection3
Efficiency
Dissipated Power
2
3
3
Overload, short circuit: Constant current or
Hiccup mode (user settable)
Thermal protection
Output overvoltage
LDT481-12
LDT481-24
LDT481-48
LDT481-72
DC OK - green LED
OVERLOAD - red LED
DC OK - dry contact (NO, 24 VDC / 1 A)
Possible for power or redundancy
(with external ORing module)
LDT481-12
LDT481-24 / LDT481-48
LDT481-72
LDT481-12
LDT481-24 / LDT481-48
LDT481-72
≥ 18 VDC
≥ 33 VDC
≥ 68 VDC
≥ 100 VDC
> 87.5%
> 93.5%
> 94%
< 69 W
< 34 W
< 31 W
Ripple and Noise are measured with 20 MHz bandwidth, probe terminated with a 0.1μF MKP parallel capacitor.
Pay attention, set the current limitation mode jumper on C.C. mode when connecting more units in parallel.
NOTE: Power rating, losses, efficiency, ripple, thermal behaviour and start-up may change outside of the nominal rated input range.
Contact factory for details.
Operating Temperature
UL certified up to 50°C
(Start-up type tested: - 40°C)4
- 40 to + 70°C
Storage Temperature
- 40 to + 80°C
Derating
- 4.5 W/°C over 50°C
Humidity
Non-condensing
5 - 95% RH
Life Time Expectancy
Overvoltage Category
Pollution Degree
Protection Class
At 25°C ambient 75% load
63200 h (7.2 years)
III (EN50178)
2 (IEC60664-1)
Class I
4.2 kVDC
2.2 kVDC
0.75 kVDC
Protection Degree
Input to Output
Input to Ground
Output to Ground
UL508 (certified)
EN60950 (reference)
EN50178 (reference)
EN55011 (CISPR11)
EN55022 (CISPR22)
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-11
EN60529
Vibration sinusoidal
IEC 60068-2-6
Shock
IEC 60068-2-27
Isolation Voltage
Standards & Approvals
EMC Emission
EMC Standards
EMC Immunity
4
Class A
Class A
Level 3
Level 3
Level 3
Level 4
Level 2
IP20
5-17.8 Hz: ±1.6 mm; 17.8-500 Hz: 2g 2Hours /
axis (X,Y,Z)
30 g 6 ms, 20 g 11 ms;
3 bumps / direction, 18 bumps total)
Possible at nominal voltage with load derating.
Europe, Middle East
+353 61 225 977
North America
+1 408 785 5200
© 2016 Bel Power Solutions & Protection
BCD.00845_AB
Asia-Pacific
+86 755 298 85888
LDT481 Series
4
INPUT CONNECTION
3 phase:
L1 = Phase 1
L2 = Phase 2
L3 = Phase 3
= Earth ground
DC:
L1 = + Positive DC
L2 = - Negative DC
L3 = do not connect
= Earth ground
OUTPUT CONNECTION
+ = Positive DC
- = Negative DC
Dry contact = NC
1
AC/DC input
2
4
DC output (load)
Diagnostic Output
(dry contact, NC output OK)
Green LED: Output OK
5
Red LED: Overload
6
Output voltage adjustment
7
Selectable limitation mode
3
Signaling:
DC OK: dry contact
NO
COM
Weight
1.3 kg
Dimensions
80 x 127 x 137.5 mm
Mounting Rail
Connection Terminals
Case Material
Screw type header (16 – 10 AWG)
Screw type header (10 – 6 AWG) ) for output on 12 V model
Aluminum
IEC 60715/H15/TH35-7.5(-15)
1.5 – 6 mm2
6 - 16 mm2
Figure 1. Mechanical Drawing
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.