Omron G3H-203S-DC3-28 New models with international standard Datasheet

Solid State Relays G3@-VD
G3H/G3HD
CSM_G3H_G3HD_DS_E_5_1
New Models with International Standards
Added to G3H Series (-VD in model number).
Same Profile as LY1 and LY2 Bi-power
Relays
• Certified by UL, CSA, and VDE (models numbers with a suffix
of “-VD”).
• Socket type, same size as LY Power Relays.
• Operation indicator provided to confirm input (models numbers
with “N” before the suffix).
Refer to Safety Precautions for All Solid State
Relays.
Note: The socket is optional.
Model Number Structure
■ Model Number Legend
G3H-@@@@@@-@
2 3 4 5 6 7
1
1.
8
Basic Model Name
G3H: Solid State Relay
Rated Load Power Supply Voltage
2:
200 VAC
2.
6.
7.
3, 4. Rated Load Current
03:
5.
3A
Terminal Type
S:
Plug-in terminals
8.
Zero Cross Function
Blank: Equipped with zero cross function
L:
Not equipped with zero cross function
Operation Indicator
Blank: Not equipped with operation indicator
N:
Equipped with operation indicator
Certification
VD:
Certified by UL, CSA, and VDE standards
G3HD-@@@@-@
1
1.
2.
3.
4.
2
3 4 5 6 7
Basic Model Name
G3H: Solid State Relay
Load Power Supply Type
D:
DC
Rated Load Power Supply Voltage
X:
50 VDC
Rated Load Current
03:
3A
5.
6.
7.
Terminal Type
S:
Plug-in terminals
Operation Indicator
Blank: Not equipped with operation indicator
N:
Equipped with operation indicator
Certification
VD:
Certified by UL, CSA, VDE
1
G3H/G3HD
Ordering Information
■ List of Models
Isolation
Zero cross
function
Photocoupler
Yes
Phototriac coupler
No
Indicator
Yes
Rated output load
Rated input voltage
3 A at 100 to 240 VAC
(See note 1.)
Model
5 to 24 VDC
G3H-203SN-VD
5 VDC
G3H-203SLN-VD
12 VDC
24 VDC
Photocoupler
---
Photocoupler
Yes
Phototriac coupler
No
3 A at 4 to 48 VDC
(See note 2.)
No
5 to 24 VDC
3 A at 100 to 240 VAC
(See note 1.)
G3HD-X03SN-VD
4 to 24 VDC
G3H-203S-VD
5 VDC
G3H-203SL-VD
12 VDC
24 VDC
Photocoupler
---
Photodiode array
---
Note: 1.
2.
3.
4.
Yes
3 A at 4 to 48 VDC
(See note 2.)
4 to 24 VDC
G3HD-X03S-VD
2.5 A at 24 to 240 VDC
(See note 3.)
12 to 24 VDC
G3HD-202SN-VD
Product is labelled “240 VAC”.
Product is labelled “48 VDC”.
Product is labelled “240 VDC”.
When ordering, specify the rated input voltage.
■ Accessories (Order Separately)
Connecting Sockets
Item
PTF08A-E
PT08
Connecting
Front connecting
Back connecting
Mounting method/
Terminal type
Track mounted
screw terminals
Solder terminals
Hold-down clip
PYC-A1
PYC-P
PT08-0
PCB terminals
PT08QN
Wire-wrapping terminals
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Input
Model
Rated voltage
Operating voltage
Impedance
Voltage level
Must operate voltage
G3H-203SN-VD
5 to 24 VDC
4 to 28 VDC
15 mA max. (See note 2.)
1 VDC min.
1 VDC min.
4 to 6 VDC
390 Ω±20%
4 VDC max.
12 VDC
9.6 to 14.4 VDC
900 Ω±20%
9.6 VDC max.
24 VDC
19.2 VDC max.
G3H-203SLN-VD 5 VDC
Must release voltage
4 VDC max.
19.2 to 28.8 VDC
2 kΩ±20%
G3HD-X03SN-VD 5 to 24 VDC
4 to 28 VDC
1.5 kΩ +20%/–10% (See note 1.) 4 VDC max.
1 VDC min.
G3H-203S-VD
4 to 24 VDC
3 to 28 VDC
15 mA max. (See note 2.)
3 VDC max.
1 VDC min.
G3H-203SL-VD
5 VDC
4 to 6 VDC
390 Ω±20%
4 VDC max.
1 VDC min.
12 VDC
9.6 to 14.4 VDC
900 Ω±20%
9.6 VDC max.
24 VDC
19.2 to 28.8 VDC
2 kΩ±20%
19.2 VDC max.
4 to 24 VDC
3 to 28 VDC
1.5 kΩ +20%/–10% (See note 1.) 3 VDC max.
1 VDC min.
9.6 to 28.8 VDC
25 mA max. (at 24 VDC)
(See note 2.)
1 VDC min.
G3HD-X03S-VD
G3HD-202SN-VD 12 to 24 VDC
9.6 VDC max.
Note: 1. The input impedance is given for the maximum operating voltage. For details, refer to the Technical Guide for Solid State Relays.
2. With constant current input system.
2
G3H/G3HD
Output
Model
Applicable load
Rated load voltage
G3H-203SN-VD
G3H-203S-VD
Load voltage range
Load current
Inrush current
100 to 240 VAC
75 to 264 VAC
0.1 to 3 A at 40°C
45 A 60 Hz, 1 cycle
G3HD-X03SN-VD
G3HD-X03S-VD
4 to 48 VDC
3 to 52.8 VDC
0.1 to 3 A at 40°C
18 A (10 ms)
G3HD-202SN-VD
24 to 240 VDC
19.2 to 264 VDC
0.001 to 2.5 A at 40°C
20 A (10 ms)
G3H-203SLN-VD
G3H-203SL-VD
■ Characteristics
Model
G3H-203SN-VD/203S-VD G3H-203SLN-VD/203SL-VD G3HD-X03SN-VD/X03S-VD
Operate time
1/2 cycle of load power
source + 1 ms max.
1 ms max.
Release time
1/2 cycle of load power source + 1 ms max.
0.5 ms max.
G3HD-202SN-VD
5 ms max.
2 ms max.
10 ms max.
Output ON voltage drop 1.6 V (RMS) max.
3 V max. (output ON-resistance: 1.25 Ω max.)
Leakage current
5 mA max. (at 100 VAC); 2.5 mA max. (at 100 VAC);
10 mA max. (at 200 VAC) 5 mA max. (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance
Destruction: 1,000 m/s2
Ambient temperature
Operating: –30°C to 80°C (with no icing)
Storage: –30°C to 100°C (with no icing)
Ambient humidity
45% to 85%
Certified standards
G3H: UL508, CSA C22.2 No. 14, EN60947-4-3
G3HD: UL508, CSA C22.2 No. 14, EN60950-1
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Weight
Approx. 50 g
5 mA max. (at 50 VDC)
0.1 mA max. (at 200 VDC)
1,500 VAC, 50/60 Hz for 1 min
Engineering Data
One Cycle Surge Current: Non-repetitive
G3H-203SN-VD/203S-VD/203SLN-VD/
203SL-VD
G3HD-X03SN-VD/X03S-VD
G3HD-202SN-VD
G3H-203SN-VD/203S-VD/203SLN-VD/
G3H-203SL-VD
Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
G3H-203SN-VD, G3H-203S-VD
G3H-203SLN-VD, G3H-203SL-VD
G3HD-X03SN-VD, G3HD-X03S-VD
3
2.5
G3HD-X03SN-VD/X03S-VD
G3HD-202SN-VD
Inrush current (A)
4
Inrush current (A, Peak)
Load current (A)
Load Current vs.
Ambient Temperature
Characteristics
50
40
30
28
26
24
22
20
G3HD-202SN-VD
18
30
16
2
G3HD-X03SN-VD
G3HD-X03S-VD
14
G3HD-202SN-VD
20
1.5
12
10
8
1
6
10
4
0
−30 −20
0
20
40
60
80
100
Ambient temperature (°C)
0
10
30 50 100 200
500 1,000
5,000
Energized time (ms)
2
0
10
20 30
50 70 100
200 300 500 1,000 2,000
Energized time (ms)
3
G3H/G3HD
Dimensions
Note: All units are in millimeters unless otherwise indicated.
(Bottom View)
28 max.
1
2
3
4(+)
Load
5
(+)
(
)
(−)
36.5 max.
42.5 max.
21.5 max.
6(−)
Load
Load power
supply
7
Input
−
−
8
+
+
Input voltage
Note: 1. The plus and minus symbols
shown in the parentheses
are for DC loads.
2. The coil has no polarity.
3. The load is possible to connect
either + side or - side.
Safety Precautions
■ Precautions for Correct Use
EMC Directive Compliance
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
1. AC-switching models comply with EMC Directives under the
following conditions ("-VD" models only).
Less than 3 m
Load
Connection
Input
The SSR for DC switching use can connect to a load regardless of
the polarity of the positive and negative output terminals.
Close Mounting of Multiple Relays
If multiple Relays are mounted side by side, be aware that the outer
wall of each SSR works as a heat sink.
The SSR casing serves to dissipate heat. Install the Relays so that
they are adequately ventilated. If poor ventilation is unavoidable,
reduce the load current by half.
Protective Terminal
No overvoltage absorption element is built in. (The G3HD-202SN
has a built-in varistor.) Be sure to connect an overvoltage absorption
element when using the G3H or G3HD with an inductive load.
G3H-VD
Output
Varistor: 470 V, 0.6 W
Film capacitor: 1 µF, 250 VAC
Varistor
Film Capacitor
• Connect a varistor between the output terminals.
• Connect a film capacitor to the load power supply.
• The input cable must be less than 3 m.
2. DC-switching models comply with EMC Directives under the
following conditions ("-VD" models only).
Less than 10 m
Load
Input
G3HD-VD
Output
• The input cable must be less than 10 m.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
4
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2011.4
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2011 All Right Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
G3H-203S-DC3-28 G3H-203SLN DC24 G3H-203SN DC5-24 G3HD-X03S-DC3-28 G3H-DX03SNDC5-24 G3HD202SN DC12-24V G3HD-X03SN-VD DC5-24 G3HD-X03SN DC5-24
Similar pages