LEM HASS600-S Current transducer hass 50 .. 600- Datasheet

Current Transducer HASS 50 .. 600-S
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.
IPN = 50 .. 600 A
All data are given with RL = 10 kΩ
Electrical data
Primary nominal Primary current
rms current
measuring range
IPN (A)
IPM (A)
50
±150
100
±300
200
±600
300
±900
400
±1100
500
±1100
600
±1100
GTh
Theoretical sensitivity @ IPN
Vout
Analog output voltage @ IP
Vref
Reference voltage 1)
Output voltage
Output impedance
Load impedance
RL
Load resistance
Rout
Output internal resistance
CL
Capacitive loading (±20 %)
UC
Supply voltage (±5 %) 2)
IC
Current consumption @ UC = 5 V
Features
Type
HASS 50-S
HASS 100-S
HASS 200-S
HASS 300-S
HASS 400-S
HASS 500-S
HASS 600-S
0.625 V/ IPN
VOE ±(0.625·IP/ IPN) V
2.5 ±0.025
V
typ. 200
Ω
≥200
Ω
≥2
kΩ
<5
Ω
= 4.7
nF
5 V
19 (typ)
mA
25 (max)
mA
Accuracy - Dynamic performance data
Accuracy 3) @ IPN, TA = 25° C
Linearity error
0 .. IPN
0 .. IPM
TCVOE Temperature coefficient of VOE
(Vout - Vref @ IP = 0)
TCVref Temperature coefficient of Vref
TCG
Temperature coefficient of G
VOE
Electrical offset voltage @ IP = 0, TA = 25 °C
VOM
Magnetic offset voltage @ IP = 0
after an overload of IPM
tra
Reaction time to 10 % of IPN step
tr
Step response time to 90 % of IPN
HASS 50-S
others
di/dt
di/dt accurately followed
IPN ≥100 A
IPN <100 A
Vno
Output voltage noise (DC .. 20 MHz)
BW
Frequency bandwidth (-3 dB) 4)
X
εL
≤±1
%
≤±0.5
%
≤±1
%
≤±0.1
mV/K
≤±190
ppm/K
≤±250
ppm/K
Vref ±0.015
V
<±0.4 %
<3
µs
<4 µs
<3.5
µs
100
A/µs
IPNA/µs
<40 mVpp
DC .. 240
kHz
●● Hall effect measuring principle
●● Galvanic separation between
primary and secondary circuit
●● Insulation test voltage 3300 V
●● Low power consumption
●● Single power supply +5 V
●● Fixed offset & sensitivity
●● Insulating plastic case recognized
according to UL 94-V0.
Advantages
●● Easy installation
●● Small size and space saving
●● Only one design for wide current
ratings range
●● High immunity to external
interference
●● Internal & external reference.
Applications
●● AC variable speed drives and
servo motor drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
●● Industrial.
74.71.25.000.0, 74.71.34.000.0, 74.71.44.000.0, 74.71.46.000.0, 74.71.48.000.0, 74.71.50.000.0, 74.71.52.000.0
5November2014/Version 17
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com
Current Transducer HASS 50 .. 600-S
General data
Ambient operating temperature
Ambient storage temperature
Mass
Standard
TA
TS
m
-40 .. +105
°C
-40 .. +105
°C
55
g
EN 50178: 1997
Notes: 1) It is possible to overdrive Vref with an external reference voltage between
0.5 - 2.65 V providing its ability to sink or source approximately 5 mA
2)
Maximum supply voltage (not operating) <6.5 V
3)
Excluding offset and magnetic offset voltage
4)
Small signal only to avoid excessive heatings of the magnetic core.
Insulation coordination
Rms voltage for AC insulation test, 50 Hz, 1 min
Partial discharge extinction rms voltage @ 10 pC
Impulse withstand voltage 1.2/50 µs
Creepage distance
Clearance distance
Comparative Tracking Index (group I)
Ud
Ue
ÛW
dCp
dCI
CTI
3.3
>1
6
Min
>5.5
>5.5
>600
kV
kV
kV
mm
mm
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
●● Over voltage category OV 3
●● Pollution degree PD2
●● Non-uniform field
EN 50178
IEC 61010-1
Rated insulation voltage
Nominal voltage
Basic insulation
600 V
600 V
Reinforced insulation
300 V
150 V
dCp, dCI, ÛW
Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer’s
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury
and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
5November2014/Version 17
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com
Dimensions HASS 50 .. 600-S (in mm)
22.8
16
Connection
Terminal pin1:
Terminal pin 2:
Terminal pin 3:
Terminal pin 4:
d4.5
10.4
2.5
20
R5.2
Vref (IN/OUT)
Output
0V
+5 V
Ip
4.8
3
1
4
Molex
5
d2.5
Required connection circuit
Terminal Pin
1 Vref(IN/OUT)
2 Output
3 0V
4
+5V
V
(IN/OUT)
ref
1...Vref(IN/OUT)
Output
R =10Kohm
L
0V
2...OUTPUT
+5V
3...0V
4...+5V
Operation principle
+UC
Vout
Vref (IN/OUT)
0V
5November2014/Version 17
5
20
40 +/-0.5
HASS
9.8
R0.5
10.4
30 +/-0.5
20.4
Mechanical characteristics
●●
●●
●●
●●
●●
General tolerance
Aperture for primary conductor
Transducer fastening
Recommended fastening torque
Connection of secondary
Remarks
±0.5 mm
20.4 × 10.4 × 0.5 mm
M4
<1.5 N·m
Molex 5045-04A
●● IS is positive when IP flows in the direction of the arrow.
●● Temperature of the primary conductor should not exceed
120 °C.
●● This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
●● Installation of the transducer must be done unless
otherwise specified on the datasheet, according to LEM
Transducer Generic Mounting Rules. Please refer to
LEM document N°ANE120504 available on our Web site:
Products/Product Documentation.