Vicor IB048E120T40P300 4:1 intermediate bus converter module: up to 500 w output Datasheet

IBC Module
IB0xxE120T40xx-xx
®
S
US
C
C
NRTL
US
4:1 Intermediate Bus Converter Module: Up to 500 W Output
Features
• Input: 36 – 60 Vdc
• 97.8% peak efficiency
(38 – 55 Vdc for IB048x)
• Low profile: 0.38” height above board
• Output: 12.0 Vdc at 48 Vin
• Industry standard 1/8 Brick pinout
• Output current up to 40 A
• Sine Amplitude Converter
• Output power: up to 500 W
Size:
2.30 x 0.9 x 0.38 in
58,4 x 22,9 x 9,5 mm
[A]
• Low noise 1 MHz ZVS/ZCS
• 2,250 Vdc isolation
(1,500 Vdc isolation for IB048x)
[A]
Applications
For lower power applications see 300 W model IB0xxE120T32xx-xx
• Enterprise networks
Product Overview
• Optical access networks
The Intermediate Bus Converter (IBC) Module is a very efficient, low profile, isolated, fixed
• Storage networks
ratio converter for power system applications in enterprise and optical access networks.
• Automated test equipment
Rated at up to 360 W from 38 Vin and up to 500 W from 50 to 55 Vin, the IBC
conforms to an industry standard eighth brick footprint while supplying the power of
a quarter brick. Its leading efficiency enables full load operation at 55°C with only 200
LFM airflow. Its small cross section facilitates unimpeded airflow — above and below
its thin body — to minimize the temperature rise of downstream components.
PART NUMBER DESIGNATION
Input
Voltage
Function
I
B
0
x
IB = Intermediate
Bus Converter
048 = 38 - 55 Vdc
050 = 36 - 60 Vdc
054 = 36 - 60 Vdc*
Package
x
E
Output Voltage
(Nom.) x 10
1
E = Eighth Brick
Format
2
Temperature Grade
0
T
Output
Current
4
T = -40°C ≤ TOPERATING ≤ +100°C
-40°C ≤ TSTORAGE ≤ +125°C
120 = (VOUT nominal @ VIN = 48 Vdc) X 10
(4:1 transfer ratio)
Enable
Logic
Pin
Length
x
x
0
N = Negative
P = Positive
40 = Max Rated Output Current
*w/operating transient to 75 Vdc
IBC MODULE
Rev 1.0
vicorpower.com
Page 1 of 16
03/2015
800 927.9474
1 = 0.145 in
2 = 0.210 in
3 = 0.180 in
Options
-
x
x
00 = Open frame
IB0xxE120T40xx-xx
SPECIFICATIONS
All specifications valid at 48 VIN , 100% rated load and 25°C ambient, unless otherwise indicated.
Absolute Maximum Ratings
Min
Input voltage (+In to –In)
Max
-0.5
75
Unit
Notes
See Input Range Specific
Vdc
Characteristics for details
Input voltage slew rate
5
V/µs
EN to –IN
-0.5
20
Vdc
Output voltage (+Out to –Out)
-0.5
See note
Vdc
See OVP setpoint max
40
A
Pout ≤ 500 W
2,250
(1,500 for IB048x)
Vdc
1 min.
-40
125
°C
Hottest Semiconductor
-55
125
°C
Output current
Dielectric withstand
(input to output)
Temperature
Operating junction
Storage
Electrical Characteristics
Attribute
Symbol
Conditions / Notes
Min
Typ
Max
Unit
38
48
55
75
Vdc
Vdc
0.003
5
V/µs
33
31
2
38
36
Vdc
Vdc
Vdc
µs
µs
INPUT RANGE SPECIFIC CHARACTERISTICS
IB048E120T40xx-xx
Operating input voltage
Non-operating input surge withstand
<100 ms
Operating input dv/dt
Undervoltage protection
Turn-on
Turn-off
Turn-on/ Turn-off hysteresis
Time constant
Undervoltage blanking time
UV blanking time is enabled after start up
Overvoltage protection
Turn-off
Turn-on
Time constant
Peak short circuit input current
DC Output voltage band
Output OVP set point
Dielectric withstand
Insulation resistance
50
100
7
200
12.0
64
64
4
30
13.75
60
55
No load, over Vin range
Module will shut down
Input to output; 1 min
Input to output
IBC MODULE
Rev 1.0
vicorpower.com
Page 2 of 16
03/2015
800 927.9474
9.5
16.2
1,500
30
Vdc
Vdc
µs
A
Vdc
Vdc
Vdc
MΩ
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
All specifications valid at 48 VIN , 100% rated load and 25°C ambient, unless otherwise indicated.
Electrical Characteristics (Continued)
Attribute
Symbol
Conditions / Notes
Min
Typ
Max
Unit
36
48
60
75
Vdc
Vdc
0.003
5
V/µs
31
29
2
36
34
Vdc
Vdc
Vdc
µs
µs
INPUT RANGE SPECIFIC CHARACTERISTICS CONT.
IB050E120T40xx-xx
Operating input voltage
Non-operating input surge withstand
<100 ms
Operating input dv/dt
Undervoltage protection
Turn-on
Turn-off
Turn-on/ Turn-off hysteresis
Time constant
Undervoltage blanking time
UV blanking time is enabled after start up
Overvoltage protection
Turn-off
Turn-on
Time constant
Peak short circuit input current
DC Output voltage band
Output OVP set point
Dielectric withstand
Insulation resistance
No load, over Vin range
Module will shut down
Input to output; 1 min
Input to output
IB054E120T40xx-xx
Operating input voltage
Operating input surge withstand
<100 ms
100
7
200
12
69
69
4
40
15
Vdc
Vdc
µs
A
Vdc
Vdc
Vdc
MΩ
60
75
Vdc
Vdc
0.003
5
V/µs
31
29
2
36
34
Vdc
Vdc
Vdc
µs
µs
50
65
60
9
16.2
2,250
30
36
Operating input dv/dt
Undervoltage protection
Turn-on
Turn-off
Turn-on/ Turn-off hysteresis
Time constant
Undervoltage blanking time
UV blanking time is enabled after start up
Overvoltage protection
Turn-off
Turn-on
Time constant
Peak short circuit input current
DC Output voltage band
Output OVP set point
Dielectric withstand
Insulation resistance
50
48
100
7
200
12
79.5
78
4
30
15
Vdc
Vdc
µs
A
Vdc
Vdc
Vdc
MΩ
30
ms
50
µs
76
75
No load, over Vin range
Module will shut down
Input to output; 1 min
Input to output
9
16.2
2,250
30
COMMON INPUT SPECIFICATIONS
Turn ON delay
VIN reaching turn-on voltage
to enable function operational, see Figure 6
Enable to 10% VOUT; pre-applied VIN,
see Figure 7, 0 load capacitance
Start up inhibit
Turn-on delay
IBC MODULE
Rev 1.0
vicorpower.com
Page 3 of 16
03/2015
800 927.9474
20
25
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
All specifications valid at 48 VIN , 100% rated load and 25°C ambient, unless otherwise indicated.
Electrical Characteristics (Continued)
Attribute
Symbol
Conditions / Notes
Min
Typ
Max
Unit
50
µs
250
ms
3.9
2.4
10.1
18
W
W
A
A
400
mArms
25
A
µF
nH
47
470
µF
0
500
40
W
A
15
%
mΩ
COMMON INPUT SPECIFICATIONS CONT.
From 10% to 90% VOUT, 10% load,
0 load capacitance. See Figure 8
See page 12 for restart after EN pin disable
Output voltage rise time
Restart turn-on delay
No Load power dissipation
Enabled
Disabled
Input current
Inrush current overshoot
3.0
0.17
Low line, full load
Using test circuit in Figure 21, 15% load, high line
At max power;
Using test circuit in Figure 22, See Figure 5
Input reflected ripple current
Repetitive short circuit peak current
Internal input capacitance
Internal input inductance
Recommended external
input capacitance
8.8
5
200 nH maximum source inductance
OUTPUT
Output power [a]
Output current
Output start up load
Effective output resistance
Line regulation (K factor)
of Iout max, maximum output capacitance
Current share accuracy
Efficiency
50% load
Full load
Internal output inductance
Internal output capacitance
Load capacitance
0.247
See Figure 1
See Figure 1
97.4
97.0
Output Overload protection threshold
Over current protection time constant
Short circuit current response time
Switching frequency
Dyanmic response - Load
Vo overshoot/undershoot
Vo response time
Dyanmic response - Line
0.253
10
%
3000
%
%
nH
µF
µF
150
mVp-p
150
%
1.2
1.5
ms
µs
MHz
100
mV
µs
1.25
V
97.8
97.4
1.6
55
0
20 MHz bandwidth (Figure 16),
using test circuit in Figure 23
Of Iout max., will not shutdown when started
into max Cout; and 15% load
Auto restart with duty cycle <10%
Output voltage ripple
60
105
1.0
Load change: +/- 25% of IOUT Max,
Slew rate (di/dt) = 1 A/µs.
See Figures: 11-14
Line step of 5 V in 1 µs, within VIN operating
range. (CIN = 500 uF, CO = 350 uF)
(Figure 15 illustrates similar converter response
when subjected to a more severe line transient.)
Vo overshoot
[a]
VOUT = K • VIN @ no load
Full power operation; See Parallel Operation
on page 13; up to 3 units
4.8
0.250
1
Does not exceed IPC-9592 derating guidelines. At 70°C ambient, full power operation may exceed IPC-9592 guidelines, but does not exceed
component ratings, does not activate OTP and does not compromise reliability.
IBC MODULE
Rev 1.0
vicorpower.com
Page 4 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
Electrical Characteristics (Continued)
Attribute
Symbol
Conditions / Notes
Min
Typ
Max
Unit
15
Vdc
Typ
Max
Unit
130
200
2.4
130
OUTPUT CONT.
Unit will start up into a pre-bias
voltage on the output.
Pre-bias voltage
0
Control & Interface Specifications
Attribute
Symbol
Enable (negative logic)
Module enable threshold
Module enable current
Module disable threshold
Module disable current
Disable hysteresis
Enable pin open circuit voltage
Conditions / Notes
Min
Referenced to –IN
0.8
VEN = 0.8 V
VEN = 2.4 V
500
2.5
EN to –IN resistance
Enable (positive logic)
Module enable threshold
Module disable threshold
EN source current (operating)
EN voltage (operating)
Open circuit, 10 V applied between EN and -IN
Referenced to –IN
3.0
35
2.0
2.5
4.7
5
VEN = 5 V
Vdc
µA
Vdc
µA
mV
Vdc
kΩ
3.0
1.45
2
5.3
Vdc
Vdc
mA
Vdc
General Characteristics
Conditions: 25°C case, 75% rated load and specified input voltage range unless otherwise specified.
Attribute
Symbol
MTBF
Service life
Calculated per Telcordia SR-332, 40°C
Calculated at 30°C
TJ ; Converter will reset when over
temperature condition is removed
Input to output
Input to output
Over temperature shut down
Dielectric withstand
Insulation resistance
Mechanical
Weight
Length
Width
Height above customer board
Pin Solderability
Moisture Sensitivity Level
Clearance to customer board
Conditions / Notes
Min
Typ
Max
1.0
7
125
Mhrs
Years
130
135
1,500
Agency approvals
Altitude, operating
Relative humidity, Operating
RoHS compliance
Storage life for normal solderability
Not applicable, for wave soldering only
From lowest component on IBC
UL60950-1
EN60950-1, IEC60950-1
Derate operating temp 1°C
per 1,000 feet above sea level
Non condensing
Compatible with RoHS directive 2002/95/EC
IBC MODULE
Rev 1.0
vicorpower.com
Page 5 of 16
03/2015
800 927.9474
°C
Vdc
MΩ
30
0.71 / 20.3
2.30 /58.4
0.9/22.9
0.38 /9.5
MSL
Unit
1
N/A
0.12/0.30
oz/g
in/mm
in/mm
in/mm
Years
in/mm
cURus
cTUVus
-500
10,000
Feet
10
90
%
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
IPC-9592A, Based on Class II Category 2 the following detail is applicable. – Pre-conditioning required
Environmental Qualification
Test Description
Test Detail
Quantity Tested
5.2.3 HALT (Highly Accelerated Life testing)
Low Temp
High Temp
Rapid Thermal Cycling
6 DOF Random Vibration Test
Input Voltage Test
Output Load Test
Combined Stresses Test
3
3
3
3
3
3
3
5.2.4 THB (Temp. Humidity Bias)
(72 hr presoak required) 1000 hrs – Continuous Bias
30
5.2.5 HTOB (High Temp. Operating Bias)
Power cycle - On 42 minutes
Off 1 minute, On 1 minute, Off 1 minute, On 1 minute, Off 1 minute,
On 1 minute, Off 1 minute, On 1 minute, Off 10 minutes. Alternating
between maximum and minimum operating Voltage every hour.
5.2.6 TC (Temp. Cycling)
700 cycles , 30 minute dwell at each extreme – 20C minimum ramp rate.
30
5.2.7 Power Cycling
Reference IPC-9592A
3
5.2.8 – 5.2.13 Shock and Vibration
Random Vibration – Operating IEC 60068-2-64 (normal operation vibration)
Random Vibration Non-operating (transportation) IEC 60068-2-64
Shock Operating - normal operation shock IEC 60068-2-27
Free fall - IEC 60068-2-32
Drop Test 1 full shipping container (box)
3
3
3
3
12
5.2.14 Other Environmental Tests
5.2.14.1 Corrosion Resistance – Not required
5.2.14.2 Dust Resistance – Unpotted class II GR-1274-CORE
5.2.14.3 SMT Attachment Reliability IPC-9701 - J-STD-002
5.2.14.4 Through Hole solderability – J-STD-002
N/A
3
3
5
ESD Classification Testing
Sample size assumes CDM testing
12
Total Quantity (est.)
30
161
IBC MODULE
Rev 1.0
vicorpower.com
Page 6 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
WAVEFORMS
Efficiency TAMB 55°C
99%
98%
98%
97%
97%
Efficiency (%)
Efficiency (%)
Efficiency TAMB 25°C
99%
96%
95%
94%
93%
96%
95%
94%
93%
92%
92%
0
8
16
24
32
40
0
8
16
VIN :
38 V
Iout (A)
VIN :
38 V
24
32
Iout (A)
48 V
55 V
48 V
55 V
Figure 2 — Efficiency vs. output current, 55°C ambient
Figure 1 — Efficiency vs. output current, 25°C ambient
Efficiency TAMB 70°C
99%
Efficiency (%)
98%
97%
96%
95%
94%
93%
92%
0
8
16
24
32
40
Iout (A)
VIN :
38 V
48 V
55 V
Figure 3 — Efficiency vs. output current, 70°C ambient
Figure 4 — Inrush current at high line 15% load; 5 A/div
Figure 5 — Input reflected ripple current at nominal line, full load
Figure 6 — Turn on delay time;
VIN turn on delay at nominal line, 15% load
IBC MODULE
Rev 1.0
vicorpower.com
Page 7 of 16
03/2015
800 927.9474
40
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
WAVEFORMS (CONT.)
Figure 7 — Turn on delay time;
Enable turn on delay at nominal line, 15% load
Figure 8 — Output voltage rise time at nominal line, 10% load
Figure 9 — Overshoot at turn on at nominal line, 15% load
Figure 10 — Undershoot at turn off at nominal line, 10% load
Figure 11 — Load transient response; nominal line
Load step 75– 100%
Figure 12 — Load transient response; Full load to 75%; nominal line
IBC MODULE
Rev 1.0
vicorpower.com
Page 8 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
WAVEFORMS (CONT.)
Figure 13 — Load transient response; nominal line
Load step 0 – 25%
Figure 14 — Load transient response; 25–0%; nominal line
Figure 15 — Input transient response;
Vin step low line to high line at full load
Figure 16 — Output ripple; Nominal line, full load
Figure 17 — Two modules parallel array test. VOUT and IIN change when
one module is disabled. Nominal VIN, IOUT = 40 A
Figure 18 — Two modules parallel array test. VOUT and IIN change when
one module is enabled. Nominal VIN, IOUT = 40 A
IBC MODULE
Rev 1.0
vicorpower.com
Page 9 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
WAVEFORMS (CONT.)
Output Current Derating
45
40
40
35
35
Output Current (A)
Output Current (A)
Output Current Derating
45
30
25
20
15
10
30
25
20
15
10
5
5
0
0
25
35
55
45
65
75
85
25
95
35
45
400 LFM
75
85
95
Ambient Temperature (°C)
Ambient Temperature (°C)
200 LFM
65
55
200 LFM
600 LFM
Figure 19 — Maximum output current derating vs ambient air
temperature. Transverse airflow, Board and junction
temperatures within IPC-9592 derating guidelines
400 LFM
600 LFM
Figure 20 — Maximum output current derating vs ambient air
temperature. Longitudinal airflow, Board and junction
temperatures within IPC-9592 derating guidelines
Current Probe
_
47 µF
Current Probe
+OUT
IBC
–IN
–OUT
10 µH
C*
+
Vsource
_
470 µF
+IN
EN
–IN
*Maximum load capacitance
Figure 21 — Inrush current overshoot
10 µF
+IN
Figure 22 — Input reflected ripple current
0.1 µF
+OUT
IBC
–IN
E – Load
–OUT
Cya
Cyc
Cyb
Cyd
20 MHz BW
Cy a-d = 4700 pF
Figure 23 — Test circuit; output voltage ripple
IBC MODULE
Rev 1.0
vicorpower.com
Page 10 of 16
03/2015
800 927.9474
+OUT
Load
Vsource
EN
Load
+IN
+
IBC
–OUT
IB0xxE120T40xx-xx
SPECIFICATIONS (CONT.)
THERMAL DATA
Figure 24 — Thermal plot, 200 LFM, 25°C, 48 Vin, 450 W output power
Figure 25 — Thermal plot, 200 LFM, 25°C, 48 Vin, 450 W output power
Figure 26 — Thermal plot, 400 LFM, 25°C, 48 Vin, 450 W output power
Figure 27 — Thermal plot, 400 LFM, 25°C, 48 Vin, 450 W output power
Figure 28 — Thermal plot, 600 LFM, 25°C, 48 Vin, 450 W output power
Figure 29 — Thermal plot, 600 LFM, 25°C, 48 Vin, 450 W output power
IBC MODULE
Rev 1.0
vicorpower.com
Page 11 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
PIN / CONTROL FUNCTIONS
+In / -In – DC Voltage Input Pins
The IBC input voltage range should not be exceeded. An internal
undervoltage/overvoltage lockout function prevents operation outside of
the normal operating input range. The IBC turns on within an input voltage
window bounded by the “Input under-voltage turn-on” and “Input
over-voltage turn-off” levels, as specified. The IBC may be protected against
accidental application of a reverse input voltage by the addition of a
rectifier in series with the positive input, or a reverse rectifier in shunt with
the positive input located on the load side of the input fuse.
5
1
2 Top View
3
The connection of the IBC to its power source should be implemented with
minimal distribution inductance. If the interconnect inductance exceeds
100 nH, the input should be bypassed with a RC damper to retain low
source impedance and stable operation. With an interconnect inductance
of 200 nH, the RC damper may be 47 µF in series with 0.3 Ω. A single
electrolytic or equivalent low-Q capacitor may be used in place of the series
RC bypass.
4
Pin
1
2
3
4
5
EN - Enable/Disable
Negative Logic Option
If the EN port is left floating, the IBC output is disabled. Once this port ispulled lower than 0.8 Vdc with respect to –In, the output is enabled. The
EN port can be driven by a relay, opto-coupler, or open collector transistor.
Refer to Figures 6 and 7 for the typical enable / disable characteristics. This
port should not be toggled at a rate higher than 1 Hz. The EN port should
also not be driven by or pulled up to an external voltage source.
Figure 30 — IBC Pin Designations
Positive Logic Option
If the EN port is left floating, the IBC output is enabled. Once this port is
pulled lower than 1.4 Vdc with respect to –In, the output is disabled. This
action can be realized by employing a relay, opto-coupler, or open collector
transistor. This port should not be toggled at a rate higher than 1 Hz.
The EN port should also not be driven by or pulled up to an external voltage
source. The EN port can source up to 2 mA at 5 Vdc. The EN port should
never be used to sink current.
If the IBC is disabled using the EN pin, the module will attempt to restart
approximately every 250ms. Once the module has been disabled for at least
250ms, the turn on delay after the EN pin is enabled will be as shown in
Figure 7.
+Out / -Out – DC Voltage Output Pins
Total load capacitance at the output of the IBC should not exceed the
specified maximum. Owing to the wide bandwidth and low output
impedance of the IBC, low frequency bypass capacitance and significant energy storage may be more densely and efficiently provided by adding
capacitance at the input of the IBC.
IBC MODULE
Rev 1.0
vicorpower.com
Page 12 of 16
03/2015
800 927.9474
Function
Vin+
Enable
VinVoutVout+
IB0xxE120T40xx-xx
APPLICATIONS NOTE
Parallel Operation
Input Impedance Recommendations
The IBC will inherently current share when operated in an array. Arrays may
be used for higher power or redundancy in an application. Current sharing
accuracy is maximized when the source and load impedance presented to
each IBC within an array are equal. The recommended method to achieve
matched impedances is to dedicate common copper planes within the PCB
to deliver and return the current to the array, rather than rely upon traces
of varying lengths. In typical applications the current being delivered to the
load is larger than that sourced from the input, allowing narrower traces to
be utilized on the input side if necessary. The use of dedicated power
planes is, however, preferable.
To take full advantage of the IBC capabilities, the impedance presented to
its input terminals must be low from DC to approximately 5 MHz.
The source should exhibit low inductance and should have a critically
damped response. If the interconnect inductance is excessive, the IBC input
pins should be bypassed with an RC damper (e.g., 47 µF in series with
0.3 Ω) to retain low source impedance and proper operation. Given the
wide bandwidth of the IBC, the source response is generally the limiting
factor in the overall system response.
One or more IBCs in an array may be disabled without adversely affecting
operation or reliability as long as the load does not exceed the rated power
of the enabled IBCs.
The IBC power train and control architecture allow bi-directional power
transfer, including reverse power processing from the IBC output to its
input. The IBC’s ability to process power in reverse improves the IBC transient response to an output load dump.
Thermal Considerations
The temperature distribution of the VI Brick can vary significantly
with its input /output operating conditions, thermal management and
environmental conditions. Although the PCB is UL rated to 130°C, it is
recommended that PCB temperatures be maintained at or below 125°C.
For maximum long term reliability, lower PCB temperatures are
recommended for continuous operation, however, short periods of
operation at 125°C will not negatively impact performance or reliability.
Anomalies in the response of the source will appear at the output of the
IBC multiplied by its K factor. The DC resistance of the source should be
kept as low as possible to minimize voltage deviations. This is especially
important if the IBC is operated near low or high line as the
overvoltage/undervoltage detection circuitry could be activated.
Input Fuse Recommendations
The IBC is not internally fused in order to provide flexibility in configuring
power systems. However, input line fusing of VI Bricks must always be
incorporated within the power system. A fast acting fuse should be placed
in series with the +In port. See safety agency approvals.
Application Notes
For IBC and VI Brick application notes on soldering, thermal management,
board layout, and system design visit vicorpower.com.
WARNING: Thermal and voltage hazards. The IBC can operate with surface
temperatures and operating voltages that may be hazardous to personnel.
Ensure that adequate protection is in place to avoid inadvertent contact.
IBC MODULE
Rev 1.0
vicorpower.com
Page 13 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
IBC BLOCK DIAGRAM
Reverse
Current
Protection
Current
Transformer
FET Drive
Transformer
Secondary
Main
Transformer
Current
Sense
FET Drive
Transformer
Primary
Lr
Cr
⎯
Q
Controller
Q
Current
Sense
Voltage
Sense
EN
-IN
+IN
UVLO
OVLO
Sensing
CIN
V2 (VCC)
VB
Switching
Regulator
FET Drive
Transformer
Primary
FET Drive
Transformer
Secondary
Resonant
Tank
IBC Block Diagram
FET Drive
Transformer
Secondary
Primary
Isolation
Barrier
Secondary
COUT
-OUT
+OUT
The Sine Amplitude Converter TM (SAC TM) uses a high frequency resonant tank to transfer energy from input to output. The resonant tank is formed by Cr and
leakage inductance from the main transformer, Lr, as shown in the block diagram. The controller regulates switching frequency of the FET drivers, monitors
current sensing, and provides undervoltage and overvoltage protection.
Figure 31 — IBC Block diagram
IBC MODULE
Rev 1.0
vicorpower.com
Page 14 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
MECHANICAL DRAWINGS
Pin Length (X)
Designator
Length
1
0.145 [3.68]
2
0.21 [5.33]
3
0.18 [4.57]
(X)
Figure 32 — IBC outline drawing
Top View
Figure 33 — IBC PCB recommended hole pattern
IBC MODULE
Rev 1.0
vicorpower.com
Page 15 of 16
03/2015
800 927.9474
IB0xxE120T40xx-xx
Vicor’s comprehensive line of power solutions includes high density AC-DC and DC-DC modules and accessory components, fully configurable AC-DC and DC-DC power supplies, and complete custom power
systems.
Information furnished by Vicor is believed to be accurate and reliable. However, no responsibility is assumed by Vicor for its use. Vicor makes no
representations or warranties with respect to the accuracy or completeness of the contents of this publication. Vicor reserves the right to make
changes to any products, specifications, and product descriptions at any time without notice. Information published by Vicor has been checked and
is believed to be accurate at the time it was printed; however, Vicor assumes no responsibility for inaccuracies. Testing and other quality controls are
used to the extent Vicor deems necessary to support Vicor’s product warranty. Except where mandated by government requirements, testing of all
parameters of each product is not necessarily performed.
Specifications are subject to change without notice.
Vicor’s Standard Terms and Conditions
All sales are subject to Vicor’s Standard Terms and Conditions of Sale, which are available on Vicor’s webpage or upon request.
Product Warranty
In Vicor’s standard terms and conditions of sale, Vicor warrants that its products are free from non-conformity to its Standard Specifications (the “Express Limited Warranty”). This warranty is extended only to the original Buyer for the period expiring two (2) years after the date of shipment and is
not transferable.
UNLESS OTHERWISE EXPRESSLY STATED IN A WRITTEN SALES AGREEMENT SIGNED BY A DULY AUTHORIZED VICOR SIGNATORY, VICOR DISCLAIMS
ALL REPRESENTATIONS, LIABILITIES, AND WARRANTIES OF ANY KIND (WHETHER ARISING BY IMPLICATION OR BY OPERATION OF LAW) WITH RESPECT TO THE PRODUCTS, INCLUDING, WITHOUT LIMITATION, ANY WARRANTIES OR REPRESENTATIONS AS TO MERCHANTABILITY, FITNESS FOR
PARTICULAR PURPOSE, INFRINGEMENT OF ANY PATENT, COPYRIGHT, OR OTHER INTELLECTUAL PROPERTY RIGHT, OR ANY OTHER MATTER.
This warranty does not extend to products subjected to misuse, accident, or improper application, maintenance, or storage. Vicor shall not be liable
for collateral or consequential damage. Vicor disclaims any and all liability arising out of the application or use of any product or circuit and assumes
no liability for applications assistance or buyer product design. Buyers are responsible for their products and applications using Vicor products and
components. Prior to using or distributing any products that include Vicor components, buyers should provide adequate design, testing and operating safeguards.
Vicor will repair or replace defective products in accordance with its own best judgment. For service under this warranty, the buyer must contact
Vicor to obtain a Return Material Authorization (RMA) number and shipping instructions. Products returned without prior authorization will be returned to the buyer. The buyer will pay all charges incurred in returning the product to the factory. Vicor will pay all reshipment charges if the product was defective within the terms of this warranty.
Life Support Policy
VICOR’S PRODUCTS ARE NOT AUTHORIZED FOR USE AS CRITICAL COMPONENTS IN LIFE SUPPORT DEVICES OR SYSTEMS WITHOUT THE EXPRESS
PRIOR WRITTEN APPROVAL OF THE CHIEF EXECUTIVE OFFICER AND GENERAL COUNSEL OF VICOR CORPORATION. As used herein, life support devices or systems are devices which (a) are intended for surgical implant into the body, or (b) support or sustain life and whose failure to perform
when properly used in accordance with instructions for use provided in the labeling can be reasonably expected to result in a significant injury to the
user. A critical component is any component in a life support device or system whose failure to perform can be reasonably expected to cause the
failure of the life support device or system or to affect its safety or effectiveness. Per Vicor Terms and Conditions of Sale, the user of Vicor products
and components in life support applications assumes all risks of such use and indemnifies Vicor against all liability and damages.
Intellectual Property Notice
Vicor and its subsidiaries own Intellectual Property (including issued U.S. and Foreign Patents and pending patent applications) relating to the products described in this data sheet. No license, whether express, implied, or arising by estoppel or otherwise, to any intellectual property rights is
granted by this document. Interested parties should contact Vicor's Intellectual Property Department.
The products described on this data sheet are protected by the following U.S. Patents Numbers:
5,945,130; 6,403,009; 6,710,257; 6,911,848; 6,930,893; 6,934,166; 6,940,013; 6,969,909; 7,038,917;
7,166,898; 7,187,263; 7,361,844; D496,906; D505,114; D506,438; D509,472; and for use under 6,975,098 and 6,984,965
Vicor Corporation
25 Frontage Road
Andover, MA, USA 01810
Tel: 800-735-6200
Fax: 978-475-6715
email
Customer Service: [email protected]
Technical Support: [email protected]
IBC MODULE
Rev 1.0
vicorpower.com
Page 16 of 16