Panel Meters and Controllers AC Ammeter or Voltmeter Type DI3-DIN AV1/AV5 • 3-dgt µP-based for AC currents or voltages • Selectable CT/VT primary range • DIN-rail mounting • Degree of protection (front): IP 40 Product Description Ordering Key 3-dgt µP-based meter with double input for AC currents or voltages. With 20 selectable CV/VT primary ranges. Model Range code Measurement Power supply Setpoints Options The housing is for DIN-rail mounting and ensures a degree of protection (front) of IP 40. Type Selection Range code AV1: AV5: Supply Specifications Power supply 1 A/100 V Standard current/voltage 5 A/500 V Standard current/voltage See Range Table AC supply 24 VAC, -15% +10%, 50/60 Hz B: 48 VAC, -15% +10%, 50/60 Hz C: 115 VAC, -15% +10%, 50/60 Hz D: 230 VAC, -15% +10%, 50/60 Hz (standard) Power supply on request A: 1) 1) Overload protection Cont. Current: Voltage: For 1 s Current: Voltage: Accuracy (@ 25°C ± 5°C, R.H. ≤ 60%) Temperature drift Display Sampling rate Indication Max. Min. 500 VAC range Other ranges Over range Input range selection Decimal point position Power consumption 230 VAC, -15% +10%, 50/60 Hz (standard) 24 VAC, 48 VAC, 115 VAC, -15% +10%, 50/60 Hz (on request) 3.2 VA 1) 1) Input Specifications Rated input DI3-DIN AV5AD0XX General Specifications 5 A/500 VAC, 45 to 400 Hz (1 A/100 VAC on request) Operating temperature Storage temperature 1.2 x rated input 1.2 x rated input 5 x rated input 2 x rated input ± 0.5% f.s., ± 1 dgt ± 350 ppm/ºC 7-segment LED, h 14.2 mm, 3 digits 1 time/s 999 000 Scalesuppressionupto5%f.s. Scalesuppressionupto 3% f.s. EEE DIP-switch selectable DIP-switch selectable Specifications are subject to change without notice Insulation reference voltage Dielectric strength Noise rejection CMRR EMC Safety standards Connector Housing Dimensions Material Degree of protection Weight Approvals 0° to 50°C (32° to 122°F) (R.H. < 90% non-condensing) -10° to 60°C (14° to 140°F) (R.H. < 90% non-condensing) 300 V to ground 4000 V for 1 minute rms rms 100 dB, 40 to 60 Hz. IEC 60801-2, IEC 60801-3, IEC 60801-4 (level 2), EN 50 081-1, EN 50 082-1 EN 61 010-1, IEC 61010-1, VDE 0411 Screw-type 89 x 53.5 x 58.5 mm (3-DIN modules) ABS, self-extinguish.: UL 94 V-0 Front: IP 40 Approx 200 g CE, CSA 1 DI3-DIN AV1/AV5 Range Table Range Connection 1A/100 V 5A/500 V 10 A 15 A 25 A 40 A 50 A 60 A 100 A 150 A 220 V 250 A 380 V 400 A 500 A/V 500 A 600 A/V 600 A 1000 A/V 1000 A Direct 1A Direct 5A CT10/1 A CT15/1 A CT25/1 A CT40/1 A CT50/1 A CT60/1 A CT100/1 A CT150/1 A CT10/5 A CT15/5 A CT25/5 A CT40/5 A CT50/5 A CT60/5 A CT100/5 A CT150/5 A CT250/1 A CT250/5 A CT400/1 A CT500/1 A CT500/5 A CT600/1 A CT600/5 A CT1000/1 A CT1000/5 A CT400/5 A Direct 100 V Direct 500 V VT220/100 V VT380/100 V VT500/100 V VT600/100 V VT1000/100 V Decimal point Resolution position Voltage drop Input imp. Range code ammeters voltmeters 999/99.9 9.99/999 9.99 99.9 99.9 99.9 99.9 99.9 99.9 999 999 999 999 999 999 999 999 999 999 999 1V 250 mV 1 V/250 mV 1 V/250 mV 1 V/250 mV 1 V/250 mV 1 V/250 mV 1 V/250 mV 1 V/250 mV 1 V/250 mV 1 MΩ 1 MΩ V AV1 AV5 AV1/AV5 AV1/AV5 AV1/AV5 AV1/AV5 AV1/AV5 AV1/AV5 AV1/AV5 AV1/AV5 AV1 AV1/AV5 AV1 AV1/AV5 AV1 AV5 AV1 AV5 AV1 AV5 1 MΩ 1 V/250 mV 1 MΩ 1 V/250 mV 1V 250 mV 1V 250 mV 1V 250 mV 1 MΩ 1 MΩ 1 MΩ Dimensions (mm) A 45 89 Front Panel Description 1 mA/0.1 V 10 mA/1 V 10 mA 100 mA 100 mA 100 mA 100 mA 100 mA 100 mA 1A 1V 1A 1V 1A 1 A/V 1A 1 A/V 1A 1 A/V 1A 1 53.5 49.5 58.5 1. Display 3-dgt (maximum read-out 999). 46 54.5 Alphanumeric indication by means of 7-segment display for: - Displaying of the measured value, over-range. Wiring Diagrams 2 Power supply 4 5 6 7 8 1 2 3 Power supply 4 5 6 7 8 IN V 3 NC 2 IN 1 IN A 8 NC 7 V.T. IN V 6 NC 5 IN A Power supply 4 IN 3 NC 2 IN V 1 NC 8 IN 7 IN A 6 NC 5 Voltage measurements Direct C.T. IN V Power supply 4 NC 3 IN 2 NC 1 IN A Current measurements Direct Specifications are subject to change without notice