PHOENIX EMD-FL-3V-690 Electronic monitoring relay for voltage monitoring in three-phase network Datasheet

EMD-FL-3V-690
Electronic monitoring relay for voltage monitoring in
three-phase networks
INTERFACE
Data sheet
103233_en_01
1
© PHOENIX CONTACT - 09/2009
Description
Increasingly higher demands are being placed on safety and
system availability – across all sectors. Processes are
becoming more and more complex, not only in mechanical
engineering and the chemical industry, but also in plant and
automation technology. Demands on power engineering are
also increasing constantly.
Features
–
–
–
–
–
–
Error-free and therefore cost-effective operation can only be
achieved through continuous monitoring of important network –
and system parameters. Electronic monitoring relays in the –
EMD series are available for a wide range of monitoring tasks –
to avoid the consequences of errors or to keep them within
limits.
Undervoltage monitoring
Window function
Phase sequence monitoring
Phase failure monitoring
Asymmetry monitoring
Adjustable threshold values
Adjustable response delay
Power supply via power module can be selected
Two PDTs
The operating states are indicated using colored LEDs, errors
that may occur can be sent to a control system via a floating
contact or can shut down a part of the system. Some device
versions are equipped with startup and response delays in
order to briefly tolerate measured values outside the set
monitoring range.
WARNING: Risk of electric shock
Never carry out work when voltage is present.
Make sure you always use the the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
EMD-FL-3V-690
2
Ordering data
Description
Order No.
Pcs. / Pkt.
Electronic monitoring relay for voltage monitoring in three-phase networks EMD-FL-3V-690
2885249
1
Accessories
Type
Order No.
Pcs. / Pkt.
Power modules, pluggable, for EMD-FL-..., supply voltage:
88 V AC ... 121 V AC
EMD-SL-PS45-110AC
2885281
1
Power modules, pluggable, for EMD-FL-..., supply voltage:
108 V AC ... 132 V AC
EMD-SL-PS45-120AC
2885744
1
Power modules, pluggable, for EMD-FL-..., supply voltage:
195 V AC ... 264 V AC
EMD-SL-PS45-230AC
2885294
1
Power modules, pluggable, for EMD-FL-..., supply voltage:
323...456 V AC
EMD-SL-PS45-400AC
2885304
1
Power modules, pluggable, for EMD-FL-..., supply voltage:
425...550 V AC
EMD-SL-PS45-500AC
2885317
1
3
Type
Technical data
Input data
Input name
Measuring input
Measured value
AC sine (48 Hz ... 63 Hz)
Protection
max. 20 A
Nominal input voltage UN
3 ~ 690 V
Maximum input voltage
3 ~ 950 V
Input resistance of voltage input
1 MΩ
Maximum temperature coefficient
< 0.1 %/K
Setting range for response delay
0.1 s ... 10 s
Min. setting range
-30 % ... 20 % (From UN)
Max. setting range
-20 % ... 30 % (From UN)
Min setting range of the voltage threshold value
483 V AC ... 828 V AC
Max. setting range of the voltage threshold value
552 V AC ... 897 V AC
Function
Undervoltage, window, asymmetry, phase sequence, phase failure
Basic accuracy
± 5 % (of scale end value)
Setting accuracy
≤ 5 % (of scale end value)
Repeat accuracy
≤2%
Asymmetry
5 % ... 25% / OFF
Recovery time
500 ms
Output data
Contact type
2 floating PDT contacts
Nominal insulation voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse
5 A (fast-blow)
Supply
Range of supply voltages
110 V AC ... 500 V AC (see Power modules)
Frequency range
50 Hz ... 60 Hz
Nominal power consumption
4.5 VA (1.5 W)
103233_en_01
PHOENIX CONTACT
2
EMD-FL-3V-690
General data
Mains type
3-phase
Service life mechanical
Approx. 2 x 107 cycles
Service life, electrical
2 x 105 cycles at ohmic load, 1000 VA
Switching frequency
max. 60 (per minute at 100 VA ohmic load)
max. 6 (per minute at 1000 VA ohmic load)
Operating mode
100% operating factor
Degree of protection
IP40 (housing) / IP20 (connection terminal blocks)
Pollution degree
2 (according to EN 50178)
Surge voltage category
III, basic insulation (as per EN 50178)
Rated insulation voltage
300 V (According to EN 50178)
Assembly
on TS 35 profile rail acc. to EN 60715
Mounting position
Any
Width
45 mm
Height
113 mm
Length
90 mm
Type of housing
Polyamide PA, self-extinguishing
Color
green
Weight
280 g
Connection data
Conductor cross section, solid
0.5 mm² ... 2.5 mm²
Conductor cross section, stranded
0.25 mm² ... 2.5 mm²
Stripping length
8 mm
Type of connection
Screw connection
Tightening torque
1 Nm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
15 % ... 85 %
Climatic class
3K3 (in acc. with EN 60721)
Conformance / approvals
Conformity
CE compliant
UL, USA / Canada
UL/C-UL listed UL 508
Conformance with EMC directive 2004/108/EC
Immunity to interference according to
EN 61000-6-2
Emitted interference according to
EN 61000-6-3
Conformance with LV directive 2006/95/EC
Electronic equipm. for electrical power installations according to
103233_en_01
EN 50178
PHOENIX CONTACT
3
EMD-FL-3V-690
4
Block diagram
16 18 26 28
L1
L2
L3
15
A1
25
POWER
U = 110...500 V AC
MODULE
A2
5
Safety notes
WARNING: Risk of electric shock
Never carry out work when voltage is present.
6
10 15
20
5
AS
MA
X
-10
+3
(% 0
)
0
MIN
5
12
W
S
FU
NC US
TIO
N
18
A2
16
18
A2
6
7
1
2
3
4
5
6
7
8
9
10
11
12
"ASYM" LED: Asymmetry
"MAX" LED: Upper threshold value
"MIN" LED: Lower threshold value
"SEQ" LED: Phase sequence
"REL" LED: Output relay
"FUNCTION" rotary switch: Function selection
"DELAY" potentiometer: Response delay
"MIN" potentiometer: Lower threshold value
"MAX" potentiometer: Upper threshold value
"ASYM" potentiometer: Asymmetry
Universal snap-on foot for EN DIN rails
Power module
11
EMD-FL-3V-690
REL
DE
LA 10
Y (s
U
)
W
16
+2
(% 0
)
7
0
5
L3
Y M 25
(%
0
)
-10
-20
-20
SEQ
4
AC
30
5-2 4
S4 29
L-P8 85
D-So.:2
EM .-N
Ord
~
0V
23 2VVA
Hz 64
/60 0 2
505 23
19
15
L2
3~ Voltage monitor
MIN
3
ASYM
2
A1
L1
MAX
1
Structure
7
8
9
10
Power supply
The power module for power supply is supplied in a transport casing to prevent the connection legs from being bent.
To install the power module in the relay housing, remove the transport casing and position the power module in the recess
in the side of the housing (ensure that it is the right way round). The red locking latches snap in with an audible click when
the power module is securely positioned.
To remove the power module, press the two red locking latches together and pull out the power module.
103233_en_01
PHOENIX CONTACT
4
EMD-FL-3V-690
8
Installation
WARNING: Risk of electric shock
Never carry out work when voltage is present.
The module can be snapped onto all 35 mm DIN rails according to EN 60715.
9
Diagnostics
The LEDs indicate the following error states:
"ASYM" LED (Red)
–
–
LED flashes: Set threshold value exceeded, set delay time is running
LED ON: Set threshold value exceeded, delay time has elapsed
"MIN" and "MAX" LEDs (Red)
–
–
–
LED flashes: Set threshold value exceeded, set delay time is running
LED ON: Set threshold value exceeded, delay time has elapsed
Both LEDs flash alternately: Lower set threshold value is greater than upper threshold value
"SEQ" LED (Red)
–
LED ON: Phases connected incorrectly. LED lights up immediately, relay drops out without delay.
"REL" LED (Yellow)
–
–
LED ON: Output relay has picked up
LED OFF: Output relay has dropped out
103233_en_01
PHOENIX CONTACT
5
EMD-FL-3V-690
10
Connection example
L1
L2
L3
N
max. 20 A
A1
15
L1
L2
16
L3
15
25
16 18
26 28
18
A2
25
26
28
3 ~ 690 V measuring range with 400 V AC power module
(3 ~ 690 V AC mains)
11
Function
If an error is present when the monitoring module is activated,
output relay "R" remains dropped out and the LED for the
corresponding threshold value lights up.
For all functions the "MIN" and "MAX" LEDs flash alternately
if the minimum value selected is greater than the maximum
value.
The "FUNCTION" rotary switch is used to set the desired
function:
– U = Undervoltage monitoring (UNDER)
– US = Undervoltage Monitoring With Phase Sequence
and Phase Failure Monitoring (UNDER + SEQ)
– W = Monitoring of the area between thresholds MIN and
MAX (window function) (WIN)
– WS = Monitoring of the area between thresholds MIN
and MAX (window function) with phase sequence and
phase failure monitoring (WIN + SEQ)
103233_en_01
PHOENIX CONTACT
6
EMD-FL-3V-690
Undervoltage Monitoring (UNDER and UNDER + SEQ)
U
LED U
LED MAX
If the measured voltage (average value of the linked voltages)
falls below the value set at the "MIN" controller, the set
response delay (DELAY) starts (red "MIN" LED flashes). After
the delay time has elapsed (red "MIN" LED is ON), output
relay "R" drops out (yellow "REL" LED is OFF).
If the measured voltage exceeds the value set at the "MAX"
controller, output relay "R" picks up again (yellow "REL" LED
is ON).
LED MIN
LED REL, R
MAX
MIN
START
DELAY
< DELAY
Window Function (WIN and WIN + SEQ)
U
LED U
LED MAX
LED MIN
LED REL, R
MAX
MIN
DELAY
< DELAY DELAY
Output relay "R" picks up (yellow "REL" LED is ON) if the
measured voltage (average value of the linked voltages)
exceeds the value set at the "MIN" controller. If the measured
voltage exceeds the value set at the "MAX" controller, the set
response delay (DELAY) starts (red "MAX" LED flashes).
After the delay time has elapsed (red "MAX" LED is ON),
output relay "R" drops out (yellow "REL" LED is OFF).
Output relay "R" picks up again (yellow "REL" LED is ON) if
the measured voltage falls below the maximum value again
(red "MAX" LED is OFF). If the measured voltage falls below
the value set at the "MIN" controller, the set response delay
(DELAY) starts (red "MIN" LED flashes).
After the delay time has elapsed (red "MIN" LED is ON),
output relay "R" drops out (yellow "REL" LED is OFF).
Phase Sequence Monitoring (SEQ)
Phase sequence monitoring can be enabled for all functions.
In the event that the phase direction has been modified (red
"SEQ" LED is ON), output relay "R" drops out without delay
(yellow "REL" LED is OFF).
Phase Failure Monitoring (SEQ)
In the event that one of the phase voltages fails, the set
response delay (DELAY) starts (red "SEQ" LED flashes).
After the time delay has elapsed (red "SEQ" LED is ON),
output relay "R" drops out (yellow "REL" LED is OFF).
Reverse voltages (e.g., motors that continue running on two
phases) are not detected using this function. This is done by
monitoring asymmetry using a suitable selection of
thresholds.
103233_en_01
PHOENIX CONTACT
7
EMD-FL-3V-690
Asymmetry Monitoring
If the asymmetry of the linked voltages exceeds the value set
at the "ASYM" controller, the set response delay (DELAY)
starts (red "ASYM" LED flashes). After the delay time has
elapsed (red "ASYM" LED is ON), output relay "R" drops out
(yellow "REL" LED is OFF).
If a neutral conductor is connected, the asymmetry between
the phase voltages (star voltage) and neutral conductor is
also monitored. In this case both asymmetry values are used
for evaluation. As soon as one of the two values exceeds the
value set at the "ASYM" controller, the response delay starts
(red "ASYM" LED flashes). After the delay time has elapsed
(red "ASYM" LED is ON), output relay "R" drops out (yellow
"REL" LED is OFF).
Neutral Conductor Break Monitoring Using Asymmetry
Monitoring
A neutral conductor break between the system and supply
network is detected as an asymmetry between the phase
voltages and the neutral conductor, and the response delay
(DELAY) starts (red "ASYM" LED flashes). After the delay
time has elapsed (red "ASYM" LED is ON), output relay "R"
drops out (yellow "REL" LED is OFF).
A neutral conductor break between this monitoring module
and the monitored system cannot be detected.
103233_en_01