Bel DCPDU Dc power distribution unit Datasheet

Bel Power Solutions DC Power Distribution Unit (PDU) is used to
distribute DC auxiliary power and monitoring signals in Open Racks.
This device is installed in an IT chassis and works in conjunction with
the OCP V2 Open Rack.
The DC supply voltage is distributed from the V2 Power Shelves and it
is used to supply the switches and a rack-monitoring device.
The monitoring signals are distributed from the V2 Power Shelves to
the rack-monitoring device.
•
Designed for V2 Power shelf
•
Input voltage range: 40 – 72 VDC , max 15 A (x2)
•
2x Power DC inputs
•
4x Power DC outputs
•
Different output power connector for higher flexibility
•
Interconnections for monitoring and communication signals to rack
monitor trough RJ45 connectors
•
Full compatibility with Open Compute project specification
•
Robust mechanical design
•
UL approved Link to OCP specification:
http://www.opencompute.org/wiki/Open_Rack/SpecsAndDesigns
DC PDU
2
DC PDU
YSD.00134
A maximum of 600 W total is allocated to power the switches and a rack-monitoring device. Each Power Shelf is capable of
providing the 600 W by itself, or, if two shelves are present in the rack, each will supply 300 W. Each of the 2 DC inputs from the
shelves is connected in the PDU to 2 separate outputs implemented with different connectors (Molex and Anderson Power). The
picture below shows the power electrical connections in the PDU.
Figure 1: Electrical Schematic
The PDU collects the monitoring and communication signals from the Power Shelves and distributes them to the Rack-Monitoring
device. The signal connectors are standard RJ45. The picture below shows the electrical connections of the monitoring and
communication signals in the PDU.
NOTE: The colors in the following figure are not standard.
Figure 2. Communication Wiring
[email protected]
DC PDU
3
The table below shows a summary of the PDU input electrical characteristics and interfaces:
Nominal DC Input Voltage
54
Input Voltage Range
VDC
40
Input Current
72
15
Input Power Connectors
2x Molex Sabre
Rack Monitor Input
2x RJ45 input connectors connected from each power shelf
VDC
A
2.1 INPUT POWER CONNECTIONS
2x Input connectors - female Molex Saber 7.50 mm receptacle housing with a latch (44441-2003) with the Molex Sabre
crimp female terminal (43375-0001).
PIN
DESCRIPTION
1
+54 VDC (red)
2
RTN (black)
3
GND (green)
Figure 3. Molex 44441-2003
The table below shows a summary of the PDU output electrical characteristics and interfaces:
2 pcs
Output Connectors
2 pcs connected via right angle connectors on the PCB
Output Voltage Range
40
Output Current
72
15
Communication Connector
RJ45
LED Indicator
2 pcs to indicate that a valid 54 VDC nominal voltage is
present (40 to 72 VDC).
VDC
A
Europe, Middle East
+353 61 225 977
North America
+1 408 785 5200
© 2018 Bel Power Solutions & Protection
BCD.00765_003
Asia-Pacific
+86 755 298 85888
DC PDU
4
3.1 OUTPUT POWER CONNECTIONS
The PDU implements 2 +2 output Power connectors implemented with 2 different connectors types.
Below the implemented PNs from Molex and APP are shown.
Figure 4. DC Output Connectors
Agency Approvals
High-Pot Test
UL 60950-1
CE Mark
RoHS Compliant
DC input side (+54 VDC and return) to the earth
ground chassis (GND)
750
Operating
Altitude
Non-Operating (without derating)
VDC
3000
10000
15000
49000
m
ft
m
ft
Operating Ambient Temperature
-5
+45
°C
Storage Temperature
-40
+70
°C
-55
+85
°C
10
5
90
95
%
5
140
g
0.25
0.75
g
Transportation Temperature
Relative Humidity
Shock
Sinusoidal Vibration
short term storage, 72 hours
Operating: Non-condescending
Non-operating: 38.7°C maximum wet bulb
temperature with no cosmetic damage
Operating : 11 ms, 3 half-sine wave shocks, 3 axes
Non-Operating: 2 ms, 6 half-sine wave shocks, 3
axes
Operating: zero to peak, 10 to 500 Hz, 0.25 oct/min
Non-Operating : zero-to-peak, 10 to 500 Hz, 0.5
oct/min
[email protected]
DC PDU
Dimensions (W x H x D)
5
248 x 45 x 121 mm
Figure 5. Dimension Drawing DC PDU (Top View)
Europe, Middle East
+353 61 225 977
North America
+1 408 785 5200
© 2018 Bel Power Solutions & Protection
BCD.00765_003
Asia-Pacific
+86 755 298 85888
DC PDU
6
Figure 6. Dimension Drawing DC PDU (Side View)
Figure 7. Dimension Drawing DC PDU (Side View)
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support
systems, equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject to change without notice.
[email protected]
Similar pages