XP Power DNR120-960TS Three phase ac input Datasheet

ACDC
120960 Watts
DNR120960TS Series
xppower.com
•
Three Phase AC Input
•
Up to 93% Efficiency
•
Wide Adjustment Range
•
Full Power 40 º C to +60 º C
•
Rugged Design for Industrial Applications
•
Single Phase Input Operation (340575 VAC)
•
3 Year Warranty
Specification
Input
General
• 340-575 VAC 3 phase (single phase
operation with 75% of rated output),
480-820 VDC
Input Frequency
• 47-63 Hz
Input Current
• See tables
Inrush Current
• DNR120: 10.0 A, DNR240: 20.0 A,
DNR480: 20.0 A, DNR960: 30.0 A,
typical at 480 VAC, cold start
Power Factor
• 0.6 typical at 480 VAC input and nominal
load, DNR960TS: 0.8 typical at 480 VAC
input and nominal load
Earth Leakage Current • 0.32 mA
Input Protection
• 3 internal fuses,
DNR120TS, DNR240TS: T2.0 A, 600 VAC,
DNR480TS: T3.15 A, 500 VAC,
DNR960TS: T5.0 A, 500 VAC
Input Voltage
Output
Output Voltage
Output Voltage Trim
Initial Set Accuracy
Minimum Load
Start Up Delay
•
•
•
•
•
Start Up Rise Time
Hold Up Time
•
•
Line Regulation
Load Regulation
•
•
Parallel Operation
•
Transient Response
•
Ripple & Noise
•
Overvoltage Protection •
Overload Protection
•
Temperature Coefficient •
Short Circuit Protection •
See table
See table
±1%
No minimum load required
<1 s (may increase at low
temperature extremes)
<150 ms
20 ms min at 480 VAC,
DNR960TS: 15 ms min at 480 VAC
±1%
±1% max (±5% for units in parallel (not
DNR120TS))
2 units can be connected in parallel
(not DNR120TS), total power available is
90% of the rated current of each unit,
minimum load per unit 10%, use Ishare
connection for DNR960TS. Redundancy
module DPM10 available for load currents
up to 10 A, contact sales
4% max deviation recovering to within
1% in 2 ms for 50% load change
100 mV pk-pk 20 MHz bandwidth,
DNR960TS: 80 mV pk-pk 20 MHz
bandwidth, (may increase at low
temperature extremes)
120-145%, auto recovery
110%-140%, constant current,
auto recovery
±0.03%/°C
Continuous trip and restart (hiccup mode)
(DNR480TS switchable hiccup mode or
power limited )
Efficiency
Isolation
Switching Frequency
Signals
MTBF
DIN Rail
• See table
• 3000 VAC Input to Output, 1500 VAC
Input to Ground, 500 VAC Output to
Ground
• DNR120TS: 70 kHz typical,
DNR240TS: 25 kHz typical,
DNR480TS: 80 kHz typical,
DNR960TS: 52 kHz typical
• DC ON indicator LED Green,
DC LOW indicator LED Red
DC OK: normally open relay on 24 V models
• DNR120TS: 550 kHrs, 240TS: 500 kHrs
480TS: 420 kHrs, 960TS: 380 kHrs to
Bellcore Issue 6, at +40 °C, GB
• Compatible with TS35/7.5 or TS35/15
Environmental
Operating Temperature • -40 °C to 70 °C (DNR480TS -30 °C),
derate linearly from 60 °C at 2.5%/°C
(3.5%/°C for DNR960TS), start up at
-35 °C (DNR480TS -20 °C)
see derating curves
Cooling
• Convection-cooled with 25 mm free space
all sides
Operating Humidity
• 20-95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Shock
• 15 g, 11 ms, 3 axis, 6 faces, 3 shocks/face
Vibration
• 2 g, 10 Hz to 500 Hz, along X, Y & Z axis,
60 min/axis, mounted on rail
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
•
•
•
•
•
•
•
Conducted Immunity
Magnetic Field
Dips & Interruptions
•
•
•
Safety Approvals
•
EN55022, Class B conducted & radiated
EN61000-3-2, Class A
EN61000-3-3
EN61000-4-2, level 4 Perf Criteria A
EN61000-4-3, level 3 Perf Criteria A
EN61000-4-4, level 4 Perf Criteria A
EN61000-4-5, installation class 4,
Perf Criteria A
EN61000-4-6, level 3 perf criteria A
EN61000-4-8, level 4 perf criteria A
EN61000-4-11, 30% 500 ms,
60% 200 ms, >95% 5000 ms
Perf Criteria A, A, A
EN60950-1 UL508 UL60950-1
Pollution Degree 2,
UL60950-1 Overvoltage Category II
UL508 Overvoltage Category III,
ANSI/ISA 12.12.01 Class 1, Division 2,
Groups A,B,C and D
Output Voltage
12
24
24
48
24
48
24
48
V
V
V
V
V
V
V
V
Input Current (typ.)
400 VAC
500 VAC
0.36 A
0.30 A
0.36 A
0.30 A
0.65 A
0.55 A
0.65 A
0.55 A
1.10 A
0.93 A
1.10 A
0.93 A
1.72 A
1.50 A
1.72 A
1.50 A
Output Voltage
Trim
11.4-14.5
22.5-28.5
22.5-28.5
47.0-56.0
22.5-28.5
47.0-56.0
22.5-28.5
47.0-56.0
Output Current(1)
V
V
V
V
V
V
V
V
10.0
5.0
10.0
5.0
20.0
10.0
40.0
20.0
Efficiency (typ.)
Model Number
87%
89%
90%
91%
90%
91%
92%
93%
DNR120TS12
DNR120TS24
DNR240TS24-I
DNR240TS48-I
DNR480TS24-I
DNR480TS48-I
DNR960TS24-I
DNR960TS48-I
A
A
A
A
A
A
A
A
ACDC
DNR120960TS
Models and Ratings
Notes
1. Reduce by 25% for single phase input operation, (340-575 VAC).
V
Mechanical Details
5.91 (150.0)
DC Output
4.39 (111.3)
Voltage Trim
6
0.3
(7.0)
1
DC DC + + - OK OK
DC LO
ON
DNR120TS
DNR240TS
4.87
(123.6)
DC LO
ON
All Units
Voltage Trim
L2
L3
1
L1
4
L2
L3
1
L1
+ + - -
5
1 6
4 4
AC Input
AC Input
2.93 (74.3)
DC Output
AC Input
Parallel
Single
L1
4.87
(123.6)
DNR480TS
4.87
Voltage (123.6)
Trim
L2
L3
1
DC Output
DC OK
4
5
DC DC
LO ON
6
+V +V-V -V
4
1
Voltage Adj.
Single/parallel & current limit
selector switches on underside
3.50 (89.0)
DC OK signal connector
on underside, Spring type,
AWG26-20/0.2-0.5 mm2
10.86 (275.7)
Pin
4.96
(125.9)
DNR960TS
DC Output
+V +V -V -V
AC Input
L1
1
L
L2
L3
DC DC
LO ON
4
DC DC
OK OK +Is -Is
1
8
Pin Connections - AC Input
Pin
Designation
1
Ground
2
L1
3
L2
4
L3
1
2
3
4
5
6
7
8
Pin Connections - DC Output
DNR120 DNR240-480 DNR960TS
Designation Designation Designation
-V
-V
DC OK*
-V
-V
DC OK*
+V
+V
+Ishare(8)
+V
+V
-Ishare(8)
DC OK*
DC OK*
+V
DC OK*
DC OK*
+V
-V
-V
* Available on 24 V versions only
Voltage trim on underside
Notes
1. All dimensions in inches (mm).
2. Tolerance: ±0.02 (0.5) maximum.
3. Weight - DNR120TS: 1.76 lb (800 g) approx.
DNR240TS: 2.43 lb (1100 g) approx.
DNR480TS: 4.23 lb (1720 g) approx.
DNR960TS: 7.05 lb (3200 g) approx.
4. Screw terminal: 10-24 AWG cable size.
5. DC OK Relay rated at 60 VDC at 300 mA.
6. Allow 0.98” (25 mm) clearance all round to ensure adequate ventilation.
7. Connection screw maximum torque: Input: 9 lbs-in (1.0 Nm),
Output: 5.5 lbs-in (0.6 Nm).
8. Connecting +Ishare and -Ishare between two power supplies will force the units
to current share.
Derating Curves
100
Load (%)
A
75
65
C
B
A DNR120-240TS
B DNR960TS
C DNR480TS
0
-40
-30
Ambient Temp (˚C)
60
70
11-May-11
Similar pages