www.murata-ps.com D1U3CS-W-1200-12-HxxC Series 81mm 1U Front End AC-DC Power Supply Converter PRODUCT OVERVIEW The D1U3CS-W-1200-12-HxxC series are 80 PLUS Gold efficiency 1200 watt, power factor corrected front end supplies with a 12V main output and a 5V or 3.3V (20W) standby. They have active current sharing and up to 8 supplies may be operated in parallel. The supplies may be hot plugged, they recover from overtemperature faults, and have status LEDs on their front panel in addition to logic and PMBus™ status signals. Their low profile 1U package and >21W/cubic inch power density make them ideal for delivering reliable, efficient power to servers, workstations, storage systems and other 12V distributed power systems. ORDERING GUIDE Part Number FEATURES 1200W output power 80 PLUS® Gold efficiency 12V main output 3.3V or 5V standby output of 20W 1U height: 3.20" x 11.00" x 1.57" 21.7 Watts per cubic inch density N+1 redundancy capable, including hot plugging (up to 8 in parallel) Active current sharing on 12V main output; ORing FET Overvoltage, overcurrent, overtemperature protection Internal cooling fan (variable speed) Power Output High Line AC Power Output Low Line AC Main Output Standby Output Airflow 1200W 1200W 1200W 1200W 1000W 1000W 1000W 1000W 12V 12V 12V 12V 3.3V 5V 3.3V 5V Back to front Back to front Front to back Front to back Min. Nom. Max. Units 90 47 81 70.5 115/230 50/60 85 74.3 264 63 89 78 8 15 25 Vac Hz D1U3CS-W-1200-12-HC4C D1U3CS-W-1200-12-HA4C D1U3CS-W-1200-12-HC3C D1U3CS-W-1200-12-HA3C INPUT CHARACTERISTICS Parameter Conditions Voltage Operating Range Frequency Turn-on Voltage Turn-off Voltage Maximum Current at Vin=200Vac Maximum current at Vin=90Vac Inrush Current Power Factor PMBus™ I²C interface with status indicators Ramp up Ramp down 1200W 1000W Cold start between 0 to 200msec At 230Vac, full load 20% load Efficiency (230Vac) excluding fan load 50% load 100% load RoHS compliant OUTPUT VOLTAGE CHARACTERISTICS Output Parameter Voltage 12V 3.3VSB www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html www.murata-ps.com/en/3d/acdc.html 5VSB Voltage Set Point Accuracy Line and Load Regulation Ripple Voltage & Noise1 Output Current (230Vac) Output Current (120Vac) Load Capacitance Voltage Set Point Accuracy Line and Load Regulation Ripple Voltage & Noise1 Output Current Load Capacitance Voltage Set Point Accuracy Line and Load Regulation Ripple Voltage & Noise1 Output Current Load Capacitance Conditions Vac Arms Apk 0.99 88 92 92 Min. % Typ. Max. 12.0 11.4 12.6 120 98.3 81.7 30000 20MHz Bandwidth 0 0 3.3 3.2 20MHz Bandwidth 0 20MHz Bandwidth 0 Vdc mV p-p A μF Vdc 3.4 100 6 10000 mV p-p A μF 5.15 50 4 10000 mV p-p A μF 5.0 4.85 Units Vdc 1 Ripple and noise are measured with 0.1 uF of ceramic capacitance and 10 uF of tantalum capacitance on each of the power supply outputs. A short coaxial cable with 50ohm scope termination is used. Available now at www.murata-ps.com/en/3d/acdc.html CB For full details go to www.murata-ps.com/rohs Test Certificate and Test Report www.murata-ps.com/support D1U3CS-W-1200-12-HxxC.A03 Page 1 of 6 D1U3CS-W-1200-12-HxxC Series 81mm 1U Front End AC-DC Power Supply Converter OUTPUT CHARACTERISTICS Parameter Conditions Output Rise Monotonicity Startup Time No voltage excursion AC ramp up 12V, 50-100% load step, 1A/μs di/dt 5VSB, 50-100% load step, 1A/μs di/dt 3.3VSB, 50-100% load step, 1A/μs di/dt Transient Response Current sharing accuracy (up to 8 in parallel) At 100% load Hot Swap Transients Holdup Time All outputs remain in regulation At full load Min. Typ. Max. Units 1.5 2.5 300 250 165 s mV ±7 % 5 % ms 12 ENVIRONMENTAL CHARACTERISTICS Parameter Conditions Storage Temperature Range Operating Temperature Range Operating Humidity Storage Humidity Altitude (without derating at 40°C) Altitude (without derating at 55°C) Shock Sinusoidal Vibration MTBF Acoustic Safety Approvals Input Fuse Material Flammability Switching Frequency Weight Noncondensing 30G non operating 0.5G, 5 – 500 Hz Per Telcordia SR-322 M1C1 @40°C Min. Typ. -40 -10 5 5 4000 1800 Max. Units 70 50 90 95 °C % m 500K 55 hrs dB LpAm CSA/UL 60950-1-07-2nd Ed. IEC 60950-1:2005 (2nd Edition) w Am. 1:2009 EN 60950-1:2006 +A11:2009 +A1:2010 CE Marking per LVD DIRECTIVE 2006/95/EC Power Supply has internal 15A/250V fast blow fuse on the AC line input UL 94V-0 90KHz for Boost PFC Converter 130KHz for Main Output Converter 3.15lbs (1.43kg) PROTECTION CHARACTERISTICS Output Voltage 12V 3.3VSB 5VSB Parameter Conditions Min. Typ. Max. Units Overtemperature (intake) Overvoltage Overcurrent at 220Vac Overcurrent at 110Vac Overvoltage Overcurrent Overvoltage Overcurrent Autorestart Latching Latching Latching Latching Autorecovery Latching Autorecovery 57 13.3 108 90 3.9 6.5 5.6 4.4 60 63 14.5 147 102 4.3 9.0 6.0 6.0 °C V Min. Typ. Max. Units A V A V A ISOLATION CHARACTERISTICS Parameter Insulation Safety Rating / Test Voltage Isolation Conditions Input to Output - Reinforced Input to Chassis - Basic Output to Chassis 3000 1500 500 Vrms Vrms Vdc www.murata-ps.com/support D1U3CS-W-1200-12-HxxC.A03 Page 2 of 6 D1U3CS-W-1200-12-HxxC Series 81mm 1U Front End AC-DC Power Supply Converter STATUS INDICATORS Condition LED Status Standby - ON; Main output - OFF; AC PRESENT Standby - ON; Main output - ON Main output overcurrent, undervoltage, overvoltage FAN_FAULT; overtemperature; standby overcurrent, standby undervoltage Blinking green Solid green Blinking red Red EMISSIONS AND IMMUNITY Characteristic Standard Compliance Input Current Harmonics Voltage Fluctuation and Flicker Conducted Emissions ESD Immunity Radiated Field Immunity Electrical Fast Transients/Burst Immunity Surge Immunity RF Conducted Immunity Magnetic Field Immunity IEC/EN 61000-3-2 IEC/EN 61000-3-3 FCC 47 CFR Part 15/CISPR 22/EN55022 IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 IEC/EN 61000-4-8 Voltage dips, interruptions IEC/EN 61000-4-11 Complies Complies Class A, 6dB margin Level 3 criteria A Level 3 criteria B Level 3 criteria B Level 3 criteria A Level 3 criteria A 3 A/m criteria B 230Vin, 100% load, Phase 0°, Dip 100% Duration 10ms (A) 230Vin, 50% load, Phase 0°, Dip 100% Duration 20ms (VSB:A, V1:A) 230Vin, 100% load, Phase 0°, Dip 100% Duration > 20ms (VSB, V1:B) www.murata-ps.com/support D1U3CS-W-1200-12-HxxC.A03 Page 3 of 6 D1U3CS-W-1200-12-HxxC Series 81mm 1U Front End AC-DC Power Supply Converter OUTPUT CONNECTOR AND SIGNAL SPECIFICATION DC and Signal Connector: FCI 51731-057LF D1 D2 D3 D4 D5 D6 C1 C2 C3 C4 C5 C6 B1 B2 B3 B4 B5 B6 A1 A2 A3 A4 A5 A6 PB1 PB2 PB3 PB4 Description PB5 PB6 Pin Assignment Signal Name Amps per pin PB1, PB2, PB3 PB4, PB5, PB6 +12V GND +12V OUT Main output voltage return Main output voltage 30 30 A1 PS_ON_L Input. Internal 10K ohm pull-up (accepts open collector/drain drive). This signal to be pulled low to turn-on power supply. N/A A2 +12VRS_RETURN Main output remote sense return N/A N/A A3 TEMP_OK A TTL logic HIGH when operating temperature within allowable range A4 PS_SEATED Power supply is plugged into the system. Internally tied to ground. N/A A5, B5, C5, D5 A6, B6, C6, D6 B1 B2 B3 +VSB +VSB GND AC OK +12VRS +12V_ISHARE Standby output voltage Standby output voltage return Input AC voltage “OK” signal output Main output remote sense Main output active load sharing bus 2.0 2.0 N/A N/A N/A B4 PS_INHIBIT/PS_KILL This signal is connected to a short pin on the PSU. When left open operation will be inhibited. When the PSU is inserted into the system, this pin must be pulled low by the system and will turn on the PSU only after all inputs have seated. N/A C1 C2 SDA SCL I2C Data line I2C Clock line N/A N/A C3 PWR_GD Power good. Active TTL HIGH when output is within regulation limits N/A C4 D1 D2 D3 D4 FAN_FAIL A0 A1 S_INT VSB RS Fan failure Address line least significant bit Address line most significant bit System interrupt Standby output remote sense N/A N/A N/A N/A N/A MATING CONNECTORS Press Fit Mating Connector FCI Straight TBD Right Angle 51761-10002406AA www.murata-ps.com/support D1U3CS-W-1200-12-HxxC.A03 Page 4 of 6 D1U3CS-W-1200-12-HxxC Series 81mm 1U Front End AC-DC Power Supply Converter WIRING DIAGRAM FOR OUTPUT Dotted lines show optional remote sense connections. Optional remote sense lines can be attached to a load that is a distance away from the power supply to improve regulation at the load. +12VRS (Main Output Remote Sense) B2 PB4-6 +12VRS (Main Output Remote Sense) +12V OUT +12V OUT PB4-6 B2 12V load D1U3CS PB1-3 A2 B3 A5,B5,C5,D5 A1 A6,B6,C6,D6 B4 D1U3CS +12V GND +12V GND +12VRS_RETURN +12V_ISHARE A2 +12V_ISHARE B3 PS_ON_L PS_ON_L +VSB GND +12VRS_RETURN +VSB +VSB PB1-3 A5,B5,C5,D5 A1 +VSB load FET, BJT, wire or switch (debounced ) to turn on +12V main output +VSB GND A6,B6,C6,D6 PS_INHIBIT/PS_KILL PS_INHIBIT/PS_KILL B4 CURRENT SHARING NOTES 12V Output: Current sharing is achieved using the active current share method. (See wiring diagram for connection details.) Current sharing can be achieved with or without remote sense connected to the common load. +VSB outputs can be tied together for redundancy but total combined output power must not exceed 20W. The +VSB output has internal ORing MOSFET for additional redundancy / internal short protection. The current share pin B3 is a connection between the two units. It is input and/or output as the voltage on the line controls the current share. A power supply will respond to a change in this voltage but a power supply can also change the voltage depending on the load drawn from it. On a single unit this would read 8V at 100% load. For two units sharing load then this should read 4V for perfect current sharing. Up to 8 units can be paralleled together. Please consult your Murata sales representative if operation with more than 8 units in parallel is needed. www.murata-ps.com/support D1U3CS-W-1200-12-HxxC.A03 Page 5 of 6 D1U3CS-W-1200-12-HxxC Series 81mm 1U Front End AC-DC Power Supply Converter 16.50 0.650 MECHANICAL DIMENSIONS 75.00 2.953 Airflow Back to Front 7.04 ±0.80 0.277 ±0.031 39.90 ±0.50 1.571 ±0.020 75.00 2.953 19.50 0.768 83.80 ±0.70 3.299 ±0.028 7.0 0.276 275.50 ±0.70 10.846 ±0.028 279.40 ±0.50 11.000 ±0.020 22.80 ±0.60 0.898 ±0.024 16.20 ±0.60 0.638 ±0.024 75.00 2.953 Power Supply BACK 17.65 0.695 40.65 1.600 63.65 2.506 Power Supply FRONT 81.30 ±0.50 3.201 ±0.020 Airflow Front to Back 15.51 ±0.80 0.611 ±0.031 75.00 2.953 AC input connector: IEC 320-C14 Dimensions: 3.20" x 11.00" x 1.571" [81.3mm x 279.4mm x 39.9mm] OPTIONAL ACCESSORIES Description Part Number 12V D1U3CS Output Connector Card D1U3CS-12-CONC APPLICATION NOTES Document Number Description Link ACAN-41 D1U3CS Output Connector Card www.murata-ps.com/data/apnotes/acan-41.pdf ACAN-43 D1U3CS-x Communication Protocol www.murata-ps.com/data/apnotes/acan-43.pdf Murata Power Solutions, Inc. 11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A. ISO 9001 and 14001 REGISTERED This product is subject to the following operating requirements and the Life and Safety Critical Application Sales Policy: Refer to: http://www.murata-ps.com/requirements/ Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without notice. © 2013 Murata Power Solutions, Inc. www.murata-ps.com/support D1U3CS-W-1200-12-HxxC.A03 Page 6 of 6