Omron E5CC-U Digital temperature controller Datasheet

New Product
Digital Temperature Controller
E5@C/E5@C-T
Large White PV Display That's Easier to Read.
Easy to Use, from Model Selection to Setup and Operation.
New Plug-in Models That Are Convenient for Maintenance and Replacement
as replacing temperature controllers is possible without changing wiring.
New Models That Mount to DIN Track and Are Ideal for HMI/PLC Connections.
And Programmable Models to Support a Wider Range of Applications.
E5GC
DIN 48 × 24 mm
E5CC
E5CC-U
DIN 48 × 48 mm
page 2
page 16
Digital Temperature Controller
E5@C
Series
E5EC
E5AC
E5DC
Programmable
Temperature Controller
(Digital Controller)
E5@C-T
Series
E5CC-T
E5EC-T
E5AC-T
DIN 48 × 96 mm
page 34
DIN 96 × 96 mm
page 34
22.5 mm wide
Mounts to DIN
Track page 50
DIN 48 × 48 mm
page 64
DIN 48 × 96 mm
page 80
DIN 96 × 96 mm
page 80
1
Digital Temperature Controller
E5GC
(48 × 24 mm)
Easy Operation and High Performance of
the E5@C Series in a Compact 48 × 24mm Body
• A compact body of 48 × 24 × 90 mm (W × H × D) that is ideal for
small equipment, laboratory instruments, and others.
• White PV display with a height of 10.5 mm for high visibility even
with the compact body.
• Removable terminal block to simplify maintenance. Select from
screw terminals or screwless clamp terminals for the wiring
method.
• High-speed sampling at 50 ms.
• Easy connections to a PLC with programless communications.
• Set up the Controller without wiring the power supply by
connecting to the computer with a Communications Conversion
Cable (sold separately). Setup is easy with the CX-Thermo (sold
separately).
48 × 24 mm
Models with Screw
Terminal Blocks
E5GC-@6
48 × 24 mm
Models with Screwless
Clamp Terminal Blocks
E5GC-@C
Refer to your OMRON website for the most recent
information on applicable safety standards.
Refer to Safety Precautions on page 104.
Main I/O Functions
Sensor Input
Universal input
• Thermocouple
• Pt
• Analog current/voltage
E5GC
Dual displays: PV/SV
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Linear current output
Indication Accuracy
• Thermocouple input:
±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% of FS
Sampling Period
• 50 ms
Event Inputs
• None
•1
•2
Serial Communications
• None
• RS-485
4-digit displays
• PF (shift) Key
• Temperature status display
• Simple programming
• Independent heating and
cooling PID control
• Changed parameter display
• Display brightness setting
• Simple transfer output (only on
models with liner current outputs)
• Work Bit Message
Auxiliary Outputs
• None
•1
•2
This datasheet is provided as a guideline for selecting products.
Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
2
E5GC
Model Number Legend and Standard Models
Model Number Legend
E5GC-@@ @ @ @ M-@@@ (Example: E5GC-RX1A6M-015)
−− − − − − −−−
A
B C D E
F
Model
A
B
Control
No. of
outputs 1 auxiliary
and 2
outputs
C
Power
supply
voltage
D
E
F
Terminal
type
Input
type
Options
Meaning
48 × 24 mm
E5GC
Control output 1
Relay output
Voltage output
(for driving SSR)
Linear current output
RX
QX
*1 CX
*2 0
1
2
A
D
6
C
M
*3
*3, *4
*5
*1
*2
*3
*4
*5
000
015
016
023
024
Control output 2
None
None
None
None
1
2
100 to 240 VAC
24 VAC/DC
Screw terminals (with cover)
Screwless clamp terminals
Universal input
HB alarm and HS alarm
Communications Event inputs
--------RS-485
------1
1
--------2
The control output can be used as a simple transfer output.
Only option 000 can be selected if an auxiliary output is zero.
Option 016 and 023 can be selected only if two auxiliary outputs are selected.
Option with HB and HS alarms (023) cannot be selected if a linear current output is selected for the control output.
Option 024 can be selected only if one auxiliary output is selected.
Heating and Cooling Control
●Using Heating and Cooling Control
A Control Output Assignment
An auxiliary output is used as the cooling control output.
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
3
E5GC
Optional Products (Order Separately)
USB-Serial Conversion Cable
Model
E58-CIFQ2
Model
Y92S-P12
Communications Conversion Cable
Model
E58-CIFQ2-E
Current Transformers (CTs)
Model
E54-CT1
E54-CT3
Mounting Adapter
Model
Y92F-53 (2pcs)
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
4
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.
Draw-out Jig
Note: Always use this product together with the E58-CIFQ2.
This Cable is used to connect to the bottom-panel Setup Tool
port.
Hole diameter
5.8 mm
12.0 mm
Waterproof Packing
Model
Y92F-55
CX-Thermo Support Software
Model
EST2-2C-MV4
Note: CX-Thermo version 4.62 or higher is required for the E5GC.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
E5GC
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Control
output
Auxiliary
output
Voltage output
(for driving SSR)
Linear current output
Number of outputs
Output specifications
Number of inputs
Event
input
External contact input
specifications
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/
THB.)
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5
V, 10 mA (reference value)
Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000
1 or 2 (depends on model)
SPST-NO relay outputs, 250 VAC, 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
1 or 2 (depends on model)
Contact input ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
Current flow: approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital displays and individual indicators
Character height: PV: 10.5 mm, SV: 5.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
serial communications.*
None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self
tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change
rate limit, logic operations, temperature status display, simple programming, moving average of input value, display brightness setting, simple transfer output, and work bit message
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with
no condensation or icing)
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* Only four set points are selectable for event inputs.
5
E5GC
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor
type
Platinum resistance
thermometer
Sensor
specification
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to
70°C
60 to
120°C
115 to
165°C
120
165
140 to
260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600
1500
1400
1300
1300
1300
1300
1200
1100
1000
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
Set value
90
100
0.0
-100
-200
100.0
-200 -199.9
0
1
0.0
-199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100
-200 -199.9 -200
9
10
11
-200 -199.9 -200
12
13
14
15
18
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input
Input type
Input specification
Setting range
Set value
6
Current
Voltage
4 to 20 mA 0 to 20 mA 1 to 5 V
0 to 5 V
Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
25
26
27
28
0 to 10 V
29
E5GC
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)
Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not
displayed.
To use alarm 1, set the output assignment to alarm 1.
Set
value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2
Upper-limit
(default)
3
Lower-limit
4
Upper- and lower-limit
range *1
5
6
7
8
9
10
11
Alarm output operation
Description of function
When alarm value X When alarm value X
is positive
is negative
Output OFF
No alarm
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*2
OFF
PV
lower limit (L). The alarm is ON when the PV is outside this
SP
deviation range.
Set
the upward deviation in the set point by setting the alarm
X
X
ON
ON
value (X). The alarm is ON when the PV is higher than the
OFF
PV
OFF
PV
SP
SP
SP by the deviation or more.
Set the downward deviation in the set point by setting the
X
X
ON
ON
alarm value (X). The alarm is ON when the PV is lower than
OFF
PV
OFF
PV
SP
SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*3
OFF
PV
lower limit (L). The alarm is ON when the PV is inside this deSP
viation range.
Upper- and lower-limit
with standby sequence *1 *5
Upper-limit with standby
sequence
Lower-limit with standby
sequence
ON
OFF
Absolute-value upper-limit
ON
OFF
Absolute-value lower-limit
ON
OFF
Absolute-value upper-limit with standby sequence
ON
OFF
Absolute-value lower-limit
with standby sequence
ON
OFF
LBA (alarm 1 type only)
PV change rate alarm
14
SP absolute-value
upper-limit alarm
ON
OFF
SP absolute-value
lower-limit alarm
ON
OFF
X
SP
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
X
SP
X
0
X
0
X
0
X
0
X
0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X
SP
X
0
PV
X
0
PV
X
0
PV
X
0
PV
ON
OFF
SP
ON
OFF
X
0
The alarm will turn ON if the process value is smaller than the
alarm value (X) regardless of the set point.
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X
0
SP
X
0
SP
This alarm type turns ON the alarm when the set point (SP)
is higher than the alarm value (X).
This alarm type turns ON the alarm when the set point (SP)
is lower than the alarm value (X).
Standard Control
X
MV
0
The alarm will turn ON if the process value is larger than the
alarm value (X) regardless of the set point.
*7
*8
SP
ON
OFF
X
0
MV
X
MV
0
Standard Control
ON
OFF
17
SP
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
ON
OFF
MV absolute-value
lower-limit alarm *9
X
-
ON
OFF
MV absolute-value
upper-limit alarm *9
*4
PV
Standard Control
16
A standby sequence is added to the upper- and lower-limit
alarm (1). *6
H
SP
ON
OFF
12
13
15
L
ON
OFF
Standard Control
X
MV
0
Always ON
ON
OFF
X
0
MV
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
ON
OFF
X
0
MV
Always ON
7
E5GC
*1 With set values 1, 4, and 5, the upper- and lower-limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
*2 Set value: 1, Upper- and lower-limit alarm
Case 3 (Always OFF)
Case 2
Case 1
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
H
SP L H
H>0, L<0
|H| > |L|
H
SP
L
H<0, L>0
|H| ≥ |L|
L SP
SP H
L
H>0, L<0
|H| ≤ |L|
*3 Set value: 4, Upper- and lower-limit range
Case 3 (Always ON)
Case 2
Case 1
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
SP L
H
H
H>0, L<0
|H| > |L|
H
SP
L
L SP
SP H L
8
H<0, L>0
|H| ≥ |L|
H>0, L<0
|H| ≤ |L|
*4 Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above at *2
• In cases 1 and 2 above, the alarm is always OFF if the upperand lower-limit hysteresis overlaps.
• In case 3, the alarm is always OFF.
*5 Set value: 5, Upper- and lower-limit alarm with standby sequence
The alarm is always OFF if upper- and lower-limit hysteresis
overlaps.
*6 Refer to the E5@C Digital Temperature Controllers User’s Manual
(Cat. No. H174) for information on the operation of the standby
sequence.
*7 Refer to the E5@C Digital Temperature Controllers User’s Manual
(Cat. No. H174) for information on the LBA.
*8 Refer to the E5@C Digital Temperature Controllers User’s Manual
(Cat. No. H174) for information on the PV change rate alarm.
*9 When heating/cooling control is performed, the MV absolutevalue upper-limit alarm functions only for the heating operation
and the MV absolute-value lower-limit alarm functions only for the
cooling operation.
E5GC
Characteristics
Indication accuracy
(at the temperature of 23°C)
Influence of temperature *2
Influence of voltage *2
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Proportional band (P) for cooling
Integral time (I) for cooling
Derivative time (D) for cooling
Control period
Manual reset value
Alarm setting range
Influence of signal source resistance
Insulation resistance
Thermocouple:
(±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max.*1
Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
CT input:
±5% FS ±1 digit max.
Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
−1,999 to 9,999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ω max.), Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC)
100 to 240 VAC: 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Dielectric strength
24 VAC/DC: 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions
Vibration
Resistance
10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions
Malfunction
100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance
300 m/s2, 3 times each in X, Y, and Z directions
Weight
Controller: Approx. 80 g, Adapter: Approx. 4 g × 2
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.62 or higher
E5GC side panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the computer. *5
Setup Tool port
E5GC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable
are used together to connect a USB port on the computer.*5
Approved standards
UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2 , overvoltage category II
EMI:
EN61326
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage:
EN55011 Group 1, class A
EMS:
EN61326
ESD Immunity:
EN61000-4-2
EMC
Electromagnetic Field Immunity:
EN61000-4-3
Burst Noise Immunity:
EN61000-4-4
Conducted Disturbance Immunity:
EN61000-4-6
Surge Immunity:
EN61000-4-5
Voltage Dip/Interrupting Immunity:
EN61000-4-11
*1 The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C max., and U
and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B thermocouples at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max.
The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W
thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*3 K thermocouple at −100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
9
E5GC
USB-Serial Conversion Cable
Applicable OS
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.62 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
Component
Communications
When Digital Temperature Controllers are connected, set
points and RUN/STOP commands can be sent from the Digital Temperature Controller that is set as the master to the
Digital Temperature Controllers that are set as slaves.
Slope and offsets can be set for the set point.
Number of connected Digital Temperature Controllers: 32
max. (including master)
Copying*
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature
Controllers that are set as slaves.
USB interface standard Conforms to USB Specification 2.0
DTE speed
38,400 bps
Connector
specifications
Computer: USB (Type A plug)
Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from the USB host controller) *
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
KEYENCE is a registered trademark of Keyence Corporation.
Power supply voltage
5 VDC
*
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Ambient operating
temperature
0 to 55°C (with no condensation or icing)
Ambient operating
humidity
10% to 80%
Storage temperature
−20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
*
Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation
procedure.
Communications Specifications
Transmission line connection
method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9,600, 19,200, 38,400, or 57,600 bps
Transmission code
ASCII
Data bit length *
7 or 8 bits
Stop bit length *
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC)
with CompoWay/F or
CRC-16 with Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer
217 bytes
Communications response
wait time
0 to 99 ms
Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Communications Functions
Programless
communications
10
You can use the memory in the PLC to read and write E5@C
parameters, start and stop operation, etc.
The E5@C automatically performs communications with
PLCs. No communications programming is required.
Number of connected Digital Temperature Controllers: 32
max. (Up to 16 for the FX Series)
Applicable PLCs: OMRON PLCs
CS Series, CJ Series, or CP Series
Mitsubishi Electric PLCs
MELSEC Q Series, L Series, or FX Series (compatible with the FX2 or FX3 (excluding the FX1S))
KEYENCE PLCs
KEYENCE KV Series
Current Transformer (Order Separately)
Ratings
Dielectric strength
1,000 VAC for 1 min
Vibration resistance
50 Hz, 98 m/s2
Weight
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Armatures (2)
Plugs (2)
Heater Burnout Alarms and SSR Failure
Alarms
CT input (for heater current
detection)
Models with detection for single-phase heaters: One input
Maximum heater current
50 A AC
Input current
indication accuracy
±5% FS ±1 digit max.
Heater burnout alarm
setting range *1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms *3
SSR failure alarm setting
range *2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms *4
*1
*2
*3
*4
For heater burnout alarms, the heater current will be measured when the
control output is ON, and the output will turn ON if the heater current is
lower than the set value (i.e., heater burnout detection current value).
For SSR failure alarms, the heater current will be measured when the
control output is OFF, and the output will turn ON if the heater current is
higher than the set value (i.e., SSR failure detection current value).
The value is 30 ms for a control period of 0.1 s or 0.2 s.
The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for
Control Output Relay (Reference Values)
Life (× 104 operations)
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
Both the programless communications and the component communications
support the copying.
500
300
200
100
E5GC
250 VAC, 30 VDC
(resistive load)
cosφ = 1
50
30
20
10
5
3
2
1
0.1
0.2 0.3 0.5
1
2
3
5
10
Switching current (A)
E5GC
External Connections
E5GC
Control Outputs
E5GC-@ @ @ @ @ M - @ @ @
Relay output
250 VAC, 2 A
(resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
(1) (2)(3)(4)(5)
(6)
↑
Terminal type
Auxiliary outputs 1, 2
The E5GC is set for a K-type thermocouple (input type = 5) by
default. An input error (s.err) wil occur if the input type setting
does not agree with the temperature sensor. Check the input type.
Relay outputs
250 VAC, 2 A
(resistive load)
(6) Options
015
Communications
(RS-485)
RS-485
B(+)
016
023
Event input 1
CT input
EV1
A(−)
−
+
7
8
(5) Sensor
(Temperature/
Analog) Input
024
Event inputs 1 and 2
EV2
CT
−
+
−
+
EV1
+
TC 10 11 12
7
8
9
9
7
8
7
9
8
9
B
A
Pt
(3) Input Power Supply
100 to 240 VAC
1
B
10 11 12
+ mA
−
24 VAC/DC
2
1
2
7
8
9 10 11 12
1
2
3
I
10 11 12
−
(no polarity)
4
5
6
V
V
+
10 11 12
(2) Auxiliary Outputs
Auxiliary
output 1
(1) Control Outputs
RX
QX
Relay output
R
Voltage output (for driving SSR) Linear current output
Q
C
CX
+
−
+
9
−
5
3
4
3
4
3
Auxiliary outputs 1, 2
Auxiliary
output 2
4
5
6
Auxiliary
output 1
6
Auxiliary
output 1
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams
Sensor input and CT input
Communications and event inputs
Power
supply
Voltage output (for driving SSR) and linear current output
Relay output
Auxiliary outputs 1 and 2
: Reinforced insulation
: Functional isolation
Note: Auxiliary outputs 1 to 2 are not insulated.
11
E5GC
Wiring Methods
E5GC-@C
Controllers with Screwless Clamp Terminal Blocks
E5GC-@6
Controllers with Screw Terminal Blocks (M3 Screws)
Controllers with Screw Terminal Blocks
Controllers with Screwless Clamp Terminals Blocks
• Terminal type: Forked or round crimped terminals
• Tightening torque for all terminals: 0.43 to 0.58 N·m
• Wire stripping length: 8 to 12 mm
• Ferrules: 8 to 12 mm
0.8 to 1.4 mm
5.8 mm max.
8 to 12 mm
8 to 12 mm
5.8 mm max.
Wires: AWG24 to AWG18 (equal to a cross-sectional area of 0.205 to 0.823 mm2) braided or solid wires
Nomenclature
E5GC
Front panel
Left Side View of the E5GC
Left-panel
Setup Tool
port
No. 1 display
Temperature unit
PV or specified parameter
No.2 display
SP or specified parameter value
Bottom View of E5GC
Operation indicators
Press O Key once to go to Adjustment Level.
Use the U D Keys to set the parameter.
Press O Key for at least 3 seconds
to go to the Initial Setting Level.
Bottom-panel Setup
Tool port
Use the M Key to change
to another parameter.
12
Use S Key to change the
digit (default setting).
E5GC
Dimensions
(Unit: mm)
Controllers
E5GC-@6
Controllers with Screw
Terminal Blocks
Waterproof Packing (Accessory)
63.6
48
Mounting Adapter (Accessory)
Terminal Cover (Accessory)
4
90
44.8
1
22
40.8
24
22
• Use two Mounting Adapters, either on the top and bottom or on the right and left.
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable
and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either
port connected constantly during operation.)
Mounted Separately
Horizontally Group Mounted
L1
To mount the Temperature Controller so that it is waterproof,
insert the Waterproof Packing onto the Temperature Controller.
Group mounting does not allow waterproofing.
22.2+0.3
0
40 min
45+0.60
L1=(48×n-2.5)
22.2+0.3
0
+1.0
+0
n: Number of mounted Controllers (2 ≤ n ≤ 6)
• To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed
adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case.
• Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to maintain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m.
• When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable
operating temperature range given below.
Horizontal group mounting: −10 to 55°C
• Use Temperature Controllers with Screwless Clamp Terminal Blocks for vertical group mounting.
E5GC-@C
Controllers with Screwless
Clamp Terminal Blocks
Waterproof Packing (Accessory)
Mounting Adapter (Accessory)
63.6
48
4
93
44.8
1
22
40.8
24
22
• Use two Mounting Adapters, either on the top and bottom or on the right and left.
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable
and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either
port connected constantly during operation.)
Mounted Separately
Horizontally Group Mounted
Vertically Group Mounted
45
L1
+0.6
+0
22.2+0.3
0
40 min
45+0.60
L1=(48×n-2.5)
+1.0
+0
n: Number of mounted Controllers (2 ≤ n ≤ 6)
22.2+0.3
0
L2
To mount the Temperature Controller so
that it is waterproof, insert the Waterproof
Packing onto the Temperature Controller.
Group mounting does not allow waterproofing.
L2=(24×n-1.5) +1.0
+0
• To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed
adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case.
• Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to maintain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m.
• When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable
operating temperature range given below.
Horizontal group mounting: −10 to 55°C
Vertical group mounting of two Controllers: −10 to 45°C
Vertical group mounting of three or more Controllers: −10 to 40°C
• If you use vertical group mounting, you cannot draw out the interior body of the Controller.
13
E5GC
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2
(2110)
250
263
1510
LED (RD)
USB connector
(type A plug)
Serial connector
LED (PWR)
LED (SD)
● Conversion Cable
E58-CIFQ2-E
Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510)
250
263
1510
E58-CIFQ2 (Order separately)
Note: Always use this product together with the E58-CIFQ2.
Conversion Cable
● Current Transformers
E54-CT1
21
15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
E54-CT1
2.8
5.8 dia.
7.5
3
Output voltage (Eo) V (r.m.s.)
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings:
400±2
Winding resistance:
18±2 Ω
10.5
40
Two, 3.5 dia.
10
30
100V
Frequency: 50 Hz
∞
1kΩ
10
Distortion
factor
10%
1
3%
1%
100mV
100Ω
10
E54-CT3
2.36 dia.
30
RL=10Ω
1
12 dia.
9
100μV
10
1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Two , M3 holes (depth: 4)
30
Connection Example
Armature
Plug
Approx. 3 dia.
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum
continuous heater current for an OMRON Digital Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
15
E54-CT3 Accessories
• Armature
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
E54-CT3
100V
Frequency: 50 Hz
Distortion
factor
10%
3%
1%
∞
1kΩ
500Ω
10
1
100mV
100Ω
50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV
(22)
10
1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
14
E5GC
● Mounting Adapter
Y92F-53 (Two provided.)
One pair is provided with the Termperature
Controller. Order this Adapter separately if it
becomes lost or damaged.
34.7
12
11.8 9.4
● Waterproof Packing
Y92S-P12
The Waterproof Packing is provided with the Temperature Controller.
Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating
environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the operating environment.
Be sure to confirm this point at your site. Consider three years a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
● Draw-out Jig
Y92F-55
Use this Draw-out Jig to remove the interior
body of the Digital Temperature Controller
from the case to perform maintenance
without removing the terminal wiring.
32.9
15
30.5
1.4
27.4
28.7
22
20
23
15
Digital Temperature Controller
E5CC/E5CC-U
(48 × 48 mm)
Large White PV Display That’s Easier to Read.
Easy to Use, from Model Selection to
Setup and Operation.
A Complete Range of I/O Capacities,
Functions, and Performance.
Handles More Applications.
• The white PV display with a height of 15.2 mm improves visibility.
48 × 48 mm
48 × 48 mm
• High-speed sampling at 50 ms.
E5CC-U
E5CC
• Models are available with up to 3 auxiliary outputs, up to 4 event
inputs, a transfer output, and a remote SP input to cover a wide Refer to your OMRON website for the most recent information on
applicable safety standards.
range of applications.
• E5CC: Short body with depth of only 60 mm.
• Set up the Controller without wiring the power supply by
Refer to Safety Precautions on page 104.
connecting to the computer with a Communications Conversion
Cable (sold separately). Setup is easy with the CX-Thermo (sold
separately).
• Easy connections to a PLC with programless communications. Use component communications to link
Temperature Controllers to each other.
Main I/O Functions
Sensor Input
Universal input
• Thermocouple
• Pt
• Analog current/voltage
E5CC/E5CC-U
Dual displays: PV/SV
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Linear current output
Indication Accuracy
• Thermocouple input:
±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input:
±0.2% of FS
Control Output 2
<E5CC>
<E5CC-U>
• None
• None
• Voltage output
(for driving SSR)
Sampling Period
• 50 ms
Event Inputs
<E5CC>
<E5CC-U>
• None
• None
•2
•4
Remote SP Input
<E5CC>
<E5CC-U>
• None
• None
•1
4-digit displays
• PF (shift) Key
• Temperature status display
• Simple programming
• Independent heating and
cooling PID control
• Changed parameter display
• Display brightness setting
Auxiliary Outputs
<E5CC>
<E5CC-U>
•3
• None
•1
•2
Transfer Output
<E5CC>
<E5CC-U>
• None
• None
•1
Serial Communications
<E5CC>
<E5CC-U>
• None
• None
• RS-485
This datasheet is provided as a guideline for selecting products.
Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
16
E5CC/E5CC-U
Model Number Legend and Standard Models
Model Number Legend
●Models with Screw Terminals
E5CC-@@ 3 @ 5 M -@@@ (Example: E5CC-RX3A5M-000)
−− − − − − −−−
A
B C D E
F
A
Model
Control outputs
1 and 2
B
C
D
No. of Power
Terminal
auxiliary supply
type
outputs voltage
E
F
Input
type
Options
Meaning
48 × 48 mm
Control output 1
Relay output
Voltage output
(for driving SSR)
Linear current output *2
Voltage output
(for driving SSR)
E5CC
RX
QX
*1 *3 CX
QQ
CQ
Linear current output *2
3
A
D
5
M
*1
000
001
*1
003
*3
004
005
006
007
Control output 2
None
None
None
Voltage output
(for driving SSR)
Voltage output
(for driving SSR)
3 (one common)
100 to 240 VAC
24 VAC/DC
Screw terminals (with cover)
Universal input
Event
Remote Transfer
HB alarm and
Communications
HS alarm
inputs
SP Input output
----------1
--2
----2
(for 3-phase
RS-485
------heaters)
--RS-485
2
--------4
--------2
Provided.
----2
Provided.
---
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.
*3. Option 004 can be selected only when "CX" is selected for the control outputs.
Heating and Cooling Control
● Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
17
E5CC/E5CC-U
Model Number Legend
●Plug-in Models
E5CC-@@ @ @ U M -000 (Example: E5CC-RW0AUM-000)
A
B C D E
A
Model
B
F
C
D
Control No. of Power
Terminal
outputs auxiliary supply
type
1 and 2 outputs voltage
E
F
Input
type
Options
Meaning
48 × 48 mm
E5CC
RW
Control output 1
Relay output (SPDT)
Control output 2
None
QX
Voltage output (for driving SSR)
None
CX
Linear current output*
None
0
None
1
1
2
2 (one common)
A
100 to 240 VAC
D
24 VAC/DC
U
Plug-in model
M
HB alarm and HS
alarm
---
000
Universal input
CommuniRemote SP Transfer outEvent inputs
cations
Input
put
---------
* The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in May 2014 or later.
List of Models
Options
Control output
No. of auxiliary
outputs
HB alarm and
HS alarm
No. of event
inputs
Voltage output
(for driving SSR)
1
---
---
---
100 to 240 VAC
24 VAC/DC
E5CC-RW0AUM-000
E5CC-RW0DUM-000
E5CC-RW1AUM-000
E5CC-RW1DUM-000
2
E5CC-RW2AUM-000
E5CC-RW2DUM-000
---
E5CC-QX0AUM-000
E5CC-QX0DUM-000
E5CC-QX1AUM-000
E5CC-QX1DUM-000
E5CC-QX2AUM-000
E5CC-QX2DUM-000
E5CC-CX0AUM-000
E5CC-CX0DUM-000
E5CC-CX1AUM-000
E5CC-CX1DUM-000
E5CC-CX2AUM-000
E5CC-CX2DUM-000
1
---
---
---
2
--Linear current
output
Model
Power supply voltage
Communications
--Relay output
Model
Power supply voltage
1
---
---
2
---
Heating and Cooling Control
●Using Heating and Cooling Control
A Control Output Assignment
An auxiliary output is used as the cooling control output.
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
18
E5CC/E5CC-U
Optional Products (Order Separately)
USB-Serial Conversion Cable
Front Covers
Model
E58-CIFQ2
Type
Hard Front Cover
Soft Front Cover
Model
Y92A-48H
Y92A-48D
Terminal Covers (for E5CC)
CX-Thermo Support Software
Model
E53-COV17
E53-COV23 (3pcs)
Model
EST2-2C-MV4
Note: The Terminal Covers E53-COV23 are provided only with E5CC
Controllers. The E53-COV10 cannot be used.
Refer to page 28 for the mounted dimensions.
Waterproof Packing
Note: CX-Thermo version 4.5 or higher is required for the E5CC.
CX-Thermo version 4.61 or higher is required for the E5CC-U.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
Model
Y92S-P8
Note: The Waterproof Packing is provided only with E5CC
Controllers.
The E5CC-U cannot be waterproofed even if the Waterproof
Packing is attached.
Current Transformers (CTs)
Hole diameter
5.8 mm
12.0 mm
Model
E54-CT1
E54-CT3
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
Waterproof Cover
Model
Y92A-48N
Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
DIN Track Mounting Adapter
Model
Y92F-52
Sockets (for E5CC-U)
Type
Front-connecting Socket
Front-connecting Socket with Finger Protection
Back-connecting Socket
Terminal Cover for Back-connecting socket
with Finger Protection
Model
P2CF-11
P2CF-11-E
P3GA-11
Y92A-48G
19
E5CC/E5CC-U
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Control
output
Voltage output
(for driving SSR)
Linear current output
Number of outputs
Auxiliary
output
Output specifications
Number of inputs
Event
input*
Transfer
output*
External contact input
specifications
Number of outputs
Output specifications
Setting method
Remote SP input*
Indication method
Multi SP*
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or
1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the
E5CC-U only for those manufactured in May 2014 or later.)
Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB/THB.)
ON/OFF control or 2-PID control (with auto-tuning)
E5CC:
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value)
E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value)
Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
E5CC: 3
E5CC-U: 1 or 2 (depends on model)
SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3
outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at
5 V (reference value)
2 or 4 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
1 (only on models with a transfer output)
Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000
Digital setting using front panel keys
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
11-segment digital display and individual indicators
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,
or serial communications.
None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving
average of input value, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting
(with no condensation or icing)
25% to 85%
-25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 18.
20
E5CC/E5CC-U
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor
type
Platinum resistance
thermometer
Sensor
specification
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to
70°C
60 to
120°C
115 to
165°C
120
165
140 to
260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600
1500
1400
1300
1300
1300
1300
1200
1100
1000
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
90
100
0
0.0
-100
-200
100.0
-200
-199.9
0
1
Set value
0.0
199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100
-200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input
Input type
Input
specification
Setting range
Set value
Current
4 to 20 mA
0 to 20 mA
Voltage
1 to 5 V
Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
25
26
27
0 to 5 V
0 to 10 V
0 to 50 mV*
28
29
30
* The range applies to the E5CC-U only for those manufactured in May 2014 or later.
21
E5CC/E5CC-U
Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Set
value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2
Upper-limit
(default)
3
Lower-limit
4
Upper- and lower-limit
range *1
5
6
7
8
9
10
11
Alarm output operation
Description of function
When alarm value X When alarm value X
is positive
is negative
Output OFF
No alarm
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*2
OFF
PV
lower limit (L). The alarm is ON when the PV is outside this
SP
deviation range.
Set the upward deviation in the set point by setting the alarm
X
X
ON
ON
value (X). The alarm is ON when the PV is higher than the
OFF
PV
OFF
PV
SP
SP
SP by the deviation or more.
Set the downward deviation in the set point by setting the
X
X
ON
ON
alarm value (X). The alarm is ON when the PV is lower than
OFF
PV
OFF
PV
SP
SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*3
OFF
PV
lower limit (L). The alarm is ON when the PV is inside this deSP
viation range.
Upper- and lower-limit
with standby sequence *1 *5
Upper-limit with standby
sequence
Lower-limit with standby
sequence
ON
OFF
Absolute-value upper-limit
ON
OFF
Absolute-value lower-limit
ON
OFF
Absolute-value upper-limit with standby sequence
ON
OFF
Absolute-value lower-limit
with standby sequence
ON
OFF
LBA (alarm 1 type only)
PV change rate alarm
14
SP absolute-value
upper-limit alarm
ON
OFF
SP absolute-value
lower-limit alarm
ON
OFF
X
SP
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
X
SP
X
0
X
0
X
0
X
0
X
ON
OFF
19
22
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X
SP
X
0
PV
X
0
PV
X
0
PV
X
0
PV
0
ON
OFF
SP
ON
OFF
X
0
The alarm will turn ON if the process value is smaller than the
alarm value (X) regardless of the set point.
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X
0
SP
X
0
SP
This alarm type turns ON the alarm when the set point (SP)
is higher than the alarm value (X).
This alarm type turns ON the alarm when the set point (SP)
is lower than the alarm value (X).
Standard Control
X
MV
0
The alarm will turn ON if the process value is larger than the
alarm value (X) regardless of the set point.
ON
OFF
X
0
MV
X
MV
0
X
MV
0
Always ON
Standard Control
ON
OFF
X
0
MV
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
ON
OFF
18
PV
*7
*8
SP
Standard Control
17
SP
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
ON
OFF
MV absolute-value
lower-limit alarm *9
X
-
ON
OFF
MV absolute-value
upper-limit alarm *9
*4
PV
Standard Control
16
A standby sequence is added to the upper- and lower-limit
alarm (1). *6
H
SP
ON
OFF
12
13
15
L
ON
OFF
RSP absolute-value
upper-limit alarm *10
ON
OFF
RSP absolute-value
lower-limit alarm *10
ON
OFF
X
MV
0
X
0
RSP
ON
OFF
RSP
ON
OFF
X
0
Always ON
X
0
RSP
X
0
RSP
This alarm type turns ON the alarm when the remote SP
(RSP) is higher than the alarm value (X).
This alarm type turns ON the alarm when the remote SP
(RSP) is lower than the alarm value (X).
E5CC/E5CC-U
*1
*2
With set values 1, 4 and 5, the upper and lower limit values can be set
independently for each alarm type, and are expressed as “L” and “H.”
Set value: 1, Upper- and lower-limit alarm
Case 2
Case 1
Case 3 (Always ON)
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
H
SP L H
H>0, L<0
|H| > |L|
SP
L
H<0, L>0
|H| ≥ |L|
L SP
H
SP H
*3
L
H>0, L<0
|H| ≤ |L|
Set value: 4, Upper- and lower-limit range
Case 1
Case 3 (Always OFF)
Case 2
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
SP L
H
H
H>0, L<0
|H| > |L|
H
SP
L
L SP
SP H L
H<0, L>0
|H| ≥ |L|
H>0, L<0
|H| ≤ |L|
*4
Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above *2
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
• Case 3: Always OFF
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
*6 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H174) for information on the operation of the standby sequence.
*7 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat.
No.H174) for information on the loop burnout alarm (LBA).
*8 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H174) for information on the PV change rate alarm.
*9 When heating/cooling control is performed, the MV absolute upper limit
alarm functions only for the heating operation and the MV absolute lower
limit alarm functions only for the cooling operation.
*10 This value is displayed only when a remote SP input is used. It functions in
both Local SP Mode and Remote SP Mode.
Remote SP input is supported only for the E5CC.
23
E5CC/E5CC-U
Characteristics
E5CC
Thermocouple:
(±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
Indication accuracy
CT input:
±5% FS ±1 digit max.
(at the ambient temperature of 23°C)
E5CC-U
Thermocouple:
(±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
Transfer output accuracy
±0.3% FS max.
Remote SP Input Type
±0.2% FS ±1 digit max.
Influence of temperature *2
Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2
Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
Input sampling period
50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
-1999 to 9999 (decimal point position depends on input type)
Influence of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance
10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction
100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance
300 m/s2, 3 times each in X, Y, and Z directions
E5CC: Controller: Approx. 120 g, Adapter: Approx. 10 g
Weight
E5CC-U: Controller: Approx. 100 g, Adapter: Approx. 10 g
E5CC: Front panel: IP66, Rear case: IP20, Terminals: IP00
Degree of protection
E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
E5CC: CX-Thermo version 4.5 or higher
Setup Tool
E5CC-U: CX-Thermo version 4.61 or higher
E5CC/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB
Setup Tool port
port on the computer. *5
Approved standards
UL 61010-1*6, KOSHA certified (some models) *7, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards
EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *8
EMI:
EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326
ESD Immunity:
EN 61000-4-2
EMC
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C,
whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6 The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11
is not certified for UL listing.
*7 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*8 Refer to information on maritime standards in Shipping Standards on page 106 for compliance with Lloyd's Standards.
24
E5CC/E5CC-U
USB-Serial Conversion Cable
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.5 or higher (Version 4.61 or
higher is required for the E5CC-U.)
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38400 bps
Connector
specifications
Computer: USB (type A plug)
Digital Temperature Controller:
Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Output current
250 mA max.
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Ambient operating
temperature
0 to 55°C (with no condensation or icing)
Ambient operating
humidity
10% to 80%
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
* Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation
procedure.
Communications Specifications
Transmission line
connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization
method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Communications Functions
Programless
communications*1
You can use the memory in the PLC to read and
write E5@C parameters, start and stop operation,
etc. The E5@C automatically performs communications with PLCs. No communications programming is required.
Number of connected Digital Temperature Controllers: 32 max. (Up to 16 for the FX Series)
Applicable PLCs
OMRON PLCs
CS Series, CJ Series, or
CP Series
Mitsubishi Electric PLCs
MELSEC Q Series, L Series, or FX Series
(compatible with the FX2 or FX3 (excluding
the FX1S))
KEYENCE PLCs
KEYENCE KV Series
Component
Communications*1
When Digital Temperature Controllers are connected, set points and RUN/STOP commands
can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
Slope and offsets can be set for the set point.
Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*2
When Digital Temperature Controllers are connected, the parameters can be copied from the
Digital Temperature Controller that is set as the
master to the Digital Temperature Controllers that
are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
KEYENCE is a registered trademark of Keyence Corporation.
*1 A Temperature Controller with version 1.1 or higher is required.
A Temperature Controller with version 2.1 or higher is required for
the FX Series or the KV Series.
*2 Both the programless communications and the component
communications support the copying.
Current Transformer (Order Separately)
Ratings
Dielectric strength
Vibration resistance
Weight
Accessories
(E54-CT3 only)
1,000 VAC for 1 min
50 Hz, 98 m/s2
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Armatures (2)
Plugs (2)
Heater Burnout Alarms and SSR Failure
Alarms
CT input (for heater
current detection)
Maximum heater
current
Input current
indication accuracy
Heater burnout
alarm setting range
*1
SSR failure alarm
setting range *2
Models with detection for single-phase
heaters: One input
Models with detection for singlephase or
three-phase heaters: Two inputs
50 A AC
±5% FS ±1 digit max.
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms *3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms *4
*1 For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output will turn ON if the
heater current is lower than the set value (i.e., heater burnout
detection current value).
*2 For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output will turn ON if the heater
current is higher than the set value (i.e., SSR failure detection
current value).
*3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
*4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for
Relays (Reference Values)
Life (× 104 operations)
Applicable OS
500
300
100
50
30
10
5
E5CC
250 VAC, 30 VDC
(resistive load)
cosφ = 1
3
1
0
1
2
3
4
5
6
Switching current (A)
25
E5CC/E5CC-U
External Connections
E5CC
Control output 1
E5CC-@@ 3 @ 5 M - @ @ @
Relay output
250 VAC, 3A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
(1)
Auxiliary outputs 1, 2, 3
(1) Control outputs 1, 2
RX
QX
Models with
1 Relay
Output
1
2
3
QQ
CX
OUT1
+
- Q
(5) Sensor (Temperature/Analog) Input
Pt
TC
V
I
A
+ 4
4
4
4
B
mA
- 5
- 5
5
5
B
V
6
6
6
+ 6
+
(6) Options
001
Event Inputs 1
and 2, and CT1
-
B(+)
RS-485
+
14
+ EV1
15
EV2
CT1
A(-)
17
COM
CT2
18
13
14
3
4
5
15
16
004
Communications
(RS-485), and
Event Inputs 3 and 4
B(+)
13
RS-485
14
A(-)
8
9
10
11
17
18
12
-
13
+
14
+
Auxiliary output 1
●
●
11
11
12
12
-
16
+
17
+
18
EV3
EV1
+
17
+
18
EV4
006
Event Inputs
1 and 2, and
Transfer Output
13
14
EV2
EV3
EV4
15
13
14
+ EV1
15
EV2
16
16
-
+
17
17
18
18
+
+V
I
E5CC-UM-000
The E5CC-U is set for a K-type thermocouple (input type =
5) by default. An input error (s.err) will occur if the input
type setting does not agree with the temperature sensor.
Check the input type.
Control output 1
Auxiliary outputs 1, 2
Relay output
250 VAC, 3 A (resistive load)
Control output 1
Auxiliary output 1
Auxiliary output 2:
Control output (cooling side)
I
Pt
+
V
mA
−
A
TC
−
−
B
+
+
B
V
Input power supply
Sensor (temperature/analog) input
Control output 1
• 100 to 240 VAC
• 24 VAC/DC (no polarity)
Control output 1:
−
Output 1
Q
+
RW
CX
QX
Models with 1
Voltage Output
(for Driving SSR)
Models with 1
Relay Output
Models with 1
Linear Current
Output
−
Output 1
C
Output 1
R
+
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
Connect M3.5 crimped terminals for the E5CC-U.
26
Auxiliary output 2
(3) Input Power Supply
100 to 240 VAC
24 VAC/DC
E5CC-U
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output
4 to 20 mA DC
0 to 20 mA DC
Load: 500 Ω max.
Relay output (three terminals used)
SPDT, 250 VAC, 3 A
(resistive load)
Auxiliary output 3
7
005
Event Inputs
1 to 4
15
16
CT1
1
2
7
8
9
10
(no polarity)
15
16
(2) Auxiliary Outputs
Auxiliary outputs 1, 2, 3
OUT1
+C
- Q
+ OUT2
1
2
3
6
003
Communications
(RS-485), CT1,
and CT2
13
The E5CC is set for a K-type thermocouple (input type = 5) by
default. An input error (s.err) will occur if the input type setting does
not agree with the temperature sensor. Check the input type.
Models with 2 Outputs: Linear Current
Output and Voltage (for Driving SSR)
OUT1
+Q
- Q
+ OUT2
OUT1 1
+
- C
2
3
1
2
3
(6)
CQ
Models with 2
Models with
Voltage Outputs
1 Linear
Current Output (for Driving SSR)
Models with 1
Voltage Output
(for Driving SSR)
OUT1 1
R
2
3
Relay outputs
Models with 3 auxiliary
outputs: 250 VAC, 2 A
(resistive load)
Control output 2
Voltage output
(for driving SSR)
12 VDC, 21 mA
(2) (3) (4) (5)
↑
Terminal type
-
007
Event Inputs
1 and 2, and
Remote SP Input
13
+
14
+ EV1
15
EV2
+
16
V +
17
mA
18
E5CC/E5CC-U
Isolation/Insulation Block Diagrams
• E5CC
Models with 3 Auxiliary Outputs
Sensor input, CT inputs, and remote SP input
Communications and event inputs
Voltage output (for driving SSR),
linear current output, and transfer output
Power
supply
Relay output
Auxiliary outputs 1, 2, 3
: Reinforced insulation
: Functional isolation
Note: Auxiliary outputs 1 to 3 are not insulated.
• E5CC-U
Models with 2 Auxiliary Outputs
Sensor input
Power
supply
Voltage output (for driving SSR) and linear current output
Relay output
Auxiliary outputs 1 and 2
: Reinforced insulation
: Functional isolation
Nomenclature
E5CC
E5CC-U
Front panel
Temperature unit
Operation indicators
Top View of E5CC
Top View of E5CC-U
No. 1 display
PV or specified parameter
No. 2 display
SP or specified parameter value
Use the U D Keys to set the
parameter.
Top-panel Setup Tool port
Press O Key once to go to Adjustment Level.
Use S Key to change the digit (default setting).
Press O Key for at least 3 seconds to go to Initial Setting Level.
Use the M Key to change to another parameter.
27
E5CC/E5CC-U
Dimensions
(Unit: mm)
Controllers
E5CC
73.1
60
4
48 × 48
1
48 × 48
44.8 × 44.8 48.8 58
Waterproof Packing
(Accessory)
Mounting Adapter
(Accessory)
Terminal Cover
(E53-COV17)
(Sold separately)
The Setup Tool port is on the top of the Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.
Panel Cutout
Mounted Separately
Group Mounted
(48 × number of units - 2.5)+1.0
0
• Recommended panel thickness is 1 to 5 mm.
• Group mounting is not possible in the vertical direction. (Maintain
the specified mounting space between Controllers.)
• To mount the Controller so that it is waterproof, insert the
waterproof packing onto the Controller.
• When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
• Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a
USB-Serial Conversion Cable are used together.
45+0.6
0
60 min.
45+0.6
0
45+0.6
0
E5CC-U
48 × 48
4
76.8
58.6
14.2
48 × 48
58
Mounting Adapter
(Accessory)
The Setup Tool port is on the top of the Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.
Panel Cutout
Mounted Separately
Group Mounted
(48 × number of units - 2.5)+1.0
0
45+0.6
0
60 min.
45+0.6
0
45+0.6
0
28
• Recommended panel thickness is 1 to 5 mm.
• Group mounting is not possible in the vertical direction. (Maintain
the specified mounting space between Controllers.)
• When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
• Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a
USB-Serial Conversion Cable are used together.
E5CC/E5CC-U
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2
(2110)
250
263
1510
LED (RD)
USB connector
(type A plug)
Serial connector
LED (PWR)
LED (SD)
● Terminal Covers
E53-COV17
● Terminal Covers
E53-COV23 (Three Covers provided.)
48
2
3.8
48.8
10
Terminal Cover
(E53-COV23)
22
44.8
9.1
● Terminal Cover (for the P3GA-11 Back-connecting Socket)
Y92A-48G
Twelve, 6.4-dia.
34
Y92A-48G
UP
47.7×47.7
48×48
P C
16.5
24.6 27.6
47.4
Note: You can attach the P3GA-11 Back-connecting Socket for finger protection.
● Waterproof Packing
Y92S-P8 (for DIN 48 × 48)
The Waterproof Packing is provided only with the E5CC.
Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.
29
E5CC/E5CC-U
● Current Transformers
E54-CT1
21
15
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT1
2.8
5.8 dia.
7.5
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings:
400±2
Winding resistance:
18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5
40
Two, 3.5 dia.
10
30
100V
Frequency: 50 Hz
∞
1kΩ
10
Distortion
factor
10%
1
3%
1%
100mV
100Ω
10
E54-CT3
2.36 dia.
30
RL=10Ω
1
12 dia.
9
100μV
10
1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT3
Two, M3 (depth: 4)
15
E54-CT3 Accessories
• Armature
Approx. 3 dia.
Connection Example
Plug
Armature
Lead
18
• Plug
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Digital Temperature Controller is 50 A.)
Number of windings:
400±2
Winding resistance:
8±0.8 Ω
30
100V
Frequency: 50 Hz
Distortion
factor
10%
3%
1%
∞
1kΩ
500Ω
10
1
100mV
100Ω
50Ω
10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
30
E5CC/E5CC-U
● Adapter
Y92F-45
Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial
Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
Fixture (Accessory)
76
4.7
69.6 to 77.6
72 × 72
67 × 67 87
Mounted to E5CC
Panel (1 to 8 mm)
Mounting Adapter
Y92F-30
(Accessory)
72 × 72
48 × 48
2.2
4.7
62.8
To back of the E5CC
● DIN Track Mounting Adapter
Y92F-52
Note: This Adapter cannot be used together with the Terminal Cover.
Remove the Terminal Cover to use the Adapter.
61
3.5
This Adapter is used to mount the
E5CC to a DIN Track.
If you use the Adapter, there is no
need for a plate to mount in the
panel or to drill mounting holes in
the panel.
38
50
Mounted to E5CC
48
80.5
31
E5CC/E5CC-U
● Watertight Cover
● Mounting Adapter
Y92A-48N
Y92F-49
21.9
14
The Mounting Adapter is provided with the
Temperature Controller.
Order this Adapter separately if it becomes
lost or damaged.
(2)
87.7
69
79.2
12
67.6
● Protective Cover
● Protective Cover
Y92A-48D
Y92A-48H
Note: This Protective Cover cannot be used
if the Waterproof Packing is installed.
This Protective Cover is hard type.
Please use it for the mis-operation
prevention etc.
This Protective Cover is soft type.
It is able to operate the controller with using
this cover.
● E5CC-U Wiring Socket
Front-connecting Socket
P2CF-11
Eleven, M3.5 × 7.5
sems screws
3
Terminal Layout/Internal Connections
(Top View)
4.5
7.8
8 7 6 5
Mounting Holes
4
Two, 4.5 dia. mounting holes
35.4
70 max.
Two,
4.5-dia.
holes
4
50 max.
40±0.2
9
3
10 11 1 2
Note: Can also be mounted
to a DIN track
31.2 max.
Note: 1. A model with finger protection (P2CF-11-E) is also available.
2. You cannot use the P2CF-11 or P2CF-11-E together with the Y92F-45.
Back-connecting Socket
P3GA-11
27dia.
4
7
3
Eleven, M3.5
sems screws
Terminal Layout/Internal Connections
(Bottom View)
5 6 7 8
4
45
25.6
3
9
2 1 11 10
45
4.5 16.3 6.2
6
8.7
Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets.
2. A Protective Cover for finger protection (Y92A-48G) is also available.
3. You cannot use the P3GA-11 together with the Y92F-45.
32
MEMO
33
Digital Temperature Controller
E5EC/E5AC
(48 × 96 mm/96 × 96 mm)
Large White PV Display That’s Easier to Read.
Easy to Use, from Model Selection to
Setup and Operation.
A Complete Range of I/O Capacities,
Functions, and Performance.
Handles More Applications.
• A white LCD PV display with a height of approx. 18 mm for the
E5EC and 25 mm for the E5AC improves visibility.
• Tool ports are provided both on the top panel and the front panel.
Set up the Controller without wiring the power supply by
96 × 96 mm
48 × 96 mm
connecting to the computer with a Communications Conversion
E5AC
E5EC
Cable (sold separately). Setup is easy with the CX-Thermo (sold
Refer to your OMRON website for the most recent
separately).
information on applicable safety standards.
• High-speed sampling at 50 ms.
• Models are available with up to 4 auxiliary outputs, up to 6 event
Refer to Safety Precautions on page 104.
inputs, a transfer output, and a remote SP input to cover a wide
range of applications.
• Short body with depth of only 60 mm.
• Easy connections to a PLC with programless communications.
Use component communications to link Temperature Controllers to each other.
• The new position-proportional control models allow you to control valves as well.
Main I/O Functions
Sensor Input
Universal input
• Thermocouple
• Pt
• Analog current/voltage
E5EC
E5AC
Three-level Display
PV, SV, and MV displayed
at the same time.
4-digit
displays
Indication Accuracy
• Thermocouple input:
±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% of FS
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Linear current output
Sampling Period
Control Output 2
• Voltage output (for driving SSR)
• Relay output
• Linear current output
• 50 ms
Event Inputs
• None
•2
•4
•6
Remote SP Input
• None
•1
• PF (shift) Key
• Setup Tool port on front panel
• Temperature status display
• Simple programming
• Independent heating and
cooling PID control
• Changed parameter display
• Display brightness setting
Auxiliary Outputs
•4
Transfer Output
• None
•1
Serial Communications
• None
• RS-485
This datasheet is provided as a guideline for selecting products.
Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
34
E5EC/E5AC
Model Number Legend and Standard Models
Model Number Legend
●Models with Screw Terminals
E5EC-@@ 4 @ 5 M -@@@ (Example: E5EC-RX4A5M-000)
−− − − − − −−−
A
B C D E
F
E5AC-@@ 4 @ 5 M -@@@ (Example: E5AC-RX4A5M-000)
−− − − − − −−−
A
B C D E
F
A
Model
B
C
D
E
F
No. of auxil- Power
Terminal Input
Options
iary out- supply
type
type
puts
voltage
Control outputs
1 and 2
Meaning
48 × 96 mm
96 × 96 mm
Control output 1
Relay output
Voltage output
(for driving SSR)
Linear current output
Voltage output
(for driving SSR)
Voltage output
(for driving SSR)
Relay output
E5EC
E5AC
RX
QX
*2 CX
QQ
QR
RR
*2 CQ
PR
*3 4
A
D
5
For RX,
For CX or
QX, QQ,
QR, RR, or CC
CQ
M
For PR
Selectable Selectable Selectable
Selectable Selectable
Option
Selectable
selection
conditions
*1
Selectable
Selectable
Selectable
Selectable
Selectable Selectable
None
None
Voltage output
(for driving SSR)
Relay output
Relay output
Linear current outLinear current output
put
Voltage output
Linear current output
(for driving SSR)
Position-proportionPosition-proportional relay output
al relay output
4 (auxiliary outputs 1 and 2 with same common and auxiliary outputs 3 and 4 with same common)
100 to 240 VAC
24 VAC/DC
Screw terminals (with cover)
Universal input
*2 CC
Control outputs 1 and 2
Control output 2
None
000
004
005
009
010
011
013
014
HB alarm
Event Remote Transfer
and
Communications
inputs SP Input output
HS alarm
------------RS-485
2
--------4
----2
(for 3-phase
RS-485
2
----heaters)
1
--4
----1
--6
Provided. Provided.
----6
Provided. Provided.
--RS-485
4
Provided. Provided.
*1. The options that can be selected depend on the type of control output.
*2. The control output cannot be used as a transfer output.
*3. A model with four auxiliary outputs must be selected.
Heating and Cooling Control
l Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
35
E5EC/E5AC
Optional Products (Order Separately)
USB-Serial Conversion Cable
Model
E58-CIFQ2
Communications Conversion Cable
Note: Always use this product together with the E58-CIFQ2.
This Cable is used to connect to the front-panel Setup Tool
port.
Terminal Covers
Model
E53-COV24 (3pcs)
Note: The Terminal Covers E53-COV24 are provided with the Digital
Temperature Controller.
Waterproof Packing
Model
Y92S-P9
Y92S-P10
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.
Waterproof Cover
Applicable Controller
E5EC
E5AC
Model
Y92A-49N
Y92A-96N
Front Port Cover
Model
Y92S-P7
Note: This Front Port Cover is provided with the Digital Temperature
Controller.
Mounting Adapter
Model
Y92F-51 (2pcs)
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
36
Hole diameter
5.8 mm
12.0 mm
Model
E54-CT1
E54-CT3
CX-Thermo Support Software
Model
E58-CIFQ2-E
Applicable Controller
E5EC
E5AC
Current Transformers (CTs)
Model
EST2-2C-MV4
Note: CX-Thermo version 4.5 or higher is required for the E5EC/
E5AC.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
E5EC/E5AC
Specifications
Ratings
Power supply voltage
Operating voltage range
E5EC
Power consumption
E5AC
Sensor input
Input impedance
Control method
Relay output
Control
output
Auxiliary
output
Voltage output
(for driving SSR)
Linear current output
Number of outputs
Output specifications
Number of inputs
Event input External contact input
specifications
Transfer
output
Number of outputs
Output specifications
Remote SP input
Potentiometer input
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
Models with option selection of 000:6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or
2.3 W max. at 24 VDC
All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Models with option selection of 000:7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or
2.4 W max. at 24 VDC
All other models: 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB/THB.)
ON/OFF or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA (reference value)
Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
(The maximum load current is 21 mA for models with two control outputs.)
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
4
SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
2, 4 or 6 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
1 (only on models with a transfer output)
Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000
Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
100 Ω to 10 kΩ
Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: E5EC: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
E5AC: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, or PV/SV/Remaining soak time
Numbers of digits: 4 digits each for PM, SV, and MV displays
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,
or serial communications.
None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting
(with no condensation or icing)
25% to 85%
-25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
37
E5EC/E5AC
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor
type
Platinum resistance
thermometer
Sensor
specification
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to
70°C
60 to
120°C
115 to
165°C
120
165
140 to
260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600
1500
1400
1300
1300
1300
1300
1200
1100
1000
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
90
100
0.0
-100
-200
100.0
-200
-199.9
0
1
Set value
0.0
-199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100
-200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input
Input type
Input
specification
Setting range
Set value
38
Current
4 to 20 mA 0 to 20 mA
Voltage
1 to 5 V
0 to 5 V
Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
25
26
27
28
0 to 10 V
29
E5EC/E5AC
Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Set
value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2
Upper-limit
(default)
3
Lower-limit
4
Upper- and lower-limit
range *1
Alarm output operation
Description of function
When alarm value X When alarm value X
is positive
is negative
Output OFF
No alarm
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*2
OFF
PV
lower limit (L). The alarm is ON when the PV is outside this
SP
deviation range.
Set the upward deviation in the set point by setting the alarm
X
X
ON
ON
value (X). The alarm is ON when the PV is higher than the
OFF
PV
OFF
PV
SP
SP
SP by the deviation or more.
Set the downward deviation in the set point by setting the
X
X
ON
ON
alarm value (X). The alarm is ON when the PV is lower than
OFF
PV
OFF
PV
SP
SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*3
OFF
PV
lower limit (L). The alarm is ON when the PV is inside this deSP
viation range.
Upper- and lower-limit
with standby sequence *1 *5
Upper-limit with standby
sequence
ON
OFF
7
Lower-limit with standby
sequence
ON
OFF
8
Absolute-value upper-limit
ON
OFF
9
Absolute-value lower-limit
ON
OFF
10
Absolute-value upper-limit with standby sequence
ON
OFF
11
Absolute-value lower-limit
with standby sequence
ON
OFF
12
13
LBA (alarm 1 type only)
PV change rate alarm
14
SP absolute-value
upper-limit alarm
ON
OFF
15
SP absolute-value
lower-limit alarm
ON
OFF
5
6
L
H
X
ON
OFF
SP
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
X
SP
X
0
X
0
X
0
X
0
ON
OFF
MV absolute-value
upper-limit alarm *9
X
0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X
SP
X
0
PV
X
0
PV
The alarm will turn ON if the process value is smaller than the
alarm value (X) regardless of the set point.
PV
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
PV
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X
0
X
0
ON
OFF
SP
ON
OFF
X
0
X
0
SP
This alarm type turns ON the alarm when the set point (SP)
is higher than the alarm value (X).
SP
This alarm type turns ON the alarm when the set point (SP)
is lower than the alarm value (X).
X
0
Standard Control
X
MV
0
The alarm will turn ON if the process value is larger than the
alarm value (X) regardless of the set point.
*7
*8
SP
ON
OFF
X
0
MV
X
MV
0
Standard Control
ON
OFF
17
SP
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
ON
OFF
MV absolute-value
lower-limit alarm *9
X
-
Standard Control
16
A standby sequence is added to the upper- and lower-limit
alarm (1). *6
*4
PV
SP
X
MV
0
Always ON
Standard Control
ON
OFF
X
0
MV
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
ON
OFF
18
RSP absolute-value
upper-limit alarm *10
ON
OFF
19
RSP absolute-value
lower-limit alarm *10
ON
OFF
X
MV
0
X
0
RSP
ON
OFF
RSP
ON
OFF
X
0
Always ON
X
0
RSP
This alarm type turns ON the alarm when the remote SP
(RSP) is higher than the alarm value (X).
RSP
This alarm type turns ON the alarm when the remote SP
(RSP) is lower than the alarm value (X).
X
0
39
E5EC/E5AC
*1
With set values 1, 4 and 5, the upper and lower limit values can be set
independently for each alarm type, and are expressed as “L” and “H.”
*2. Set value: 1, Upper- and lower-limit alarm
Case 2
Case 1
Case 3 (Always ON)
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
H
SP L H
H>0, L<0
|H| > |L|
H
SP
L
H<0, L>0
|H| ≥ |L|
L SP
SP H
L
H>0, L<0
|H| ≤ |L|
*3. Set value: 4, Upper- and lower-limit range
Case 1
L
Case 3 (Always OFF)
Case 2
H SP
H<0, L>0
|H| < |L|
SP L
H
H
H>0, L<0
|H| > |L|
H
SP
L
L SP
SP H L
40
H<0, L<0
H<0, L>0
|H| ≥ |L|
H>0, L<0
|H| ≤ |L|
*4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above *2
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
• Case 3: Always OFF
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
*6. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H174) for information on the operation of the standby sequence.
*7. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H174) for information on the loop burnout alarm (LBA). This setting cannot
be used with a position-proportional model.
*8. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H174) for information on the PV change rate alarm.
*9. When heating/cooling control is performed, the MV absolute upper limit
alarm functions only for the heating operation and the MV absolute lower
limit alarm functions only for the cooling operation.
*10. This value is displayed only when a remote SP input is used. It functions in
both Local SP Mode and Remote SP Mode.
E5EC/E5AC
Characteristics
Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Transfer output accuracy
±0.3% FS max.
Remote SP Input Type
±0.2% FS ±1 digit max.
Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
Influence of temperature *2
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1%FS ±1 digit max.
Influence of voltage *2
CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
Input sampling period
50ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in
Integral time (I)
units of 0.1 s)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
-1999 to 9999 (decimal point position depends on input type)
Influence of signal source resisThermocouple: 0.1°C/Ω max. (100 Ω max.)
tance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance
10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction
100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance
300 m/s2, 3 times each in X, Y, and Z directions
E5EC
Controller: Approx. 210 g, Adapter: Approx. 4 g × 2
Weight
E5AC
Controller: Approx. 250 g, Adapter: Approx. 4 g × 2
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.5 or higher
E5EC/E5AC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port
on the computer.*5
Setup Tool port
E5EC/E5AC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion
Cable are used together to connect to a USB port on the computer.*5
Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *6
EMI
EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326
ESD Immunity:
EN 61000-4-2
EMC
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
Indication accuracy
(at the ambient temperature of
23°C)
*1
*2
*3
*4
*5
*6
The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples
at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples
at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The
indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
K thermocouple at -100°C max.: ±10°C max.
The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
Refer to information on maritime standards in Shipping Standards on page 106 for compliance with Lloyd's Standards.
41
E5EC/E5AC
USB-Serial Conversion Cable
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.5 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38,400 bps
Connector
specifications
Computer: USB (type A plug)
Digital Temperature Controller:
Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Output current
250 mA max.
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Ambient operating
temperature
0 to 55°C (with no condensation or icing)
Ambient operating
humidity
10% to 80%
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
*
Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation
procedure.
Communications Specifications
Transmission line
connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization
method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission
code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes
Communications
response wait time
*
0 to 99 ms
Default: 20 ms
The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level.
Communications Functions
Programless
communications*1
You can use the memory in the PLC to read and
write E5@C parameters, start and stop operation,
etc. The E5@C automatically performs communications with PLCs. No communications programming is required.
Number of connected Digital Temperature Controllers: 32 max. (Up to 16 for the FX Series)
Applicable PLCs
OMRON PLCs
CS Series, CJ Series, or CP Series
Mitsubishi Electric PLCs
MELSEC Q Series, L Series, or FX Series
(compatible with the FX2 or FX3 (excluding
the FX1S))
KEYENCE PLCs
KEYENCE KV Series
Component
Communications*1
When Digital Temperature Controllers are connected, set points and RUN/STOP commands
can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
Slope and offsets can be set for the set point.
Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*2
When Digital Temperature Controllers are connected, the parameters can be copied from the
Digital Temperature Controller that is set as the
master to the Digital Temperature Controllers that
are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
KEYENCE is a registered trademark of Keyence Corporation.
*1 A Temperature Controller with version 1.1 or higher is required.
A Temperature Controller with version 2.1 or higher is required for
the FX Series or the KV Series.
*2 Both the programless communications and the component
communications support the copying.
Current Transformer (Order Separately)
Ratings
Dielectric strength
Vibration resistance
Weight
Accessories
(E54-CT3 only)
1,000 VAC for 1 min
50 Hz, 98 m/s2
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Armatures (2)
Plugs (2)
Heater Burnout Alarms and SSR Failure
Alarms
CT input (for heater
current detection)
Maximum heater
current
Input current indication accuracy
Heater burnout
alarm setting range
*1
SSR failure alarm
setting range *2
Models with detection for singlephase
heaters: One input
Models with detection for singlephase or
three-phase heaters: Two inputs
50 A AC
±5% FS ±1 digit max.
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms *3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms *4
*1. For heater burnout alarms, the heater current will be measured when the
control output is ON, and the output will turn ON if the heater current is
lower than the set value (i.e., heater burnout detection current value).
*2. For SSR failure alarms, the heater current will be measured when the
control output is OFF, and the output will turn ON if the heater current is
higher than the set value (i.e., SSR failure detection current value).
*3. The value is 30 ms for a control period of 0.1 s or 0.2 s.
*4. The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for
Relays (Reference Values)
Life (× 104 operations)
Applicable OS
500
300
E5EC/E5AC
250 VAC, 30 VDC
(resistive load)
cosφ = 1
100
50
30
10
5
3
1
0
1
2
3
4
5
6
Switching current (A)
42
E5EC/E5AC
External Connections
E5EC/E5AC
E5EC-@@ 4 @ 5 M - @ @ @
(1)
(2) (3) (4) (5)
↑
Terminal type
Control output 1
Control output 2
Relay output
250 VAC, 5 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 40 mA
When There Is a
Control Output 2:
21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
Relay output
250 VAC, 5 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
(1) Control output
RX
Auxiliary outputs 1, 2, 3, 4
(2) (3) (4) (5)
↑
Terminal type
OUT1
+ C
-
3
4
5
6
17
EV1
18
EV2
19
RR
+Q
OUT2
PR
Models with 2
Relay Outputs
OUT1
3
4
5
6
R
R
OUT2
100 to 240 VAC
R
OUT2
CC
R
Close
OUT1
3
4
5
6
+ C
+ C
-
OUT2
1
2
3
4
5
6
7
8
9
10
11
12
1
2
2
28
+
29
+ EV5 30
EV6
31
32
33
34
+
Remote V + 35
mA
SP input
36
-
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
+ Q
OUT2
Auxiliary outputs 1, 2, 3, 4
O
W
C
Auxiliary output 4
Auxiliary output 3
Auxiliary output 2
TC
22
- 23
+ 24
19
20
21
CT1
013
6 event Inputs, transfer
output, and remote SP input
-
13
+
28
-
+
29
+ EV5 30
EV6
19
20
21
+
Transfer V +
output
I
-
Pt
A
22
B
23
B
24
I
+ 22
mA
23
24
31
32
33
34
+
+
V
Remote
35
mA
SP input
36
(5) Sensor (Temperature/Analog) Input
Auxiliary output 1
13
+
17
+ EV1 18
EV2
+
Transfer V +
I
output
-
Potentiometer Input
(2) Auxiliary Outputs
7
8
9
10
11
12
21
14
+ EV3 15
EV4
16
-
24 VAC/DC
1
CQ
OUT1
+ C
-
21
+
(no polarity)
OUT1
+Q
-
R
CT2
-
Models with 2 Outputs: Linear Current Output
and Voltage (for Driving SSR)
3
4
5
6
19
20
21
(3) Input Power Supply
Models with 2
Models with 2
Position-proportional Linear Current
Relay Output
Outputs
Open
3
4
5
6
EV2
011
6 event Inputs, 1 CT input,
transfer output, and remote SP input
Models with Voltage Output (for
Models with 2 Voltage
Outputs (for Driving SSR) Driving SSR) and Relay Output
3
4
5
6
009
010
Communications, 2 event 4 event inputs
and 1 CT input
inputs, and 2 CT inputs
B(+)
13
13
RS-485
+
14
14
EV3
A(-)
+
15
15
EV4
16
16
+
+
17
17
+ EV1 18
+ EV1 18
EV2
EV2
19
19
CT1
CT1
20
COM
20
+
17
+ EV1 18
+
+
QR
OUT1
+Q
-
The E5EC is set for a K-type thermocouple (input
type = 5) by default. An input error (s.err) will occur
if the input type setting does not agree with the
temperature sensor. Check the input type.
005
004
4 event inputs
Communications
and 2 event inputs
B(+)
13
13
RS-485
+
14
14
A(-)
+ EV3 15
15
EV4
16
16
-
Models with 1
Linear Current Output
OUT1
+Q
-
3
4
5
6
QQ
3
4
5
6
(6)
(6) Options
Relay output
Models with 4 auxiliary
outputs: 250 VAC, 2 A
(resistive load)
CX
Models with 1
Voltage Output
(for Driving SSR)
OUT1
R
3
4
5
6
(1)
20
21
QX
Models with
1 Relay Output
E5AC-@@ 4 @ 5 M - @ @ @
(6)
V
V
+
22
23
24
14
+ EV3 15
EV4
16
+
17
+ EV1 18
EV2
19
20
21
014
Communications, 4 event Inputs,
transfer output, and remote SP input
B(+)
13
RS-485
14
A(-)
15
-
+
+ EV5
EV6
+
Transfer V +
I
output
-
28
29
30
31
32
33
+
34
+
V
Remote
mA 35
SP input
36
16
-
+
17
+ EV1 18
EV2
19
20
21
Note: 1. The application of the terminals depends on
the model.
2. Do not wire the terminals that are shown with
a gray background.
3. When complying with EMC standards, the
cable that connects the sensor must be 30 m
or less. If the cable length exceeds 30 m,
compliance with EMC standards will not be
possible.
4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams
Models with 4 Auxiliary Outputs
Sensor input, CT inputs, potentiometer input, and remote SP input
Communications and event inputs
Power
Supply
Voltage output (for driving SSR),
linear current output, and transfer output
Relay output
Auxiliary outputs 1, 2
Auxiliary outputs 3, 4
: Reinforced insulation
: Functional isolation
Note: Auxiliary outputs 1 to 2 and 3 to 4 are not insulated.
43
E5EC/E5AC
Nomenclature
E5EC
Front panel
No. 1 display
PV or specified parameter
Temperature unit
Top View of E5EC
No. 2 display
Operation indicators
SP or specified parameter value
No. 3 display
Front-panel Setup Tool port
Manipulated value or other value
Manipulated
or other
value
Use the Uvalue
D Keys
to set
Top-panel
Setup
Tool port
the parameter.
Use S Key to change the digit (default setting).
Use the M Key to change to another parameter.
Press O Key once to go to Adjustment Level.
Press O Key for at least 3 seconds to go to Initial Setting Level.
E5AC
Front Panel
Temperature unit
Operation indicators
Top View of E5AC
No. 1 display
PV or specified parameter
No. 2 display
SP or specified parameter value
Front-panel Setup Tool port
No. 3 display
Manipulated value or other value
Press the U or D Key to set the parameter.
Press the S Key to change the digit (default setting).
Press the O Key once to go to the Adjustment Level.
Press the O Key for at least 3 seconds to go to the Initial Setting Level.
44
Press the M Key to change to another parameter.
Top-panel
Setup
Tool port
E5EC/E5AC
Dimensions
(Unit: mm)
Controllers
E5EC
48
(64)
60
4
1
96
44
The Setup Tool ports are on the front and top
of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion
Cable is required to make the connection.
91 Refer to the instructions that are provided
with the USB-Serial Conversion Cable for the
connection procedure.
110
Note: Do not leave the USB-Serial
Conversion Cable connected when
you use the Temperature Controller.
Waterproof
Packing (Accessory)
Mounted Separately
Mounting Adapter
(Accessory)
Group Mounted *
(48 × number of units − 2.5)+1.0
0
45+0.6
0
*
Selections for Control Outputs 1 and 2: QQ, QR, RR, CC, PR, or CQ
If you also specify 011, 013, or 014 for the option selection and use
group mounting, the ambient temperature must be 45°C or less.
If the ambient temperature is 55°C, maintain the following mounting
spaces between Controllers.
92+0.8
0
60 min.
45-0.6
0
Group mounting does not
allow waterproofing.
120 min.
92+0.8
0
92-0.8
0
120 min.
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
• To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
• When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
45
E5EC/E5AC
E5AC
(64)
60
4
1
96 x 96
91 x 91
110
Waterproof
Packing (Accessory)
91
Mounting Adapter
(Accessory)
The Setup Tool ports are on the front and top of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.
Group Mounted *
Mounted Separately
(96 × number of units − 3.5)+1.0
0
92+0.8
0
92+0.8
0
Group mounting does not
allow waterproofing.
120 min.
92+0.8
0
46
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
• To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
• When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
E5EC/E5AC
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2
(2110)
250
263
1510
LED (RD)
USB connector
(type A plug)
Serial connector
LED (PWR)
LED (SD)
● Conversion Cable
E58-CIFQ2-E
Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510)
250
263
E58-CIFQ2 (Order Separately)
1510
Conversion Cable
Note: Always use this product together with the E58-CIFQ2.
● Terminal Covers
E53-COV24 (Three Covers provided.)
2
3.8
● Waterproof Packing
Y92S-P9 (for DIN 48 × 96)
The Waterproof Packing is provided with the Temperature
Controller.
Order the Waterproof Packing separately if it becomes lost or
damaged.
The degree of protection when the Waterproof Packing is used
is IP66.
Also, keep the Port Cover on the front-panel Setup Tool port
of the E5EC/E5AC securely closed.
To maintain an IP66 degree of protection, the Waterproof
Packing and the Port Cover for the front-panel Setup Tool port
must be periodically replaced because they may deteriorate,
shrink, or harden depending on the operating environment.
Y92S-P10 (for DIN 96 × 96) The replacement period will vary with the operating
environment.
Check the required period in the actual application.
Use 3 years or sooner as a guideline.
If a waterproof structure is not required, then the Waterproof
Packing does not need to be installed.
10
91
● Setup Tool Port Cover for top panel
Y92S-P7
Order this Port Cover
separately if the Port Cover on
the front-panel Setup Tool port
is lost or damaged. The
Waterproof Packing must be
periodically replaced because
it may deteriorate, shrink, or
harden depending on the
operating environment.
● Mounting Adapter
Y92F-51 (Two Adapters provided.)
One pair is provided with the
Controller.
Order this Adapter
separately if it becomes lost
or damaged.
47
E5EC/E5AC
● Watertight Cover
Y92A-96N (96 × 96)
● Watertight Cover
Y92A-49N (48 × 96)
21.9
21.9
(2)
(2)
131.7
131.7
67.6
115.6
29.4
29.4
● Current Transformers
E54-CT1
21
15
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT1
2.8
5.8 dia.
7.5
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings:
400±2
Winding resistance:
18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5
40
Two, 3.5 dia.
10
30
100V
Frequency: 50 Hz
∞
1kΩ
10
Distortion
factor
10%
1
3%
1%
100mV
10
100Ω
1
RL=10Ω
E54-CT3
2.36 dia.
30
12 dia.
9
100μV
10
1
10
100mA
1
40 × 40
30
Connection Example
Plug
Armature
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON Digital
Temperature Controller is 50 A.)
Number of windings:
400±2
Winding resistance:
8±0.8 Ω
15
Approx. 3 dia.
100 1,000A
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT3
Two, M3 (depth: 4)
E54-CT3 Accessories
• Armature
10
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz
Distortion
factor
10%
3%
1%
∞
1kΩ
500Ω
10
1
100mV
100Ω
50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV
(22)
10
1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
48
MEMO
49
Digital Temperature Controller
E5DC
(22.5 mm Wide, and DIN Track-mounting Type)
The E5DC Mounts to DIN Track and Is Ideal
for Connections to HMIs and PLCs.
It provides the Same Easy Operation and
Advanced Performance as the Rest of the
E5@C Series.
• A slim body at 85 × 22.5 mm (D × W) that fits into narrow control
panels and mounts to DIN Track.
• Removable terminal block for easy replacement to simplify maintenance.
• High-speed sampling at 50 ms for applications with high-speed
temperature increases.
• Easy connections to a PLC with programless communications.
• Set up the Controller without wiring the power supply by connecting
to the computer with a Communications Conversion Cable (sold separately).
Setup is easy with the CX-Thermo (sold separately).
• Models are available with up to 2 auxiliary outputs and 1 event input to
complete basic functions.
• A white PV display (height: 8.5 mm) is easy to read when setting up,
checking alarms, and making settings in a control panel.
22.5 mm Wide, and
DIN Track-mounting Type
E5DC
Refer to your OMRON website for the most recent
information on applicable safety standards.
Refer to Safety Precautions on page 104.
Main I/O Functions
Sensor Input
Universal input
• Thermocouple
• Pt
• Analog current/voltage
E5DC
Dual displays: PV/SV
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Linear current output
Indication Accuracy
• Thermocouple input:
±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input:
±0.2% of FS
Auxiliary Outputs
• None
•2
Sampling Period
• 50 ms
Event Inputs
• None
•1
Serial Communications
• None
• RS-485
4-digit displays
• PF (shift) Key
• Temperature status display
• Simple programming
• Independent heating and
cooling PID control
• Changed parameter display
• Display brightness setting
This datasheet is provided as a guideline for selecting products.
Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)
50
E5DC
Model Number Legend and Standard Models
Model Number Legend
●Models with Screw Terminals
E5DC-@@ @ @ S M-@@@ (Example: E5DC-RX0ASM-015)
−− − − − − −−−
A
B C D E
F
A
Model
B
No. of
Control
auxiliary
output 1
outputs
C
Power
supply
voltage
D
E
F
Terminal
type
Input
type
Options
Meaning
E5DC
22.5 mm wide and mounts to DIN Track
Control output 1
Control output 2
Relay output
None
Voltage output
None
(for driving SSR)
Linear current output *5
None
None
2 (one common)
100 to 240 VAC
24 VAC/DC
Screw terminals
Universal input
HB alarm and HS alarm
Communications Event input
------1
RS-485
----RS-485
------1
1
--1
RX
QX
CX
0
2
A
D
S
M
*1
*2
*3
*4
*2
*1
*2
*3
*4
*5
000
002
015
016
017
Option 000 can be selected only if two auxiliary outputs are selected.
Options 002 and 017 can be selected only if the control output is a relay output or voltage output and two auxiliary outputs are selected.
Option 015 cannot be selected if the control output is a relay output or voltage output and two auxiliary outputs are selected.
Options 016 can be selected only if the control output is a linear current output and two auxiliary outputs are selected.
The control output cannot be used as a transfer output.
List of Models
Options
Control output
No. of auxiliary
outputs
---
Relay output
2
---
Voltage output
(for driving SSR)
2
HB alarm and HS
alarm
--Detection for singlephase heater
--Detection for singlephase heater
No. of event inputs
2
---
Model
Power supply voltage
Communications
--1
--1
--Linear current
output
Model
Power supply voltage
--1
100 to 240 VAC
24 VAC/DC
RS-485
E5DC-RX0ASM-015
E5DC-RX0DSM-015
---
E5DC-RX2ASM-000
E5DC-RX2DSM-000
RS-485
E5DC-RX2ASM-002
E5DC-RX2DSM-002
---
E5DC-RX2ASM-017
E5DC-RX2DSM-017
RS-485
E5DC-QX0ASM-015
E5DC-QX0DSM-015
---
E5DC-QX2ASM-000
E5DC-QX2DSM-000
RS-485
E5DC-QX2ASM-002
E5DC-QX2DSM-002
---
E5DC-QX2ASM-017
E5DC-QX2DSM-017
RS-485
E5DC-CX0ASM-015
E5DC-CX0DSM-015
---
E5DC-CX2ASM-000
E5DC-CX2DSM-000
RS-485
E5DC-CX2ASM-015
E5DC-CX2DSM-015
---
E5DC-CX2ASM-016
E5DC-CX2DSM-016
Note: These products are sold as a set with a terminal block (i.e., Terminal Unit).
Heating and Cooling Control
●Using Heating and Cooling Control
A Control Output Assignment
An auxiliary output is used as the cooling control output.
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
51
E5DC
Optional Products (Order Separately)
USB-Serial Conversion Cable
End Plate
Model
E58-CIFQ2
Model
PFP-M
Communications Conversion Cable
Spacer
Model
E58-CIFQ2-E
Model
PFP-S
Note: Always use this product together with the E58-CIFQ2.
This Cable is used to connect to the front-panel Setup Tool
port.
DIN Tracks
Model
PFP-100N
PFP-50N
Current Transformers (CTs)
Hole diameter
5.8 mm
12.0 mm
Model
E54-CT1
E54-CT3
Unit Labels
Model
Y92S-L2
Mounting Adapter
Model
Y92F-53 (2pcs)
Short Bars
Model
Y92S-P11 (4 pcs)
CX-Thermo Support Software
Model
EST2-2C-MV4
Note: CX-Thermo version 4.6 or higher is required for the E5DC.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
52
End Cover
Model
Y92F-54
E5DC
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Control
output
Auxiliary
output
Voltage output
(for driving SSR)
Linear current output
Number of outputs
Output specifications
Number of inputs
Event
input
External contact input
specifications
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/
THB.)
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5
V, 10 mA (reference value)
Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000
2 (depends on model)
SPST-NO relay outputs: 250 VAC, 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
1 (depends on model)
Contact input ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
Current flow: approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital displays and individual indicators
Character height: PV: 8.5 mm, SV: 8.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
serial communications.*
None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self
tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change
rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with
no condensation or icing)
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* Only two set points are selectable for event inputs.
53
E5DC
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor
type
Platinum resistance
thermometer
Sensor
specification
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to
70°C
60 to
120°C
115 to
165°C
120
165
140 to
260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600
1500
1400
1300
1300
1300
1300
1200
1100
1000
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
Set value
90
100
0.0
-100
-200
100.0
-200 -199.9
0
1
0.0
-199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100
-200 -199.9 -200
9
10
11
-200 -199.9 -200
12
13
14
15
18
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input
Input type
Input specification
Setting range
Set value
54
Current
Voltage
4 to 20 mA 0 to 20 mA 1 to 5 V
0 to 5 V
Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
25
26
27
28
0 to 10 V
29
E5DC
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)
Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not
displayed.
To use alarm 1, set the output assignment to alarm 1.
Set
value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2
Upper-limit
(default)
3
Lower-limit
4
Upper- and lower-limit
range *1
Alarm output operation
Description of function
When alarm value X When alarm value X
is positive
is negative
Output OFF
No alarm
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*2
OFF
PV
lower limit (L). The alarm is ON when the PV is outside this
SP
deviation range.
Set the upward deviation in the set point by setting the alarm
X
X
ON
ON
value (X). The alarm is ON when the PV is higher than the
OFF
PV
OFF
PV
SP
SP
SP by the deviation or more.
Set the downward deviation in the set point by setting the
X
X
ON
ON
alarm value (X). The alarm is ON when the PV is lower than
OFF
PV
OFF
PV
SP
SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*3
OFF
PV
lower limit (L). The alarm is ON when the PV is inside this deSP
viation range.
Upper- and lower-limit
with standby sequence *1 *5
Upper-limit with standby
sequence
ON
OFF
7
Lower-limit with standby
sequence
ON
OFF
8
Absolute-value upper-limit
ON
OFF
9
Absolute-value lower-limit
ON
OFF
10
Absolute-value upper-limit with standby sequence
ON
OFF
11
Absolute-value lower-limit
with standby sequence
ON
OFF
12
13
LBA (alarm 1 type only)
PV change rate alarm
14
SP absolute-value
upper-limit alarm
ON
OFF
15
SP absolute-value
lower-limit alarm
ON
OFF
5
6
L
H
X
ON
OFF
SP
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
X
SP
X
0
X
0
X
0
X
0
ON
OFF
MV absolute-value
upper-limit alarm *9
X
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X
SP
X
0
PV
X
0
PV
The alarm will turn ON if the process value is smaller than the
alarm value (X) regardless of the set point.
PV
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
PV
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X
0
X
0
0
ON
OFF
SP
ON
OFF
X
0
X
0
SP
This alarm type turns ON the alarm when the set point (SP)
is higher than the alarm value (X).
SP
This alarm type turns ON the alarm when the set point (SP)
is lower than the alarm value (X).
X
0
Standard Control
X
MV
0
The alarm will turn ON if the process value is larger than the
alarm value (X) regardless of the set point.
*7
*8
SP
ON
OFF
X
0
MV
X
MV
0
Standard Control
ON
OFF
17
SP
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
ON
OFF
MV absolute-value
lower-limit alarm *9
X
-
Standard Control
16
A standby sequence is added to the upper- and lower-limit
alarm (1). *6
*4
PV
SP
Standard Control
X
MV
0
Always ON
ON
OFF
X
0
MV
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
ON
OFF
X
0
MV
Always ON
55
E5DC
*1 With set values 1, 4, and 5, the upper- and lower-limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
*2 Set value: 1, Upper- and lower-limit alarm
Case 3 (Always OFF)
Case 2
Case 1
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
H
SP L H
H>0, L<0
|H| > |L|
H
SP
L
H<0, L>0
|H| ≥ |L|
L SP
SP H
L
H>0, L<0
|H| ≤ |L|
*3 Set value: 4, Upper- and lower-limit range
Case 3 (Always ON)
Case 2
Case 1
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
SP L
H
H
H>0, L<0
|H| > |L|
H
SP
L
L SP
SP H L
56
H<0, L>0
|H| ≥ |L|
H>0, L<0
|H| ≤ |L|
*4 Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above at *2
• In cases 1 and 2 above, the alarm is always OFF if the upperand lower-limit hysteresis overlaps.
• In case 3, the alarm is always OFF.
*5 Set value: 5, Upper- and lower-limit alarm with standby sequence
The alarm is always OFF if upper- and lower-limit hysteresis
overlaps.
*6 Refer to the E5@C Digital Temperature Controllers User’s Manual
(Cat. No. H174) for information on the operation of the standby
sequence.
*7 Refer to the E5@C Digital Temperature Controllers User’s Manual
(Cat. No. H174) for information on the LBA.
*8 Refer to the E5@C Digital Temperature Controllers User’s Manual
(Cat. No. H174) for information on the PV change rate alarm.
*9 When heating/cooling control is performed, the MV absolutevalue upper-limit alarm functions only for the heating operation
and the MV absolute-value lower-limit alarm functions only for the
cooling operation.
E5DC
Characteristics
Thermocouple:
(±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max.*1
Indication accuracy
Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is greater) ±1 digit max.
(when mounted individually, ambiAnalog input:
±0.2% FS ±1 digit max.
ent temperature of 23°C)
CT input:
±5% FS ±1 digit max.
Influence of temperature *2
Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2
Analog input: ±1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
R, S, B, W, or PLII thermocouple: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Installation influence (E5DC only)
Other thermocouple: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Input sampling period
50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0% to 100.0% (in units of 0.1%)
Alarm setting range
−1,999 to 9,999 (decimal point position depends on input type)
Influence of signal source resisThermocouple: 0.1°C/Ω max. (100 Ω max.), Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
tance
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions
Vibration
Resistance
10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions
Malfunction
100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance
300 m/s2, 3 times each in X, Y, and Z directions
Weight
Controller: Approx. 120 g
Degree of protection
Main unit: IP20, Terminal unit: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.6 or higher
E5DC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer. *5
Setup Tool port
E5DC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are
used together to connect a USB port on the computer.*5
Approved standards
UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2 , overvoltage category II
EMI:
EN61326
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage:
EN55011 Group 1, class A
EMS:
EN61326
ESD Immunity:
EN61000-4-2
EMC
Electromagnetic Field Immunity:
EN61000-4-3
Burst Noise Immunity:
EN61000-4-4
Conducted Disturbance Immunity:
EN61000-4-6
Surge Immunity:
EN61000-4-5
Voltage Dip/Interrupting Immunity:
EN61000-4-11
*1 The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C max., and U
and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B thermocouples at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max.
The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W
thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*3 K thermocouple at −100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
57
E5DC
USB-Serial Conversion Cable
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.6 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0
DTE speed
38,400 bps
Connector
specifications
Computer: USB (Type A plug)
Digital Temperature Controller: Special serial connector
Power supply
Bus power (Supplied from the USB host controller) *
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.)
Ambient operating
temperature
0 to 55°C (with no condensation or icing)
Ambient operating
humidity
10% to 80%
Dielectric strength
1,000 VAC for 1 min
Storage temperature
−20 to 60°C (with no condensation or icing)
Vibration resistance
50 Hz, 98 m/s2
Storage humidity
10% to 80%
Weight
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Altitude
2,000 m max.
Weight
Approx. 120 g
Accessories (E54-CT3 only)
Armatures (2)
Plugs (2)
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation
procedure.
Communications Specifications
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
KEYENCE is a registered trademark of Keyence Corporation.
*1 A Temperature Controller with version 2.1 or higher is required for
the FX Series or the KV Series.
*2 Both the programless communications and the component
communications support the copying.
Current Transformer (Order Separately)
Ratings
Heater Burnout Alarms and SSR Failure
Alarms
CT input (for heater current
detection)
Models with detection for single-phase heaters: One input
Maximum heater current
50 A AC
Input current
indication accuracy
±5% FS ±1 digit max.
Transmission line connection
method
RS-485: Multidrop
Heater burnout alarm
setting range *1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms *3
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
SSR failure alarm setting
range *2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms *4
Protocol
CompoWay/F, or Modbus
Baud rate*
9,600, 19,200, 38,400, or 57,600 bps
Transmission code
ASCII
Data bit length *
7 or 8 bits
Stop bit length *
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC)
with CompoWay/F or
CRC-16 with Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer
217 bytes
Communications response
wait time
0 to 99 ms
Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Communications Functions
You can use the memory in the PLC to read and write E5@C
parameters, start and stop operation, etc.
The E5@C automatically performs communications with
PLCs. No communications programming is required.
Number of connected Digital Temperature Controllers: 32
Programless max. (Up to 16 for the FX Series)
communica- Applicable PLCs: OMRON PLCs
tions *1
CS Series, CJ Series, or CP Series
Mitsubishi Electric PLCs
MELSEC Q Series, L Series, or FX Series (compatible with the FX2 or FX3 (excluding the FX1S))
KEYENCE PLCs
KEYENCE KV Series
58
When Digital Temperature Controllers are connected, the parameters can be copied from the Digital Temperature Controller that is set as the master to the Digital Temperature
Controllers that are set as slaves.
Copying*2
*1
*2
*3
*4
For heater burnout alarms, the heater current will be measured when the
control output is ON, and the output will turn ON if the heater current is
lower than the set value (i.e., heater burnout detection current value).
For SSR failure alarms, the heater current will be measured when the
control output is OFF, and the output will turn ON if the heater current is
higher than the set value (i.e., SSR failure detection current value).
The value is 30 ms for a control period of 0.1 s or 0.2 s.
The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for
Control Output Relay (Reference Values)
Life (× 104 operations)
*
When Digital Temperature Controllers are connected, set
points and RUN/STOP commands can be sent from the DigiComponent tal Temperature Controller that is set as the master to the DigCommunica- ital Temperature Controllers that are set as slaves.
tions*1
Slope and offsets can be set for the set point.
Number of connected Digital Temperature Controllers: 32
max. (including master)
Applicable OS
500
300
100
50
30
10
5
E5DC
250 VAC, 30 VDC
(resistive load)
cosφ = 1
3
1
0
1
2
3
4
5
6
Switching current (A)
E5DC
External Connections
E5DC
Control output
Auxiliary outputs 1, 2
Relay output
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
The E5DC is set for a K-type thermocouple (input type = 5) by default.
An input error (s.err) will occur if the input type setting does not agree
with the temperature sensor. Check the input type.
Relay outputs
250 VAC: 2 A (resistive load)
SM
E5DC
Control output
24 VAC/DC
100 to 240 VAC
RX
5
6
2
2
(no polarity)
1
5
9
2
6
10
Options
002
Communications and 1 CT
B(+)
RS-485
A(-)
3
4
A(-)
5
6
R
+Q
-
1 linear
current output
5
6
+ C
-
Auxiliary Outputs
9
10
11
11
CT1
Auxiliary output 2
Auxiliary output 1
8
Sensor (Temperature/Analog) Input
3
7
4
8
016
One event input
-
3
7
+
4
8
EV1
CX
1 voltage output
(for driving SSR)
7
015
Communications
B(+)
RS-485
QX
1 relay
output
1
1
Options
Control Output
Input Power Supply
12
3
7
13
4
8
14
TC
12
-
13
+ 14
A
B
B
Pt
12
13
14
I
+ 12
mA
13
14
V
12
V
- 13
14
+
Do not connect anything to the terminals
that are shaded gray.
017
One event input and one CT
-
3
+
4
EV1
7
CT1
8
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30m,
compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams
Sensor input and CT input
Communications and event input
Power
supply
Voltage output (for driving SSR) and linear current output
Relay output
Auxiliary outputs 1 and 2
: Reinforced insulation
: Functional isolation
Note: Auxiliary outputs 1 to 2 are not insulated.
59
E5DC
Nomenclature
E5DC
Front panel
Bottom View of E5DC
No. 1 display
PV or specified parameter
Operation indicators
No.2 display
SP or specified parameter value
Press O Key once to go to
Adjustment Level.
Use the M Key to change to another
parameter.
Press O Key for at least 3
seconds to go to Initial
Setting Level.
Use the U D Keys to
set the parameter.
Use S Key to change the digit (default setting).
Bottompanel Setup
Tool port
Front-panel Setup Tool port
Dimensions
(Unit: mm)
Controllers
E5DC
(85)
81
4
22.5
22.5
96
35 110
91
4
Mounting Adapter
(Accessory: Sold separately)
The Setup Tool ports are on the front and bottom of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Digital
Temperature Controller.
Mounted Separately
Two-Unit Mounting
92 +0.8
0
Group Mounted
(22.5 × number of units) +1.0
22.7 +0.3
0
0
45 +0.6
0
92 +0.8
0
92 +0.8
0
120 min
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.)
• When two or more Digital Temperature Controllers are mounted, make sure that the surrounding temperature does
not exceed the allowable operating temperature specified in the specifications.
60
E5DC
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2
(2110)
250
263
1510
LED (RD)
USB connector
(type A plug)
Serial connector
LED (PWR)
LED (SD)
● Conversion Cable
E58-CIFQ2-E
Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510)
250
263
1510
E58-CIFQ2 (Order separately)
Note: Always use this product together with the E58-CIFQ2.
Conversion Cable
● Current Transformers
E54-CT1
21
15
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
E54-CT1
2.8
5.8 dia.
7.5
3
Output voltage (Eo) V (r.m.s.)
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings:
400±2
Winding resistance:
18±2 Ω
10.5
40
Two, 3.5 dia.
10
30
100V
Frequency: 50 Hz
∞
1kΩ
10
Distortion
factor
10%
1
3%
1%
100mV
100Ω
10
E54-CT3
2.36 dia.
30
RL=10Ω
1
12 dia.
9
100μV
10
1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Two , M3 holes (depth: 4)
30
Connection Example
Armature
Plug
Approx. 3 dia.
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum
continuous heater current for an OMRON Digital Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
15
E54-CT3 Accessories
• Armature
Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
E54-CT3
100V
Frequency: 50 Hz
Distortion
factor
10%
3%
1%
∞
1kΩ
500Ω
10
1
100mV
100Ω
50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV
(22)
10
1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
61
E5DC
● Mounting Adapters
Y92F-53 (Two included.)
● Short Bars
Y92S-P11 (Four included.)
This accessory is not included with the
product. Order it separately to mount
the product to a panel.
Use this product to connect between terminals (for power supplies,
communications, etc.) when you use multiple E5DC Controllers.
27.5
34.7
2.4
22.5
12
24.8
11.8 9.4
0.8
3
5
● DIN Tracks
PFP-100N
PFP-50N
● End Plate
PFP-M
10
6.2
M4×8
pan head
screw
1.8
1
50
35.5 35.3
1.8
11.5
10
M4 spring washer
7.3±0.15
1.3
4.8
4.5
35±0.3
15
25
10
25
25
1000 (500)*
*
10
25
15 (5)*
1
Dimensions in parentheses are for the PFP-50N.
● Unit Labels
Y92S-L2
● Spacer
PFP-S
16
12
5
The Unit Labels for the Digital Panel
Meter are used. Use either the °C or °F
label from the sheet.
34.8
44.3
16.5
● End Cover
Y92F-54 (Two included.)
3.9
96
62
27±0.15
68
5.3
Use the End Cover when you mount the E5DC to a
panel to hide the gap between the Controller and the
panel.
MEMO
63
Programmable Temperature Controller (Digital Controller)
E5CC-T
(48 × 48 mm)
Programmable Controllers Join the E5†C Series!
Program up to 256 segments can handle a wide
variety of applications.
• Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each
• The white PV display with a height of 15.2 mm improves visibility.
• High-speed sampling at 50 ms.
• Models are available with up to 3 auxiliary outputs, up to 4 event
inputs, and a transfer output to cover a wide range of applications.
• Short body with depth of only 60 mm.
• Set up the Controller without wiring the power supply by connecting to
the computer with a Communications Conversion Cable (sold
separately). Setup is easy with the CX-Thermo (sold separately).
• Easy connections to a PLC with programless communications. Use
component communications to link Temperature Controllers to each
other.
48 × 48 mm
E5CC-T
Refer to your OMRON website for the most recent
information on applicable safety standards.
Refer to Safety Precautions on page 104.
Main I/O Functions
Sensor Input
Universal input
• Thermocouple
• Pt
• Analog current/voltage
E5CC-T
Dual displays: PV/SV
Control Output 1
• Relay output
• Voltage output (for driving
SSR)
• Linear current output
Indication Accuracy
• Thermocouple input: ±0.3%
of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% of FS
Control Output 2
• None
• Voltage output (for driving
SSR)
Sampling Period
• 50 ms
Event Inputs
• None
•2
•4
Serial Communications
• None
• RS-485
4-digit displays
• PF (shift) Key
• Temperature status display
• Operating and editing the program
• Independent heating and cooling
PID control
• Parameter mask setting
• Display brightness setting
Auxiliary Outputs
•3
Transfer Output
• None
•1
This datasheet is provided as a guideline for selecting products.
Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C-T Digital Temperature Controllers Programmable Type User’s Manual (Cat. No. H185)
E5@C-T Digital Temperature Controllers Programmable Type Communications Manual (Cat. No. H186)
64
E5CC-T
Model Number Legend and Standard Models
Model Number Legend
●Models with Screw Terminals
E5CC-T @@3 @5 M -@@@ (Example: E5CC-TRX3A5M-000)
−−−−−− −−−
A BC D E
F
A
Model
Control outputs
1 and 2
B
C
D
No. of Power
Terminal
auxiliary supply
type
outputs voltage
E
F
Input
type
Options
E5CC-T
RX
QX
*1 CX
QQ
CQ
3
A
D
5
M
*1
000
001
*1
003
*3
004
005
006
Meaning
48 × 48 mm Programmable Type
Control output 1
Control output 2
Relay output
None
Voltage output
None
(for driving SSR)
Linear current output *2
None
Voltage output
Voltage output
(for driving SSR)
(for driving SSR)
Voltage output
Linear current output *2
(for driving SSR)
3 (one common)
100 to 240 VAC
24 VAC/DC
Screw terminals (with cover)
Universal input
HB alarm
CommunicaEvent
Transfer
and HS
tions
inputs
output
alarm
--------1
--2
--2 (for 3-phase
RS-485
----heaters)
--RS-485
2
------4
------2
Provided.
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The linear current output cannot be used as a transfer output.
*3. Option 004 can be selected only when “CX” is selected for the control outputs.
Heating and Cooling Control
● Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
65
E5CC-T
Optional Products (Order Separately)
USB-Serial Conversion Cable
Model
E58-CIFQ2
Front Covers
Type
Hard Front Cover
Soft Front Cover
Model
Y92A-48H
Y92A-48D
Terminal Covers
CX-Thermo Support Software
Model
E53-COV17
E53-COV23 (3pcs)
Model
EST2-2C-MV4
Note: The Terminal Covers E53-COV23 are provided with the Digital
Temperature Controller. The E53-COV10 cannot be used.
Refer to page 75 for the mounted dimensions.
Waterproof Packing
Model
Y92S-P8
Note: The Waterproof Packing is provided with the Digital
Temperature Controller.
Current Transformers (CTs)
Hole diameter
5.8 mm
12.0 mm
Model
E54-CT1
E54-CT3
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
Waterproof Cover
Model
Y92A-48N
Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
DIN Track Mounting Adapter
Model
Y92F-52
66
Note: CX-Thermo version 4.61 or higher is required for the E5CC-T.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
E5CC-T
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Control
output
Auxiliary
output
Voltage output
(for driving SSR)
Linear current output
Number of outputs
Output specifications
Number of inputs
Event input External contact input
specifications
Transfer
output
Number of outputs
Output specifications
Setting method
Indication method
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
7.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB/THB.)
2-PID control (with auto-tuning) or ON/OFF control
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA (reference value)
Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
3
SPST-NO relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000
operations, Minimum applicable load: 10 mA at 5 V (reference value)
2 or 4 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
1 (only on models with a transfer output)
Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000
Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: PV: 15.2 mm, SV: 7.1 mm
None
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB)
alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust
tuning, PV input shift, protection functions, extraction of square root, MV change rate limit, logic
operations, temperature status display, moving average of input value, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting
(with no condensation or icing)
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
67
E5CC-T
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor
type
Platinum resistance
thermometer
Sensor
specification
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to
70°C
60 to
120°C
115 to
165°C
120
165
140 to
260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600
1500
1400
1300
1300
1300
1300
1200
1100
1000
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
90
100
0
0.0
-100
-200
100.0
-200
-199.9
0
1
Set value
0.0
199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100
-200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input
Input type
Input
specification
Setting range
Set value
68
Current
4 to 20 mA 0 to 20 mA
Voltage
1 to 5 V
0 to 5 V
Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
25
26
27
28
0 to 10 V
29
E5CC-T
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Set
value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2
Upper-limit
(default)
3
Lower-limit
4
Upper- and lower-limit
range *1
Alarm output operation
Description of function
When alarm value X When alarm value X
is positive
is negative
Output OFF
No alarm
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*2
OFF
PV
lower limit (L). The alarm is ON when the PV is outside this
SP
deviation range.
Set the upward deviation in the set point by setting the alarm
X
X
ON
ON
value (X). The alarm is ON when the PV is higher than the
OFF
PV
OFF
PV
SP
SP
SP by the deviation or more.
Set the downward deviation in the set point by setting the
X
X
ON
ON
alarm value (X). The alarm is ON when the PV is lower than
OFF
PV
OFF
PV
SP
SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*3
OFF
PV
lower limit (L). The alarm is ON when the PV is inside this deSP
viation range.
Upper- and lower-limit
with standby sequence *1 *5
Upper-limit with standby
sequence
ON
OFF
7
Lower-limit with standby
sequence
ON
OFF
8
Absolute-value upper-limit
ON
OFF
9
Absolute-value lower-limit
ON
OFF
10
Absolute-value upper-limit with standby sequence
ON
OFF
11
Absolute-value lower-limit
with standby sequence
ON
OFF
12
13
LBA (alarm 1 type only)
PV change rate alarm
14
SP absolute-value
upper-limit alarm
ON
OFF
15
SP absolute-value
lower-limit alarm
ON
OFF
5
6
L
H
X
ON
OFF
SP
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
X
SP
X
0
X
0
X
0
X
0
ON
OFF
MV absolute-value
upper-limit alarm *9
X
0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X
SP
X
0
PV
X
0
PV
X
0
PV
X
0
PV
ON
OFF
SP
ON
OFF
X
0
The alarm will turn ON if the process value is smaller than the
alarm value (X) regardless of the set point.
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X
0
SP
X
0
SP
This alarm type turns ON the alarm when the set point (SP)
is higher than the alarm value (X).
This alarm type turns ON the alarm when the set point (SP)
is lower than the alarm value (X).
Standard Control
X
MV
0
The alarm will turn ON if the process value is larger than the
alarm value (X) regardless of the set point.
*7
*8
SP
ON
OFF
X
0
MV
X
MV
0
Standard Control
ON
OFF
17
SP
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
ON
OFF
MV absolute-value
lower-limit alarm *9
X
-
Standard Control
16
A standby sequence is added to the upper- and lower-limit
alarm (1). *6
*4
PV
SP
X
MV
0
Always ON
Standard Control
ON
OFF
X
0
MV
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
ON
OFF
X
0
MV
Always ON
69
E5CC-T
*1
*2
With set values 1, 4 and 5, the upper and lower limit values can be set
independently for each alarm type, and are expressed as “L” and “H.”
Set value: 1, Upper- and lower-limit alarm
Case 2
Case 1
Case 3 (Always ON)
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
H
SP L H
H>0, L<0
|H| > |L|
SP
L
H<0, L>0
|H| ≥ |L|
L SP
H
SP H
*3
L
Set value: 4, Upper- and lower-limit range
Case 1
L
Case 3 (Always OFF)
Case 2
H SP
H<0, L>0
|H| < |L|
SP L
H
H
H>0, L<0
|H| > |L|
H
SP
L
L SP
SP H L
70
H>0, L<0
|H| ≤ |L|
H<0, L<0
H<0, L>0
|H| ≥ |L|
H>0, L<0
|H| ≤ |L|
*4
Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above *2
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
• Case 3: Always OFF
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
*6 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
User's Manual (Cat. No. H185) for information on the operation of the
standby sequence.
*7 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
User's Manual (Cat. No. H185) for information on the loop burnout alarm
(LBA).
*8 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
User's Manual (Cat. No. H185) for information on the PV change rate
alarm.
*9 When heating/cooling control is performed, the MV absolute upper limit
alarm functions only for the heating operation and the MV absolute lower
limit alarm functions only for the cooling operation.
E5CC-T
Characteristics
Thermocouple:
(±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
CT input:
±5% FS ±1 digit max.
Transfer output accuracy
±0.3% FS max.
Influence of temperature *2
Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2
Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Input sampling period
50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
-1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Influence of signal source resistance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance
10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction
100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance
300 m/s2, 3 times each in X, Y, and Z directions
Weight
Controller: Approx. 120 g, Adapter: Approx. 10 g
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.61 or higher
E5CC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on
Setup Tool port
the computer. *5
Approved standards
UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards
EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II
EMI:
EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326
ESD Immunity:
EN 61000-4-2
EMC
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
Indication accuracy
(at the ambient temperature of 23°C)
*1 The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L
thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not
specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever
is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*3 K thermocouple at −100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
71
E5CC-T
Program Control
Number of programs (patterns)
Number of segments (steps)
Segment setting method
Segment times
Alarm setting
Reset operation
Startup operation
PID sets
Number of sets
Setting method
Alarm SP function
Program status control
Wait operation
Time signals
Segment operation
Program operation
Wait method
Wait width setting
Number of outputs
Number of ON/OFF
Operations
Setting method
Program status output
PV start
Program startup operation
Operation end operation
Program SP shift
72
Standby
8
32
Time setting (Segment set with set point and time.)
Slope setting (Segment set with segment type, set point, slope, and time.)
0 h 0 min to 99 h 59 min
0 min 0 s to 99 min 59 s
Set separately for each program.
Select either stopping control or fixed SP operation.
Select continuing, resetting, manual operation, or run mode.
8
Set separately for each program (automatic PID group selection also supported).
Select from ramp SP and target SP.
Advance, segment jump, hold, and wait
Program repetitions and program links
Waiting at segment ends
Same wait width setting for all programs
2
1 each per output
Set separately for each program.
Program end output (pulse width can be set), run output, stage output
Select from segment 1 set point, slope-priority PV start
0 h 0 min to 99 h 59 min
0 day 0 h to 99 day 23h
Select from resetting, continuing control at final set point, and fixed SP control.
Same program SP shift for all programs
E5CC-T
USB-Serial Conversion Cable
Applicable OS
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.61 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38400 bps
Connector
specifications
Computer: USB (type A plug)
Digital Temperature Controller:
Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Output current
250 mA max.
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Component
Communications
When Digital Temperature Controllers are connected, set points and RUN/STOP commands
can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
Slope and offsets can be set for the set point.
Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*1
When Digital Temperature Controllers are connected, the parameters can be copied from the
Digital Temperature Controller that is set as the
master to the Digital Temperature Controllers that
are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
*1 Both the programless communications and the component
communications support the copying.
Current Transformer (Order Separately)
Ratings
Ambient operating
temperature
0 to 55°C (with no condensation or icing)
Dielectric strength
Vibration resistance
Ambient operating
humidity
10% to 80%
Weight
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Communications Specifications
Transmission line
connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization
method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Communications Functions
Programless
communications*1
You can use the memory in the PLC to read and
write E5@C-T parameters, start and reset operation, etc. The E5@C-T automatically performs
communications with PLCs. No communications
programming is required.
Number of connected Digital Temperature Controllers: 32 max.
Applicable PLCs
OMRON PLCs
CS Series, CJ Series, or
CP Series
Mitsubishi Electric PLCs
MELSEC Q Series, L Series
Heater Burnout Alarms and SSR Failure
Alarms
CT input (for heater
current detection)
Maximum heater
current
Input current
indication accuracy
Heater burnout
alarm setting range
*1
SSR failure alarm
setting range *2
Models with detection for single-phase
heaters: One input
Models with detection for singlephase or
three-phase heaters: Two inputs
50 A AC
±5% FS ±1 digit max.
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms *3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms *4
*1 For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output will turn ON if the
heater current is lower than the set value (i.e., heater burnout
detection current value).
*2 For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output will turn ON if the heater
current is higher than the set value (i.e., SSR failure detection
current value).
*3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
*4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for
Relays (Reference Values)
Life (× 104 operations)
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
* Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation
procedure.
Accessories
(E54-CT3 only)
1,000 VAC for 1 min
50 Hz, 98 m/s2
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Armatures (2)
Plugs (2)
500
300
100
50
30
10
5
E5CC-T
250 VAC, 30 VDC
(resistive load)
cosφ = 1
3
1
0
1
2
3
4
5
6
Switching current (A)
73
E5CC-T
External Connections
E5CC-T
Control output 1
Relay output
250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
(1)
R
Auxiliary outputs
Control output 2
12 VDC, 21 mA
CX
OUT1
1
2
3
QQ
+Q
−
1
2
3
CQ
Models with 2
Voltage Outputs
(for Driving SSR)
Models with 1
Linear Current
Output
OUT1
+ C
−
1
2
3
A
B
B
Pt
4
5
6
(6) Options
001
Event inputs 1 and 2,
and CT1
−
13
+
EV1
+
EV2
CT1
14
+
mA
−
I
4
5
6
OUT1
V
4
− 5
V
6
+
+ C
- OUT2
+ Q
Auxiliary outputs 1, 2, and 3
1
13
7
2
14
3
8
9
4
15
16
10
5
17
11
6
18
12
7
Auxiliary output 3
8
Auxiliary output 2
9
Auxiliary output 1
10
(3) Input Power Supply
100 to 240 VAC
005
006
Communications (RS-485)
and event inputs 3 and 4
Event inputs 1 to 4
Event inputs 1 and 2, and
transfer output
B(+)
A(−)
B(+)
13
RS-485
14
A(−)
15
16
CT1
COM
CT2
−
17
18
+
EV3
EV4
+
13
−
+
14
15
+
16
−
17
18
EV1
EV2
+
EV3
+ EV4
Isolation/Insulation Block Diagrams
Models with 3 Auxiliary Outputs
Sensor input and CT inputs
Communications and event inputs
Voltage output (for driving SSR),
linear current output, and transfer output
Relay output
Auxiliary outputs 1, 2, 3
: Reinforced insulation
: Functional isolation
Note: Auxiliary outputs 1 to 3 are not insulated.
74
12
(no polarity)
13
14
−
15
+
+
EV1
EV2
13
14
15
16
16
17
17
18
18
+
+V
I
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
Power
supply
11
12
004
RS-485
24 VAC/DC
11
Communications
(RS-485), CT1, and CT2
16
18
(2) Auxiliary Outputs
OUT1
1
2
3
003
15
17
Models with 2 Outputs:
Linear Current Output
and Voltage (for Driving SSR)
+Q
− OUT2
+Q
(5) Sensor (Temperature/Analog) Input
TC
4
− 5
+ 6
(6)
The E5CC-T is set for a K-type thermocouple (input
type = 5) by default. An input error (s.err) will occur
if the input type setting does not agree with the
temperature sensor. Check the input type.
Relay output
Models with 3 auxiliary outputs:
250 VAC: 2 A
(resistive load)
Voltage output
(for driving SSR)
Models with 1
Voltage Output
(for Driving SSR)
OUT1
1
2
3
5M
(2) (3) (4) (5)
Terminal type
(1) Control outputs 1, 2
RX
QX
Models with
1 Relay
Output
3
E5CC T
Transfer output
−
E5CC-T
Nomenclature
E5CC-T
Front panel
Temperature unit
Operation indicators
No. 1 display
PV or specified monitor/setting parameter
Top View of E5CC-T
No. 2 display
Press O Key once to go to
Program Setting Level.
SP or specified monitor/parameter value
Top-panel Setup Tool port
Press O Key for at least 3
seconds to go to Initial Setting
Level.
Use the UD Keys to set the
parameter.
Press U Key for at least 1 second
when Process value/Set point
parameter are displayed in Program
SP Mode to go to Display Segment
Selection parameter in Program
Setting Level.
Use the M Key to change to another parameter.
Press M and D Keys simultaneously for at
least 1 second to switch between run and reset
status.
Use S Key to change the digit (default setting).
Dimensions
(Unit: mm)
Controllers
E5CC-T
48 × 48
4
1
Panel Cutout
Mounted Separately
Group Mounted
(64)
60
(48 × number of units - 2.5)+1.0
0
48 × 48
58
45+0.6
0
Group mounting does not
allow waterproofing.
60 min.
45+0.6
0
Waterproof Packing
(Accessory)
Mounting Adapter
(Accessory)
45+0.6
0
• Recommended panel thickness is 1 to 5 mm.
The Setup Tool port is on the top of the Temperature Controller.
It is used to connect the Temperature Controller to the computer • Group mounting is not possible in the vertical direction. (Maintain
the specified mounting space between Controllers.)
to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to
• To mount the Controller so that it is waterproof, insert the
make the connection.
waterproof packing onto the Controller.
Refer to the instructions that are provided with the USB-Serial
• When two or more Controllers are mounted, make sure that the
Conversion Cable for the connection procedure.
surrounding temperature does not exceed the allowable operating
Note: Do not leave the USB-Serial Conversion Cable
temperature specified in the specifications.
connected when you use the Temperature Controller. • Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a
USB-Serial Conversion Cable are used together.
75
E5CC-T
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2
(2110)
250
263
1510
LED (RD)
USB connector
(type A plug)
Serial connector
LED (PWR)
LED (SD)
● Terminal Covers
E53-COV17
48
● Terminal Covers
E53-COV23 (Three Covers provided.)
2
3.8
48.8
10
Terminal Cover
(E53-COV23)
22
44.8
9.1
● Waterproof Packing
Y92S-P8 (for DIN 48 × 48)
76
The Waterproof Packing is provided with the Temperature Controller.
Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
E5CC-T
● Current Transformers
E54-CT1
21
15
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT1
2.8
5.8 dia.
7.5
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings:
400±2
Winding resistance:
18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5
40
Two, 3.5 dia.
10
30
100V
Frequency: 50 Hz
∞
1kΩ
10
Distortion
factor
10%
1
3%
1%
100mV
100Ω
10
E54-CT3
2.36 dia.
30
RL=10Ω
1
12 dia.
9
100μV
10
1
40 × 40
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT3
Two, M3 (depth: 4)
15
E54-CT3 Accessories
• Armature
Approx. 3 dia.
Connection Example
Plug
Armature
Lead
18
• Plug
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Digital Temperature Controller is 50 A.)
Number of windings:
400±2
Winding resistance:
8±0.8 Ω
30
100V
Frequency: 50 Hz
Distortion
factor
10%
3%
1%
∞
1kΩ
500Ω
10
1
100mV
100Ω
50Ω
10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
77
E5CC-T
● Adapter
Y92F-45
Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial
Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
Fixture (Accessory)
76
4.7
69.6 to 77.6
72 × 72
67 × 67 87
Mounted to E5CC-T
Panel (1 to 8 mm)
72 × 72
Mounting Adapter
Y92F-30
(Accessory)
48 × 48
2.2
4.7
62.8
To back of the E5CC-T
● DIN Track Mounting Adapter
Y92F-52
Note: This Adapter cannot be used together with the Terminal Cover.
Remove the Terminal Cover to use the Adapter.
61
3.5
38
50
Mounted to E5CC-T
48
80.5
78
This Adapter is used to mount the
E5CC-T to a DIN Track.
If you use the Adapter, there is no
need for a plate to mount in the
panel or to drill mounting holes in
the panel.
E5CC-T
● Watertight Cover
● Mounting Adapter
Y92A-48N
Y92F-49
21.9
14
The Mounting Adapter is provided with the
Temperature Controller.
Order this Adapter separately if it becomes
lost or damaged.
(2)
87.7
69
79.2
12
67.6
● Protective Cover
● Protective Cover
Y92A-48D
Y92A-48H
Note: This Protective Cover cannot be used
if the Waterproof Packing is installed.
This Protective Cover is soft type.
It is able to operate the controller with using
this cover.
This Protective Cover is hard type.
Please use it for the mis-operation
prevention etc.
79
Programmable Temperature Controller (Digital Controller)
E5EC-T/E5AC-T
(48 × 96 mm/96 × 96 mm)
Programmable Controllers Join the E5†C Series!
Program up to 256 segments can handle a
wide variety of applications.
• Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each
• A white LCD PV display with a height of approx. 18 mm for the E5ECT and 25 mm for the E5AC-T improves visibility.
• Tool ports are provided both on the top panel and the front panel. Set
up the Controller without wiring the power supply by connecting to the
computer with a Communications Conversion Cable (sold
separately). Setup is easy with the CX-Thermo (sold separately).
• High-speed sampling at 50 ms.
• Models are available with up to 4 auxiliary outputs, up to 6 event
inputs, and a transfer output to cover a wide range of applications.
• Short body with depth of only 60 mm.
• Easy connections to a PLC with programless communications. Use
component communications to link Temperature Controllers to each
other.
• The new position-proportional control models allow you to control
valves as well. (The position-proportional control models are
scheduled to be released in May, 2014.)
48 × 96 mm
E5EC-T
96 × 96 mm
E5AC-T
Refer to your OMRON website for the most recent
information on applicable safety standards.
Refer to Safety Precautions on page 104.
Main I/O Functions
Sensor Input
Universal input
• Thermocouple
• Pt
• Analog current/voltage
E5EC-T
E5AC-T
Three-level Display
Simultaneous display of the PV, SP,
Program No., Segment No., etc.
4-digit
displays
Indication Accuracy
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Linear current output
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% of FS
Sampling Period
• 50 ms
Event Inputs
• None
•2
•4
•6
Serial Communications
• None
• RS-485
• PF (shift) Key
• Setup Tool port on front panel
• Temperature status display
• Operating and editting the program
• Independent heating and
cooling PID control
• Parameter mask setting
• Display brightness setting
Control Output 2
• Voltage output (for driving SSR)
• Relay output
• Linear current output
Auxiliary Outputs
•4
Transfer Output
• None
•1
This datasheet is provided as a guideline for selecting products.
Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C-T Digital Temperature Controllers Programmable Type User’s Manual (Cat. No. H185)
E5@C-T Digital Temperature Controllers Programmable Type Communications Manual (Cat. No. H186)
80
E5EC-T/E5AC-T
Model Number Legend and Standard Models
Model Number Legend
●Models with Screw Terminals
E5EC-T@@ 4 @ 5 M -@@@ (Example: E5EC-TRX4A5M-000)
−−− − − − −−−
A BC D E
F
E5AC-T@@ 4 @ 5 M -@@@ (Example: E5AC-TRX4A5M-000)
−−−− − − −−−
A BC D E
F
A
Model
Control outputs
1 and 2
B
C
D
E
F
No. of auxil- Power
Terminal Input
Options
iary out- supply
type
type
puts
voltage
48 × 96 mm Programmable Type
96 × 96 mm Programmable Type
Control output 1
Control output 2
Relay output
None
Voltage output
None
(for driving SSR)
Linear current output
None
Voltage output
Voltage output
(for driving SSR)
(for driving SSR)
Voltage output
Relay output
(for driving SSR)
Relay output
Relay output
Linear current output
Linear current output
Voltage output
Linear current output
(for driving SSR)
Position-proportional relay out- Position-proportional reput
lay output
4 (auxiliary outputs 1 and 2 with same common and
auxiliary outputs 3 and 4 with same common)
100 to 240 VAC
24 VAC/DC
Screw terminals (with cover)
Universal input
E5EC-T
E5AC-T
RX
QX
*2 CX
QQ
QR
RR
*2 CC
*2 CQ
*3 PR
4
A
D
5
Control outputs 1 and 2
For RX,
For CX or
QX, QQ,
For PR
QR, RR, or CC
CQ
Selectable Selectable Selectable
Option
Selectable Selectable
selection
Selectable
conditions
*1
Selectable
Selectable
Selectable
Selectable
Selectable Selectable
Meaning
M
HB alarm and
HS alarm
000
004
005
008
010
019
021
022
------1
1
1
-----
Communications
--RS-485
--RS-485
------RS-485
Event
Transfer output
inputs
--2
4
2
4
6
6
4
----------Provided.
Provided.
Provided.
*1. The options that can be selected depend on the type of control output.
*2. The linear current output cannot be used as a transfer output.
*3. Models with Position-proportional Control are scheduled for release in May 2014.
Heating and Cooling Control
●Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
81
E5EC-T/E5AC-T
Optional Products (Order Separately)
USB-Serial Conversion Cable
Model
E58-CIFQ2
Communications Conversion Cable
Note: Always use this product together with the E58-CIFQ2.
This Cable is used to connect to the front-panel Setup Tool
port.
Terminal Covers
Model
E53-COV24 (3pcs)
Note: The Terminal Covers E53-COV24 are provided with the Digital
Temperature Controller.
Waterproof Packing
Model
Y92S-P9
Y92S-P10
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.
Waterproof Cover
Applicable Controller
E5EC-T
E5AC-T
Model
Y92A-49N
Y92A-96N
Front Port Cover
Model
Y92S-P7
Note: This Front Port Cover is provided with the Digital Temperature
Controller.
Mounting Adapter
Model
Y92F-51 (2pcs)
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
82
Hole diameter
5.8 mm
12.0 mm
Model
E54-CT1
E54-CT3
CX-Thermo Support Software
Model
E58-CIFQ2-E
Applicable Controller
E5EC-T
E5AC-T
Current Transformers (CTs)
Model
EST2-2C-MV4
Note: CX-Thermo version 4.61 or higher is required for the E5EC-T/
E5AC-T.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
E5EC-T/E5AC-T
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
E5EC-T 8.7 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Power consumption
E5AC-T 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method
2-PID control (with auto-tuning) or ON/OFF control
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA (reference value)
Control
Voltage output
Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
output
(for driving SSR)
(The maximum load current is 21 mA for models with two control outputs.)
Linear current output
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Number of outputs
4
Auxiliary
SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load),
output
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs
2, 4 or 6 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs
1 (only on models with a transfer output)
Transfer
Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000
output
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000
Potentiometer input
100 Ω to 10 kΩ
Setting method
Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: E5EC-T: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
E5AC-T: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Indication method
Three displays. Contents: PV, SP, program No. and segment No., remaining segment time, or MV
(valve opening)
Numbers of digits: 4 digits
Bank switching
None
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB)
alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tunOther functions
ing, PV input shift, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, moving average of input value, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting
Ambient operating temperature
(with no condensation or icing)
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
Altitude
2,000 m max.
Recommended fuse
T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment
Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
Power supply voltage
83
E5EC-T/E5AC-T
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor
type
Platinum resistance
thermometer
Sensor
specification
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PLII
10 to
70°C
60 to
120°C
115 to
165°C
120
165
140 to
260°C
2300
2300
1800
1800
1700
1700
1700
Temperature range (°C)
1600
1500
1400
1300
1300
1300
1300
1200
1100
1000
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
90
100
0
0.0
-100
-200
100.0
-200
-199.9
0
1
Set value
0.0
199.9
2
3
-20.0
-100
-20.0
6
7
8
-200
4
5
0
0
16
17
0
0
0
0
0
0
19
20
21
22
23
24
-100
-200
-199.9
-200
9
10
11
12
-200
-199.9
-200
13
14
15
18
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
●Analog input
Input type
Input
specification
Setting range
Set value
84
Current
4 to 20 mA 0 to 20 mA
Voltage
1 to 5 V
0 to 5 V
Usable in the following ranges by scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
25
26
27
28
0 to 10 V
29
E5EC-T/E5AC-T
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Set
value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
2
Upper-limit
(default)
3
Lower-limit
4
Upper- and lower-limit
range *1
5
6
Alarm output operation
Description of function
When alarm value X When alarm value X
is positive
is negative
Output OFF
No alarm
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*2
OFF
PV
lower limit (L). The alarm is ON when the PV is outside this
SP
deviation range.
Set the upward deviation in the set point by setting the alarm
X
X
ON
ON
value (X). The alarm is ON when the PV is higher than the
OFF
PV
OFF
PV
SP
SP
SP by the deviation or more.
Set the downward deviation in the set point by setting the
X
X
ON
ON
alarm value (X). The alarm is ON when the PV is lower than
OFF
PV
OFF
PV
SP
SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
limit (H) and the lower deviation in the set point for the alarm
ON
*3
OFF
PV
lower limit (L). The alarm is ON when the PV is inside this deSP
viation range.
Upper- and lower-limit
ON
with standby sequence *1 *5OFF
Upper-limit with standby
ON
OFF
sequence
7
Lower-limit with standby
sequence
ON
OFF
8
Absolute-value upper-limit
ON
OFF
9
Absolute-value lower-limit
ON
OFF
10
Absolute-value upper-limit with standby sequence
ON
OFF
11
Absolute-value lower-limit
with standby sequence
ON
OFF
12
13
LBA (alarm 1 type only)
PV change rate alarm
14
SP absolute-value
upper-limit alarm
ON
OFF
15
SP absolute-value
lower-limit alarm
ON
OFF
L
H
X
SP
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
PV
ON
OFF
X
0
X
0
X
0
X
0
ON
OFF
MV absolute-value
upper-limit alarm *9
X
0
PV
A standby sequence is added to the upper-limit alarm (2). *6
PV
A standby sequence is added to the lower-limit alarm (3). *6
X
SP
X
0
PV
X
0
PV
X
0
PV
X
0
PV
ON
OFF
SP
ON
OFF
X
0
The alarm will turn ON if the process value is smaller than the
alarm value (X) regardless of the set point.
A standby sequence is added to the absolute-value upperlimit alarm (8). *6
A standby sequence is added to the absolute-value lowerlimit alarm (9). *6
X
0
SP
X
0
SP
This alarm type turns ON the alarm when the set point (SP)
is higher than the alarm value (X).
This alarm type turns ON the alarm when the set point (SP)
is lower than the alarm value (X).
Standard Control
X
MV
0
The alarm will turn ON if the process value is larger than the
alarm value (X) regardless of the set point.
*7
*8
SP
ON
OFF
X
0
MV
X
MV
0
Standard Control
ON
OFF
17
SP
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
ON
OFF
MV absolute-value
lower-limit alarm *9
X
-
Standard Control
16
ON
OFF
PV
X
SP
A standby sequence is added to the upper- and lower-limit
alarm (1). *6
*4
PV
SP
X
MV
0
Always ON
Standard Control
ON
OFF
X
0
MV
This alarm type turns ON the alarm when the manipulated
Heating/Cooling
Heating/Cooling
variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
ON
OFF
X
0
MV
Always ON
85
E5EC-T/E5AC-T
*1
*2
With set values 1, 4 and 5, the upper and lower limit values can be set
independently for each alarm type, and are expressed as “L” and “H.”
Set value: 1, Upper- and lower-limit alarm
Case 2
Case 1
Case 3 (Always ON)
H<0, L<0
L
H SP
H<0, L>0
|H| < |L|
H
SP L H
H>0, L<0
|H| > |L|
SP
L
H<0, L>0
|H| ≥ |L|
L SP
H
SP H
*3
L
Set value: 4, Upper- and lower-limit range
Case 1
L
Case 3 (Always OFF)
Case 2
H SP
H<0, L>0
|H| < |L|
SP L
H
H
H>0, L<0
|H| > |L|
H
SP
L
L SP
SP H L
86
H>0, L<0
|H| ≤ |L|
H<0, L<0
H<0, L>0
|H| ≥ |L|
H>0, L<0
|H| ≤ |L|
*4
Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above *2
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
• Case 3: Always OFF
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
*6 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
User's Manual (Cat. No. H185) for information on the operation of the
standby sequence.
*7 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
User's Manual (Cat. No. H185) for information on the loop burnout alarm
(LBA). This setting cannot be used with a position-proportional model.
*8 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
User's Manual (Cat. No. H185) for information on the PV change rate
alarm.
*9 When heating/cooling control is performed, the MV absolute upper limit
alarm functions only for the heating operation and the MV absolute lower
limit alarm functions only for the cooling operation.
E5EC-T/E5AC-T
Characteristics
Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Transfer output accuracy
±0.3% FS max.
Thermocouple input (R, S, B, W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit
Influence of temperature *2
max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2
Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Input sampling period
50ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in
Integral time (I)
units of 0.1 s)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4
Derivative time (D)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
-1999 to 9999 (decimal point position depends on input type)
Influence of signal source resisThermocouple: 0.1°C/Ω max. (100 Ω max.)
tance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance
10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction
100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance
300 m/s2, 3 times each in X, Y, and Z directions
E5EC-T
Controller: Approx. 210 g, Adapter: Approx. 4 g × 2
Weight
E5AC-T
Controller: Approx. 250 g, Adapter: Approx. 4 g × 2
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.61 or higher
E5EC-T/E5AC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB
port on the computer.*5
Setup Tool port
E5EC-T/E5AC-T front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are used together to connect to a USB port on the computer.*5
Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II
EMI
EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326
ESD Immunity:
EN 61000-4-2
EMC
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
Indication accuracy
(at the ambient temperature of
23°C)
*1
*2
*3
*4
*5
The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at
any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples
at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The
indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
K thermocouple at -100°C max.: ±10°C max.
The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
87
E5EC-T/E5AC-T
Program Control
Number of programs (patterns)
Number of segments (steps)
Segment setting method
Segment times
Alarm setting
Reset operation
Startup operation
PID sets
Number of sets
Setting method
Alarm SP function
Program status control
Wait operation
Time signals
Segment operation
Program operation
Wait method
Wait width setting
Number of outputs
Number of ON/OFF
Operations
Setting method
Program status output
PV start
Program startup operation
Operation end operation
Program SP shift
88
Standby
8
32
Time setting (Segment set with set point and time.)
Slope setting (Segment set with segment type, set point, slope, and time.)
0 h 0 min to 99 h 59 min
0 min 0 s to 99 min 59 s
Set separately for each program.
Select either stopping control or fixed SP operation.
Select continuing, resetting, manual operation, or run mode.
8
Set separately for each program (automatic PID group selection also supported).
Select from ramp SP and target SP.
Advance, segment jump, hold, and wait
Program repetitions and program links
Waiting at segment ends
Same wait width setting for all programs
2
1 each per output
Set separately for each program.
Program end output (pulse width can be set), run output, stage output
Select from segment 1 set point, slope-priority PV start
0 h 0 min to 99 h 59 min
0 day 0 h to 99 day 23h
Select from resetting, continuing control at final set point, and fixed SP control.
Same program SP shift for all programs
E5EC-T/E5AC-T
USB-Serial Conversion Cable
Applicable OS
Windows XP, Vista, or 7
Applicable software
CX-Thermo version 4.61 or higher
Applicable models
E5@C-T Series, E5@C Series, and E5CB Series
USB interface standard
Conforms to USB Specification 2.0.
DTE speed
38400 bps
Connector
specifications
Computer: USB (type A plug)
Digital Temperature Controller:
Special serial connector
Power supply
Bus power (Supplied from USB host controller.)*
Power supply voltage
5 VDC
Current consumption
450 mA max.
Output voltage
4.7±0.2 VDC
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Output current
250 mA max.
(Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.)
Component
Communications
When Digital Temperature Controllers are connected, set points and RUN/STOP commands
can be sent from the Digital Temperature Controller that is set as the master to the Digital Temperature Controllers that are set as slaves.
Slope and offsets can be set for the set point.
Number of connected Digital Temperature Controllers: 32 max. (including master)
Copying*1
When Digital Temperature Controllers are connected, the parameters can be copied from the
Digital Temperature Controller that is set as the
master to the Digital Temperature Controllers that
are set as slaves.
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
*1 Both the programless communications and the component
communications support the copying.
Current Transformer (Order Separately)
Ratings
Ambient operating
temperature
0 to 55°C (with no condensation or icing)
Dielectric strength
Vibration resistance
Ambient operating
humidity
10% to 80%
Weight
Storage temperature
-20 to 60°C (with no condensation or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 120 g
Communications Specifications
Transmission line
connection method
RS-485: Multidrop
Communications
RS-485 (two-wire, half duplex)
Synchronization
method
Start-stop synchronization
Protocol
CompoWay/F, or Modbus
Baud rate*
9600, 19200, 38400, or 57600 bps
Transmission code
ASCII
Data bit length*
7 or 8 bits
Stop bit length*
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer 217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Communications Functions
Programless
communications*1
You can use the memory in the PLC to read and
write E5@C-T parameters, start and reset operation, etc. The E5@C-T automatically performs
communications with PLCs. No communications
programming is required.
Number of connected Digital Temperature Controllers: 32 max.
Applicable PLCs
OMRON PLCs
CS Series, CJ Series, or
CP Series
Mitsubishi Electric PLCs
MELSEC Q Series, L Series
Heater Burnout Alarms and SSR Failure
Alarms
CT input (for heater
current detection)
Maximum heater
current
Input current
indication accuracy
Heater burnout
alarm setting range
*1
SSR failure alarm
setting range *2
Models with detection for single-phase
heaters: One input
50 A AC
±5% FS ±1 digit max.
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms *3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms *4
*1 For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output will turn ON if the
heater current is lower than the set value (i.e., heater burnout
detection current value).
*2 For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output will turn ON if the heater
current is higher than the set value (i.e., SSR failure detection
current value).
*3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
*4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Electrical Life Expectancy Curve for
Relays (Reference Values)
Life (× 104 operations)
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
* Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation
procedure.
Accessories
(E54-CT3 only)
1,000 VAC for 1 min
50 Hz, 98 m/s2
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Armatures (2)
Plugs (2)
500
300
E5EC-T/E5AC-T
250 VAC, 30 VDC
(resistive load)
cosφ = 1
100
50
30
10
5
3
1
0
1
2
3
4
5
6
Switching current (A)
89
E5EC-T/E5AC-T
External Connections
E5EC-T/E5AC-T
4
E5EC T
(1)
5M
(2) (3) (4) (5)
4
E5AC T
(6)
(1)
5M
(2) (3) (4) (5)
Terminal type
(6)
Terminal type
Control output 1
Control output 2
Relay output
250 VAC, 5A (resistive load)
Voltage output (for driving SSR)
12 VDC, 40 mA
21 mA if there are two control outputs
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Auxiliary outputs
Relay output
250 VAC, 5 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
Load: 500 Ω max.
Relay output
Models with 4 auxiliary
outputs:
250 VAC, 2 A
(resistive load)
(6) Options
005
008
004
Communications
Four event inputs Communications, two
and two event inputs
event inputs, and one CT
B(+)
B(+)
−
13
13
13
RS-485
RS-485
+
14
14
14
EV3
A(-)
A(-)
+
15
15
15
EV4
−
−
16
16
16
−
+
+
+
17
17
17
EV1
EV1
EV1
+
+
+
18
18
18
EV2
EV2
EV2
19
19
19
CT1
20
20
20
21
21
21
(1)Control Outputs
RX
QX
Models with
Models with 1
1 Relay Output Voltage Output
(for Driving SSR)
OUT1
3
4
5
6
R
OUT1
+Q
−
3
4
5
6
CX
100 to 240 VAC
QR
QQ
Models with 1
Linear Current
Output
RR/PR
OUT2
+Q
−
OUT1
3
4
OUT2 5
R
6
R
2
1
2
3
4
5
6
7
8
9
10
11
12
+Q
−
OUT2
R
CQ
Models with 2
Linear Current Outputs
1
2
(no polarity)
OUT1
3
4
5
6
CC
Models with 2
Relay Outputs
3
4
5
6
OUT1
+Q
−
Models with 2 Output:
Linear Current Output
and Voltage (for Driving SSR)
OUT1
3
4
5
6
+ C
−
OUT2
+ C
−
+ OUT1
- C
+ OUT2
- Q
25
26
27
28
29
30
31
32
33
34
35
36
13
14
15
16
17
18
19
20
21
22
23
24
(2) Auxiliary Outputs
(5) Sensor (Temperature/Analog) Input
Auxiliary outputs 1 to 4
7
8
9
10
11
12
TC
Auxiliary output 4
Auxiliary output 3
22
23
+ 24
−
Auxiliary output 2
Auxiliary output 1
Pt
A
B
B
22
23
24
I
+ 22
mA
23
−
24
V
−
V
+
22
23
24
−
+
EV3
+
EV4
−
+
EV1
+
EV2
CT1
13
14
15
16
17
18
19
20
21
24 VAC/DC
1
Models with Voltage Output (for
Driving SSR) and Relay Output
Models with 2 Voltage
Outputs (for Driving SSR)
OUT1 3
+ C
−
4
5
6
3
4
5
6
(3) Input Power Supply
010
Four event inputs
and one CT
Potentiometer
input
19
O
20
W
21
C
The E5@C-T is set for a K-type thermocouple (input type = 5) by
default. An input error (s.err) will not occur if the input type setting
does not agree with the temperature sensor. Check the input type.
019
Six event inputs, one CT, and
transfer output
−
13
+
14
+ EV3 15
EV4
16
−
28 −
+
+
17
29
EV1
+ EV5 30 +
18
EV2
EV6
19
31
+
CT1
+
Transfer V
20
32
I
output
21
33
−
021
Six event inputs and
transfer output
−
+
EV3
+
EV4
−
28 −
+
+
29
EV5
EV1
+
30 +
EV6
EV2
+
31
Transfer V + 32
I
output
−
33
13
14
15
16
17
18
19
20
21
022
Communications, four event inputs,
and transfer output
B(+)
13
RS-485
14
A(-)
15
−
16
28 −
+
+
29
17
EV5
EV1
+
18
30 +
EV6
EV2
19
+
31
+
Transfer V
20
32
I
output
−
21
33
* The position-proportional control models (E5EC-TPR@@@M-@@@)
will be released in May 2014.
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with
EMC standards will not be possible.
4. Connect M3 crimped terminals.
Isolation/Insulation Block Diagrams
Models with 4 Auxiliary Outputs
Sensor input, CT input, potentiometer input, and remote SP input
Communications and event inputs
Power
Supply
Voltage output (for driving SSR),
linear current output, and transfer output
Relay output
Auxiliary outputs 1, 2
Auxiliary outputs 3, 4
: Reinforced insulation
: Functional isolation
Note: Auxiliary outputs 1 to 2 and 3 to 4 are not insulated.
90
E5EC-T/E5AC-T
Nomenclature
E5EC-T
Front panel
No. 1 display
Temperature unit
Top View of E5EC-T
PV or specified monitor/parameter
Operation indicators
No. 2 display
Top-panel
Setup
Tool port
SP or specified monitor/parameter value
No. 3 display
Use S Key to change the
digit (default setting).
Program No., segment No.,
remaining segment time, or MV
(valve opening).
Use the U D Keys to set
the parameter.
Front-panel Setup Tool port
Press U Key for at least 1 second when
Process value/Set point parameter are
displayed in Program SP Mode to go to
Display Segment Selection parameter in
Program Setting Level.
Press O Key once to go to Program Setting Level.
Use the M Key to change to another parameter.
Press O Key for at least 3 seconds to go to Initial Setting Level.
Press M and D Keys simultaneously for at
least 1 second to switch between run and
reset status.
E5AC-T
Front Panel
Temperature unit
Operation indicators
Top View of E5AC-T
No. 1 display
PV or specified monitor/parameter
No. 2 display
SP or specified monitor/parameter value
Front-panel Setup Tool port
No. 3 display
Program No. and segment No.,
remaining segment time, or MV
(valve opening).
Press the O Key once to go to the
Program Setting Level.
Press the O Key for at least 3
seconds to go to the Initial Setting
Level.
Press the M Key to switch to another parameter.
Press the U or D Key
to set the parameter.
Top-panel
Setup
Tool port
Press U Key for at least 1 second when
Process value/Set point parameter are
displayed in Program SP Mode to go to
Display Segment Selection parameter in
Program Setting Level.
Press the S Key to change the digit (default setting).
Press M and D Keys simultaneously for at least 1
second to change between run and reset status.
91
E5EC-T/E5AC-T
Dimensions
(Unit: mm)
Controllers
E5EC-T
48
(64)
60
4
1
44
96
The Setup Tool ports are on the front and top
of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion
Cable is required to make the connection.
91 Refer to the instructions that are provided
with the USB-Serial Conversion Cable for the
connection procedure.
110
Note: Do not leave the USB-Serial
Conversion Cable connected when
you use the Temperature Controller.
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
Mounted Separately
Group Mounted *
(48 × number of units − 2.5)+1.0
0
45+0.6
0
*
Selections for Control Outputs 1 and 2: QQ, QR, RR, CC, PR, or CQ
If you also specify 019, 021, 022 for the option selection and use
group mounting, the ambient temperature must be 45°C or less.
If the ambient temperature is 55°C, maintain the following mounting
spaces between Controllers.
92+0.8
0
60 min.
45-0.6
0
Group mounting does not
allow waterproofing.
120 min.
92+0.8
0
92-0.8
0
120 min.
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
• To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
• When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
92
E5EC-T/E5AC-T
E5AC-T
(64)
60
4
1
96 x 96
91 x 91
110
Waterproof
Packing (Accessory)
Mounting Adapter
(Accessory)
The Setup Tool ports are on the front and top of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.
Group Mounted *
Mounted Separately
(96 × number of units − 3.5)+1.0
0
92+0.8
0
92+0.8
0
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
• To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
• When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
Group mounting does not
allow waterproofing.
120 min.
92+0.8
0
Accessories (Order Separately)
● USB-Serial Conversion Cable
E58-CIFQ2
(2110)
250
263
1510
LED (RD)
USB connector
(type A plug)
Serial connector
LED (PWR)
LED (SD)
● Conversion Cable
E58-CIFQ2-E
Conversion Cable
Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510)
250
263
E58-CIFQ2 (Order Separately)
1510
Conversion Cable
Note: Always use this product together with the E58-CIFQ2.
93
E5EC-T/E5AC-T
● Terminal Covers
E53-COV24 (Three Covers provided.)
2
3.8
● Waterproof Packing
Y92S-P9 (for DIN 48 × 96)
The Waterproof Packing is provided with the Temperature
Controller.
Order the Waterproof Packing separately if it becomes lost or
damaged.
The degree of protection when the Waterproof Packing is used
is IP66.
Also, keep the Port Cover on the front-panel Setup Tool port
of the E5EC-T/E5AC-T securely closed.
To maintain an IP66 degree of protection, the Waterproof
Packing and the Port Cover for the front-panel Setup Tool port
must be periodically replaced because they may deteriorate,
shrink, or harden depending on the operating environment.
Y92S-P10 (for DIN 96 × 96) The replacement period will vary with the operating
environment.
Check the required period in the actual application.
Use 3 years or sooner as a guideline.
If a waterproof structure is not required, then the Waterproof
Packing does not need to be installed.
10
91
● Setup Tool Port Cover for top panel
Y92S-P7
Order this Port Cover
separately if the Port Cover on
the front-panel Setup Tool port
is lost or damaged. The
Waterproof Packing must be
periodically replaced because
it may deteriorate, shrink, or
harden depending on the
operating environment.
94
● Mounting Adapter
Y92F-51 (Two Adapters provided.)
One pair is provided with the
Controller.
Order this Adapter
separately if it becomes lost
or damaged.
E5EC-T/E5AC-T
● Watertight Cover
Y92A-96N (96 × 96)
● Watertight Cover
Y92A-49N (48 × 96)
21.9
21.9
(2)
(2)
131.7
131.7
67.6
115.6
29.4
29.4
● Current Transformers
E54-CT1
21
15
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT1
2.8
5.8 dia.
7.5
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings:
400±2
Winding resistance:
18±2 Ω
3
Output voltage (Eo) V (r.m.s.)
10.5
40
Two, 3.5 dia.
10
30
100V
Frequency: 50 Hz
∞
1kΩ
10
Distortion
factor
10%
1
3%
1%
100mV
10
100Ω
1
RL=10Ω
E54-CT3
2.36 dia.
30
12 dia.
9
100μV
10
1
10
100mA
1
40 × 40
30
Connection Example
Plug
Armature
Lead
18
Output voltage (Eo) V (r.m.s.)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON Digital
Temperature Controller is 50 A.)
Number of windings:
400±2
Winding resistance:
8±0.8 Ω
15
Approx. 3 dia.
100 1,000A
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
E54-CT3
Two, M3 (depth: 4)
E54-CT3 Accessories
• Armature
10
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz
Distortion
factor
10%
3%
1%
∞
1kΩ
500Ω
10
1
100mV
100Ω
50Ω
10
RL=10Ω
• Plug
1
Approx. 6 dia.
100μV
(22)
10
1
10
100mA
1
10
100 1,000A
Thru-current (Io) A (r.m.s.)
95
E5@C/E5@C-T
Operation
Setting Levels Diagram
E5†C
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Press the O + M Keys for
at least 1 s
Operation in progress
Only when Manual Mode was used
just before power OFF
Power ON
Press the O Key
for at least 1 s or
the S Key for at
least 1 s*1
Press the O + M
Keys for at least 3 s.*2
Level changes
automatically.
Manual Control
Level
Used to set the MV
manually.
Operation Level
O Key for at
least 3 s while
a-m is
displayed.*2
Press the O Key once.
Press the S Key.*3
Press the S Key.*3
S Key for at least 1 s*1
Press the O Key
for at least 1 s.
Monitor/Setting
Item Level
Used to display
specified monitor
and setting items.
Initial Setting Level
Press the O Key for less than 1 s.
(models with communications only).
Used to set the input type
and other basic settings.
Stopped
Adjustment Level
Used to change adjustment
parameters (PID constants,
adjustment sensitivity, etc.).
Used for SP, alarm
values, and other basic
settings and monitoring.
Press the O Key for
at least 3 s*2
Release protection and
then enter the password
(−169) for the amoV
(Move to Advanced
Setting Level)
Advanced
parameter.
Press the O Key for at least 1 s.
Function
Setting Level
Used to set application functions.
Enter the password (1201)
while cmov (Move to
Calibration Level
parameter) is displayed.
Calibration Level
*1 Set the PF Setting parameter to a-m (Auto/Manual).
*2 The No. 1 display will flash when the keys are pressed for 1 s or longer.
*3 Set the PF Setting parameter to pfdp (monitor/setting items).
96
Protect Level
Used to set protection
for operations.
Communications
Setting Level
Used to set up
communications.
E5@C/E5@C-T
E5†C-T
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Press O and M Keys
for at least 1 s.
Protect Level
Used to set protection
for operations.
Starting in manual mode
Power ON
Press O and M Keys
for at least 3 s.*2
Operation in progress
Level changes
automatically.
Manual Control
Level
Press O or
S Key for at least 1 s.*1
Press S Key.*3
Operation Level
Used to set the MV
manually.
Press O Key for at
least 3 s while a-m is
displayed.*2
Press O Key
for less than 1 s.
Used for SPs and other
basic settings and
monitoring.
Press S Key
for at least 1 s.*1
Program Setting
Level
Parameter and
segment settings for
all programs
Press O Key
for less than 1 s.
Press O
Key for at
least 1 s.
Press O Key
for less than 1 s.
Press O Key
for less than 1 s.
PID Setting
Level
Parameters for all PID
sets (e.g., PID
constants)
Adjustment Level
Adjustment parameters
(e.g., PID constants for
current PID set)
Press S Key.*3
Press O Key for
at least 3 s.*2
Monitor/Setting
Item Level
Used to display
specified monitor and
setting items.
Control stops.
Initial Setting Level
Press O Key for less
than 1 s (only models
with communications).
Stopped
Used to set the input type
and other basic settings.
Release protection and then
enter the password (−169) for
the amoV (Move to Advanced
Function Setting Level)
parameter.
Communications
Setting Level
Communications settings
Press O Key for at
least 1 s.
Advanced Function
Setting Level
Advanced settings
Enter the password (1201)
while cmov (Move to
Calibration Level
parameter) is displayed.
Calibration Level
*1 Set the PF Setting parameter to a-m (Auto/Manual).
*2 The No. 1 display will flash when the keys are pressed for 1 s or longer.
*3 Set the PF Setting parameter to pfdp (monitor/setting items).
97
E5@C/E5@C-T
Operation
Parameters
E5@C
The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top
parameter in that level. Some parameters may not be displayed depending on the model and other settings.
Press the S Key*2
Power ON
Starting in Manual Mode.
Manual Control Level
Press the S Key
for at least 1 s.
*1
C
Press the O
Key or the S
Key for at least
1 s.
*1
PID
Control
only
25
0
PV/MV
Adjustment
Level
l.adj
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
at
AT Execute/Cancel
off
cmwt
off
Communications
Writing
spmd
SP Mode
lsp
ins
0.0
Process Value Input
Shift
ct1
0.0
Heater Current 1
Value Monitor
Heater Burnout
Detection 1
Heater Current 2
Value Monitor
0.0
Heater Burnout
Detection 2
lcr1
0.0
Leakage Current 1
Monitor
p
HS Alarm 1
i
d
Leakage Current 2
Monitor
HS Alarm 2
50.0
SP 0
chys
Manual Reset Value
Hysteresis (Heating)
0
soak
Hysteresis (Cooling)
0
wt-b
SP 4
w3of
mv-e
sprt
sprl
SP Ramp Fall Value
MV Upper Limit
0.0
M
Work Bit 4
ON Delay
Work Bit 4
OFF Delay
Work Bit 5
ON Delay
al-3
lcr1
Heater Current 1 Value
Monitor
M
r-s
0
M
Leakage Current 1
Monitor
al-4
Leakage Current 2
Monitor
al4h
Program Start
al4l
0
o
0.0
RUN/STOP
c-o
0.0
M
Alarm
Value 1
v-m
0.0
M
M
off
M
M
off
Communications
Monitor
chgp Changed Parameters Only
off
M
pmsk
Parameter Mask Enable
on
prlp
0
M
Displayed only for models with
communications. Changes are
effective after cycling power or
after a software reset.
Password to Move to
Protect Level
Alarm 2
Hysteresis
M
* Used with programless communications
up 1
Protocol Setting:
Switches between
cwf CompoWay/F and
Modbus.
psel
M
M
Communications
Unit No.
7
Communications
Baud Rate
M *3
area
adrh
Communications
Data Length
adrl
0
rwat
1000
M
prty
unit
M
M
Communications
even Parity
Send Data Wait
20 Time
M
0
M
up13
0
M
31
First Address
Upper Word
M
dn13
75
First Address
Lower Word
off
Receive Data
Wait Time
*3
sps
1.000
Communications
Node Number
Upload
Setting 1
Upload
Setting 13
Download
Setting 1
Download
Setting 13
M
copy
M
Communications
Stop Bits
1
dn 1
M
0
M
sdwt
Area
M
M
2
Highest
Communications
0
Unit No.
maxu
0
M
sbit
M
0.2
Communications
Setting Level
len
pfpt PF Key Protect
Alarm 2 Type
M
alh2
Press the O Key
less than 1 s.
9.6
wtpt Setting Change Protect
Alarm 1
0.2 Hysteresis
M
alt2
2
bps
M
2
M
alh1
Valve Opening
Monitor
1
Initial Setting/Communications
1
M
alt1 Alarm 1 Type
MV Monitor
(Cooling)
u-no
0
icpt Protect
or-r
MV Monitor
(Heating)
Press the O and M Keys
for at least 1 s.
M
Control Period (Cooling)
M
orev Direct/Reverse Operation
M
Move to Protect Level:
Displayed only when a
password is set.
Control Period (Heating)
20
Alarm Value
Lower Limit
M
Operation/Adjustment Protect
Work Bit 7
OFF Delay
20
M
c-cp
M
oapt
M
Alarm Value
Upper Limit
0 4
Protect Level
0
off
M
cp
0 4
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
pmov
Work Bit 7
ON Delay
Alarm
Value 4
M
Press the O and M Keys for
at least 3 s.
Work Bit 6
OFF Delay
on
M
ptrn Program Pattern
M
Soak Time Remain
Standard or
Heating/Cooling
M
st ST (Self-tuning)
Alarm Value
Lower Limit
0 3
M
Work Bit 6
ON Delay
stnd
M
M
al-1
M
s-hc
al3l
M
sktr
onof
Alarm Value
Upper Limit
0 3
M
prst
M
cntl PID ON/OFF
Alarm
Value 3
al3h
Heater Current 2 Value
Monitor
M
98
0
SP Lower Limit
-200
M
M
lcr2
M
sl-l
M
M
Work Bit 5
OFF Delay
M
M
Set Point During
SP Ramp
run
M
0
MV Lower Limit
M
ct2
1300
Alarm Value
Lower Limit
0 2
al2l
0
M
plcm
M
ct1
M
sl-h SP Upper Limit
M
Remote SP Monitor
Temperature Unit
c
Alarm Value
Upper Limit
0 2
rset
w8of
100.0
ol-l
Work Bit 3
OFF Delay
Work Bit 8
0 OFF Delay
M
M
Alarm
Value 2
al2h
M
sp-m
0
M
d-u
M
Multi-SP
0.0
0.0
Work Bit 8
0 ON Delay
same
ol-h
Work Bit 3
ON Delay
w8on
M
SP 7
al-2
0
0.0
M
0
Auto/Manual Switch
M
rsp
Alarm Value
Lower Limit
M
M
m-sp
M
w7of
SP Ramp Set Value
off
M
Press the
O Key
for at
least 3 s.
M
Decimal Point
dp
0 1
0
M
w5on
0
0.0
SP 6
a-m
M
w4of
al1l
0.0
Work Bit 2
OFF Delay
M
w4on
w7on
MV at PV Error
M
0
M
MV at Stop
M
SP 5
0
0
0
w6of
0.0
M
sp-7
mv-s
Work Bit 2
ON Delay
M
0
M
sp-6
w3on
0
Wait Band
off
0
sp-5
0
w6on
M
sp-4
w2of
Process Value/
Set Point 2
Scaling Lower Limit
0
M
0.0
M
0
Soak Time
M
SP 3
w2on
al1h
M
0
M
w5of
1
M
M
0
M
SP 2
M
Bit 1
w1on Work
ON Delay
0
1.0
M
M
Extraction of
Root
sqrp Square
Low-cut Point
0
M
SP 1
0
sp-3
Dead Band
M
hys
0
Dead Band
M
oc-h Open/Close
Hysteresis
0
1.0
M
sp-2
Derivative Time
(Cooling)
M
0
2.0
M
Integral Time
233 (Cooling)
of-r
25
M
in-l
Alarm Value
Upper Limit
0 1
M
M
db Position
Proportional
0
50.0
M
sp-1
Derivative Time
0.0
M
MV Change Rate
Limit
Work Bit 1
0 OFF Delay
c-i
c-db
0.0
Value/
25 Process
0 Set Point 1
w1of
Proportional Band
8.0 (Cooling)
M
sp-0
Integral Time
c-p
c-d
orl
0
40
M
hs2
Proportional Band
233
40
0.0
M
in-h Scaling Upper Limit
100
0.0
8.0
50.0
lcr2
Remote SP Input
Slope Coefficient
M
M
hs1
rsrt
M
M
5
0.8
M
M
hb2
0.0
M
M
0.0
rss
Remote SP Input Shift
M
0.0
ct2
Process Value Slope
1.000 Coefficient
M
M
hb1
inrt
1.000
M
in-t Input Type
Press the O Key less than 1 s.
M
M
Press the O Key for less than 1 s.
Operation Level
M
M
Initial Setting Level
Press the
O Key for
at least 1 s.
Press the O Key less than 1 s.
M
M
Press the O Key for at least 3 s.
Press the S Key*2
Other than the Auto/Manual Switch display
Starting in
Automatic
Mode.
M
spos
0.0
Copy
*3
SP Slope
*3
SP Offset
*3
M
*1. When the PF Setting parameter is set to A-M.
*2. When the PF Setting parameter is set to PFDP.
*3. Used with component communications.
E5@C/E5@C-T
Monitor/Setting Item Level
25
0
Monitor/Setting
Item Display 1
S
Monitor/Setting
Item Display 2
S
Monitor/Setting
Item Display 3
Monitor/Setting
Item Display 4
S
S
Monitor/Setting
Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
Press the O Key
for at least 1 s.
Advanced Function Setting Level
alt3
Alarm 3 Type
2
M
alh3
0.2
Alarm 3
Hysteresis
M
alt4 Alarm 4 Type
2
M
alh4
Alarm 4
0.2 Hysteresis
M
o1st
Control Output 1 Signal
4-20
M
o2st
Control Output 2 Signal
4-20
M
trst Transfer Output Signal
4-20
M
tr-t
Transfer Output Type
off
M
tr-h
100.0
Transfer Output
Upper Limit
init
Parameter Initialization
ret
M
mspu Number of Multi-SP
M
brgt
M
spru SP Ramp Time Unit
M
a1lt
M
Sequence
rest Standby
Reset
M
a2lt
M
sb1n Auxiliary Output 1
M
a3lt
M
sb2n Auxiliary Output 2
M
a4lt
M
Output 3
sb3n Auxiliary
Open in Alarm
M
prlt
off Points
m
a
n-o Open in Alarm
n-o Open in Alarm
n-o
M
sb4n
Auxiliary Output 4
Open in Alarm
n-o
M
a3on
M
st-b ST Stable Range
M
a4on
M
alfa
M
a1of
0.0
M
ev-1
msp0
M
ev-2
stop
Event Input
Assignment 1
Event Input
Assignment 2
M
Input
ev-3 Event
Assignment 3
none
M
ev-4
Event Input
Assignment 4
none
M
Input
ev-5 Event
Assignment 5
none
M
ev-6
none
M
clfl
Event Input
Assignment 6
Close/Floating
Motor Calibration
Travel Time
30
M
of Square
sqr Extraction
Root Enable
off
M Move to Advanced Function
Level:
amov Setting
Displayed when initial
0
α
0.65
0.8
M
lcma Limit Cycle MV
20.0 Amplitude
setting/communications
M protect is set to 0.
Alarm 4 ON Delay
Alarm 1 OFF Delay
Alarm 2 OFF Delay
M
mav Moving Average Count
M
mant
Control Output 1
Assignment
M
Output 2
out2 Control
Assignment
sub1
Minimum Output
ON/OFF Band
1.0
M
pf
PF Setting
shft
M
pfd1
Monitor/Setting Item 1
1
pfd2
Monitor/Setting Item 2
0
M
Auxiliary Output 2
sub2 Assignment
M
pfd3 Monitor/Setting Item 3
M
Output 3
sub3 Auxiliary
Assignment
M
pfd4 Monitor/Setting Item 4
M
Output 4
sub4 Auxiliary
Assignment
M
pfd5 Monitor/Setting Item 5
M
alma Integrated Alarm
M
No. 1 Display
spd1 PV/SP
Selection
M
t-u Soak Time Unit
M
PV/SP No. 2 Display
spd2 Selection
m
Alarm 4 OFF Delay
Heating/Cooling
Tuning Method
off
M
Auxiliary Output 1
Assignment
M
alsp
Alarm SP Selection
sp-m
0
0
0
4
0
M
MV Display Selection
odsl
o
M
Remote SP Input
M
PV Decimal Point
pvdp Display
MV at Stop and Error
Addition
rs-t
Auto/Manual Select
Addition
M
rspu Remote SP Enable
M
PV Status Display
pvst Function
M
SP
rsph Remote
Upper Limit
M
Status Display
svst SV
Function
M
SP
rspl Remote
Lower Limit
M
Display Refresh
d.ref Period
Manual Output Method
hold
M
mani
M
0.0
M
o
PV Rate of Change
Calculation Period
20
M
ompw
out1
Direct Setting of
Position Proportional
MV
off
M
lbab LBA Band
3.0
Manual MV
Limit Enable
off
M
hctm
49 Assignment
Alarm 3 OFF Delay
0
M
lbal LBA Level
alm4 (E5EC/E5AC only)
M
off
M
pvrp
alm3
M
amad
M
lba LBA Detection Time
alm2
0
M
inf Input Digital Filter
M
MV Display
o-dp
off
M
M
Alarm 3 ON Delay
0
off
M
pmvd
alm1
0
mvse
M
hsh HS Alarm Hysteresis
M
Alarm 2 ON Delay
0
M
a4of
M
manl
none
0
M
at-h AT Hysteresis
0.8
Alarm 1 ON Delay
0
M
a3of
M
hsl HS Alarm Latch
M
0
M
at-g AT Calculated Gain
1 Time Unit
Move to Protect Level
Time
M
M
a2of
M
p-db PV Dead Band
8.0
0
M
tidu Integral/Derivative
off
off
M
mot
15.0
0.0
flot
M
calb
0.1
Alarm 4 Latch
Cold Junction
Compensation
on Method
M
Burnout
hbh Heater
Hysteresis
M
hsu HS Alarm Use
0
M
M
Transfer
o1tl Simple
Ouptut 1 Lower Limit
off
Alarm 3 Latch
SP Tracking
sptr
off
0.1
cjc
a2on
100.0
Alarm 2 Latch
off
M
hbl Heater Burnout Latch
RT
off
off
off
M
Transfer
o1th Simple
Output 1 Upper Limit
on
Alarm 1 Latch
off
3
rt
on
off
M
a1on
0.0
Display Brightness
3
M
hbu HB ON/OFF
M
Output
tr-l Transfer
Lower Limit
Automatic Display
off Return Time
off
4-20
off
1300
Manual MV Initial Value
-200
M
on
off
off
0.25
M
Cooling Output
lcmt LCT
Minimum ON Time
0.2
M
to Calibration
cmov Move
Level
0
M
Move by setting password (−169).
99
E5@C/E5@C-T
E5@C-T
Some parameters may not be displayed depending on the model and other settings.
Starting in manual mode
Monitor/Setting Item Level
25
PF Monitor/
Power ON
Manual Control Level
25 Setting Item
0
S
PF Monitor/Setting
Item display 2 to 5
display 1
* The monitor/setting items to display are set in the Monitor/Setting Item 1 to 5 parameters
(Advanced Function Setting Level).
PV/Manual MV
50.0
Press S Key.*2
Press S Key.*2
Press O or S
Key for at least
1 s.*1
Press O Key for
at least 3 s while
a-m is displayed.
Press S
Key for at
least 1 s.*1
Program Setting Level
U
Operation Level
d.prg
01
25
0
prgt
Process
Value/Set Point 1
0.00
M
Elapsed
Program Time
Monitor
M
25
0
rptm
Process
Value/Set Point 2
0.00
ct1
Auto/Manual Switch
0.0
lcr1
r-r
rst
Hold
o
0.0
M
Segment Number
c-o
0
0.0
Remaining
Standby Time
Monitor
v-m
0.0
d.pid
U
M
1.i
233
PID 1 Integral
Time
40
1.c-p
8.0
233
40
M
100
al1l
PID 1 Integral
Time (Cooling)
Press O
Key for less
than 1 s.
0.0
PID 1 Dead
Band
1.ofr
1.olh
Alarm
Lower Limit
1 to 4
1.oll
0.0
1.aut
1320
1.lba
0
M
Adjustment Level
Display
Displayed only once
when entering
Adjustment Level.
AT Execute/Cancel
M
cmwt
67
D
M
styp
Segment n Format
on1
0.00
sp
Segment n SP
0
pr
Segment n Slope
0
Time Signal 1 to 2
ON Time
M
of1
M
M
Time Signal 1 to 2
Set Segment
Time Signal 1 to 2
OFF Time
M
time
Segment n Time
0.00
M
Press O Key for less than 1 s.
lcr1
0.0
Leakage Current 1 to 2
Value Monitor
1.000
M
wt-b
Wait Band
0
M
c-p
Proportional Band (Cooling)
8.0
c-i
Integral Time (Cooling)
233
M
Standby Time
c-d
Derivative Time (Cooling)
40
0.00
psps
Derivative Time
M
M
M
Heater Burnout
Detection 1 to 2
d
M
PV Input Slope
Coefficient
M
stb
Integral Time
40
off
Heater Current 1 to 2
Value Monitor
i
M
PV Input Shift
M
Fixed SP
M
0.0
inrt
Proportional Band
233
M
SP Mode
M
hb1
ins
p
8.0
M
HS Alarm 1 to 2
0.0
M
fsp
hs1
M
Communications
Writing
M
spmd
0.0
PID 1 LBA
Detection
Time
0
50.0
off
ct1
PID 1 Automatic
Selection Range
Upper Limit
ts1s
M
at
0
PID 1 MV Lower
Limit
Program
Link
Destination
end
M
psp
PID 1 MV Upper
Limit
link
M
Alarm
Upper Limit
1 to 4
45
ramp
Adjustment Level
off
PID 1 Manual
Reset Value
0
3
12
M
M
1.cdb
Program
Repetitions
0.00
1234
M
PID 1
Derivative Time
(Cooling)
Alarm Value
1 to 4
M
Valve Opening
Monitor
rpt
M
M
0
M
M
1.c-d
al1h
MV Monitor
(Cooling)
M
M
1.c-i
0
l.adj
100.0
PID 1
Proportional
Band (Cooling)
PID Set No.
M
0
M
M
For 0 to 7
al-1
Display PID
Selection
s0.0
PID 1
Derivative Time
M
M
MV Monitor
(Heating)
0
D
1
Run/Reset
(of the program)
M
M
1.d
For end
pid
M
PID 1
Proportional
Band
d.seg
end
Leakage Current 1
to 2 Value Monitor
Press O Key for less than 1 s.
1 2
3 4
5 6
7 8
D
8.0
U
M
PID Setting Level
Press the U Key
for at least 1 s in
Program SP Mode.
Display Segment Selection
END or 0 to Number of segments used − 1
d.seg
M
M
1.p
Number of
Segments Used
Process Value/Set
Point 1 or Process
Value/Set Point 2 in
Operation Level
U
Heater Current 1 to
2 Value Monitor
M
M
0.00
8
M
off
stbm
0
M
M
Program Number
0
seg
s-no
0.0
M
hold
25
D
M
M
Program No. Monitor/
Segment No. Monitor
M
prg
Display Program
Selection
M
M
pgsg
7
0
M
a-m
Program Execution
Repetitions Monitor
Press O
Key for
less than
1 s.
23
6
45
Program SP Shift Value
c-db
0.0
M
Dead Band
E5@C/E5@C-T
Press O Key
for at least 1 s.
Protect Level
Press O + M Key
for at least 3 s.
M
pmov
oapt
0
0
Operation/Adjustment
Protect
pfpt
Initial Setting/
Communications Protect
pmsk
Setting Change Protect
prlp
M
Move to Protect Level
icpt
Press O + M Key for at least 3 s. (The key pressing
time can be changed in the Move to Protect Level
Time parameter (Advanced Function Setting Level).)
1
M
M
0
off
Press O + M Key for at least 1 s.
Parameter Mask Enable
on
M
wtpt
PF Key Protect
off
M
Password to Move
to Protect Level
M
Initial Setting Level
Press O Key
for at least 3 s.
in-t
Input Type
Press O Key
for at least 1 s.
eset
SP Lower Limit
rst
M
M
in-h
Scaling Upper Limit
t-u
Scaling Lower Limit
0
t-pr
time
M
Decimal Point
0
pru
m
M
tspu
0
c
Temperature
Unit
rtsm
SP Upper Limit
p-on
cntl
Reset Operation
s-hc
1300
M
2
alh1
0.2
Standard or
Heating/Cooling
stnd
stop
o1st
4-20
M
cp
Startup Operation
cont
20
M
M
trst
4-20
tr-l
0.0
ev-1
rr-1
mot
Transfer Output
Lower Limit
vl-c
Event Input
Assignment 1
vl-o
ev-2
Event Input
Assignment 2
pms
adv
M
ev-3
Event Input
Assignment 3
to 6
sqr
none
0
Valve Completely
Closed Position
M
Valve Completely
Open Position
9999
M
Potentiometer
Specification Setting
0
M
Extraction of
Square Root
Enable
off
M
M
clfl
Travel Time
30
M
M
Transfer Output
Signal
Motor Calibration
off
M
M
Control output
1 to 2 Signal
M
Control Period
(Heating)
Transfer Output
Upper Limit
M
Alarm 1 to 4
Hysteresis
M
M
calb
M
Alarm 1 to 4
Type
M
PID ON/OFF
tr-h
100.0
M
alt1
Transfer Output
Type
M
Direct/Reverse
Operation
or-r
All PID AT Upper
Limit SP
tr-t
off
M
pid
M
M
sl-h
orev
M
Time Unit of Ramp
Rate
M
d-u
PV Start
Control Period
(Cooling)
20
M
Step Time/Rate of
Rise Programming
M
dp
c-cp
sp
M
M
in-l
Operation End
Operation
M
pvst
Program Time Unit
h-m
100
Press O Key
for at least 3 s.
sl-l
-200
5
Close/Floating
flot
amov
0
Moves to Advanced
Function Setting
Level
Enter password (−169)
to move.
M
M
Press O Key for less than 1 s.
Communications Setting Level
psel
Protocol Setting
Manual Reset Value
M
hys
Hysteresis (Heating)
Hysteresis (Cooling)
MV at Reset
M
0.0
sqrp
Communications
Baud Rate
area
len
7
Extraction of Square
Root Low-cut Point
sbit
2
Work Bit 1 to 8 ON
Delay
w1of
Work Bit 1 to 8 OFF
Delay
prty
even
M
0
Area
dn 1
Communications
Parity
rwat
Download
Setting
1 to 43
0
First Address
Upper Word
M
copy
Copy
M
off
M
adrl
Upload
Setting
1 to 23
0
M
0
Communications
Stop Bits
Communications
Node Number
M
0
adrh
0
up 1
M
Communications
Data Length
unit
Highest
Communications
Unit No.
M
First Address
Lower Word
M
0
M
M
w1on
0
100.0
M
Open/Close
Hysteresis
M
MV Upper Limit
maxu
M
0
M
bps
9.6
M
MV at PV Error
0.0
ol-l
oc-h
0.0
M
ol-h
Position Proportional
Dead Band
M
0.0
Communications
Unit No.
M
0.8
M
mv-e
1
M
1.0
u-no
M
db
2.0
M
mv-r
MV Change Rate
Limit
M
1.0
chys
orl
0.0
50.0
Send Data
Wait Time
M
M
of-r
sdwt
20
cwf
Receive Data
Wait Time
1000
M
Models with communications only: Changes to settings are applied
when the power is cycled or a software reset is performed.
M
MV Lower Limit
plcm
0
M
Communications
Monitor
*1 When PF Setting = A-M.
*2 When PF Setting = PFDP.
101
E5@C/E5@C-T
Advanced Function Setting Level
init
off
Parameter Initialization
mant
Program End ON Time
mani
Standby Time Unit
Standby Sequence Reset
n-o
Auxiliary Output 1 to 4
Open in Alarm
hsh
Heater Burnout Latch
lba
Heater Burnout Hysteresis
0.1
8.0
M
M
alfa
α
Integral/Derivative Time Unit
o
1
AT Calculated Gain
none
0.8
M
at-h
alm1
M
alm2
M
0.0
off
off
Moving Average Count
Automatic Display
Return Time
Display Brightness
Move to Protect Level Time
Cold Junction
Compensation Method
Alarm 1 to 4 ON Delay
0
pidh
0.50
p-db
Alarm 1 to 4 OFF Delay
Auxiliary Output 4
Assignment
off
M
burn
up
Burnout Method
pmst
Parameter Mask Setting
off
M
Integrated Alarm
Assignment
cmov
0
M
Alarm SP Selection
SP Tracking
PID Set Automatic
Selection Data
PID Set Automatic
Selection Hysteresis
PV Dead Band
0
manl
Display Refresh Period
0.25
M
M
M
0
pv
d.ref
M
Auxiliary Output 3
Assignment
M
M
M
pidi
SV Status Display Function
off
M
Auxiliary Output 2
Assignment
M
M
a1of
sptr
PV Status Display Function
off
M
M
3
a1on
svst
off
M
on
Auxiliary Output 1
Assignment
M
Alarm 1 to 4 Latch
PV/SP No. 2
Display Selection
M
sp-m
off
cjc
alsp
PV/SP No. 1
Display Selection
7
pvst
M
3
prlt
49
spd2
Control Output 2
Assignment
alm4
alma
spd1
M
Control Output 1
Assignment
M
M
a1lt
sub4
PF Monitor/
Setting Item 2 to 5
6
M
M
brgt
sub3
alm3
M
ret
LBA Band
M
Input Digital Filter
M
mav
sub2
pfd2
0
M
Limit Cycle MV Amplitude
20.0
inf
sub1
PF Monitor/Setting Item 1
M
M
AT Hysteresis
0.8
lcma
out2
pfd1
M
LBA Level
M
M
at-g
out1
PF Setting
1
M
M
tidu
lbab
pf
M
LBA Detection Time
3.0
0.65
102
lbal
LCT Cooling Output Min.
ON Time
shft
0.1
M
M
Minimum Output ON/OFF
Band
M
HS Alarm Hysteresis
0
off
lcmt
0.2
M
M
hbh
HS Alarm Latch
off
HB ON/OFF
on
hbl
1.0
M
M
hbu
hsl
ompw
M
M
M
Heating/Cooling Tuning
Method
M
HS Alarm Use
on
a
sb1n
hsu
hctm
0
M
M
PV Rate of Change
Calculation Period
M
RT
off
h-m
rest
rt
pvrp
20
M
M
s-u
Direct Setting of Position
Proportional MV
M
Manual MV Initial Value
0.0
0.0
pmvd
off
M
M
pend
Manual Output Method
hold
Manual MV Limit Enable
Move to Calibration Level
E5@C/E5@C-T
Error Displays (Troubleshooting)
When an error occurs, the No. 1 display or No. 2 display shows the error code.
Take necessary measure according to the error code, referring the following table.
Display
Name
Meaning
The input value exceeded the control
range.*
The input type is not set correctly.
The sensor is disconnected or shortcircuited.
The sensor is not wired correctly.
The sensor is not wired.
s.err
Input error
[[[[
Display
range
exceeded
]]]]
* Control Range
Temperature resistance
thermometer or thermocouple input:
SP Lower Limit - 20°C to SP Upper
Limit + 20°C
(SP Lower Limit - 40°F to SP Upper
Limit + 40°F)
ESIB input:
Same as specified input range.
Analog input:
Scaling range -5% to 105%
This is not an error. It
is displayed when the
Below -1,999 control range is wider
than the display
range and the PV
exceeds the display
range. The PV is
displayed for the
range that is given on
Above 9,999 the left (the number
without the decimal
point).
e333
A/D
converter
error
There is an error in the internal
circuits.
e111
Memory
error
There is an error in the internal
memory operation.
Action
Operation
After the error occurs and it is
Check the wiring for input to be sure displayed, the alarm output will
it is wired correctly, not broken, and operate as if the upper limit was
not shorted. Also check the input
exceeded.
type.
It will also operate as if transfer
If there are no problems in the wiring output exceeded the upper limit.
or input type settings, cycle the
If an input error is assigned to a
power supply.
control output or auxiliary output, the
If the display remains the same,
output will turn ON when the input
replace the Digital Temperature
error occurs.
Controller.
The error message will appear in the
If the display is restored to normal, display for the PV.
then the probable cause is external
noise affecting the control system.
Note: 1. The heating and cooling
Check for external noise.
control outputs will turn
OFF.
Note: For a temperature resistance
2. When the manual MV, MV
thermometer, the input is
at stop, MV at reset, or MV
considered disconnected if
at error is set, the control
the A, B, or B’ line is broken.
output is determined by the
set value.
-
After checking the input error, turn
the power OFF then back ON again.
If the display remains the same, the
controller must be repaired.
If the display is restored to normal,
then a probable cause can be
external noise affecting the control
system. Check for external noise.
First, cycle the power supply.
If the display remains the same, the
controller must be repaired.
If the display is restored to normal,
then a probable cause can be
external noise affecting the control
system. Check for external noise.
ffff
Overcurrent
This error is displayed when the peak
current exceeds 55.0 A.
-
ct1
ct2
lcr1
lcr2
HB or HS
alarm
If there is a HB or HS alarm, the No.
1 display will flash in the relevant
setting level.
-
----
"----" will be displayed for the Valve
Opening Monitor parameter if any of
the following error occurs.
• Motor calibration has not been
Potentiometer
performed.
Input Error
•
The wiring of the potentiometer is
(Positionincorrect or broken.
proportional
Models Only) • The potentiometer input value is
incorrect (e.g., the input is out of
range or the potentiometer has
failed).
Check for the above errors.
Control continues and operation is
normal.
The value will appear in the display
for the PV.
Refer to the E5@C Digital
Temperature Controllers User’s
Manual (Cat. No. H174) or the
E5@C-T Digital Temperature
Controllers Programmable Type
User’s Manual (Cat. No. H185) for
information on the
controllable range.
The control outputs, auxiliary
outputs, and transfer outputs turn
OFF. (A current output will be approx.
0 mA and a linear voltage output will
be approx. 0V.)
The control outputs, auxiliary
outputs, and transfer outputs turn
OFF. (A current output will be approx.
0 mA and a linear voltage output will
be approx. 0V.)
Control continues and operation is
normal.
The error message will appear for the
following displays.
Heater Current Value 1 Monitor
Heater Current Value 2 Monitor
Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
The No. 1 display for the following
parameter flashes in Operation Level
or Adjustment Level.
Heater Current Value 1 Monitor
Heater Current Value 2 Monitor
Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
However, control continues and
operation is normal.
Close control: The control output is
OFF or the value that is set for the
MV at PV Error parameter is output.
Floating control: Operation will be
normal.
103
E5@C/E5@C-T
Safety Precautions
● Be sure to read the precautions for all E5@C/E5@C-T models in the website at:
http://www.ia.omron.com/.
Warning Indications
CAUTION
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury or in
property damage.
Precautions for
Safe Use
Supplementary comments on what to
do or avoid doing, to use the product
safely.
Precautions for
Correct Use
Supplementary comments on what to
do or avoid doing, to prevent failure to
operate, malfunction or undesirable
effect on product performance.
Meaning of Product Safety Symbols
Used to warn of the risk of electric shock under
specific conditions.
Used for general prohibitions for which there is no
specific symbol.
Used to indicate prohibition when there is a risk of
minor injury from electrical shock or other source
if the product is disassembled.
Used for general CAUTION, WARNING, or
DANGER precautions for which there is no
specified symbol. (This symbol is also used as the
alerting symbol, but shall not be used in this
meaning on the product.)
Used for general mandatory action precautions
for which there is no specified symbol.
CAUTION
Do not touch the terminals while power is being
supplied.
Doing so may occasionally result in minor injury due
to electric shock.
Electric shock may occur. Do not touch any cables or
connectors with wet hands.
Electric shock, fire, or malfunction may occasionally
occur. Do not allow metal objects, conductors,
cuttings from installation work, or moisture to enter
the Digital Temperature Controller or the Setup Tool
port or ports. Attach the cover to the front-panel Setup Tool port
whenever you are not using it to prevent foreign objects from
entering the port.
Do not use the Digital Temperature Controller where
subject to flammable or explosive gas. Otherwise,
minor injury from explosion may occasionally occur.
Not doing so may occasionally result in fire. Do not
allow dirt or other foreign objects to enter the Setup
Tool port or ports, or between the pins on the
connectors on the Setup Tool cable.
104
Minor electric shock or fire may occasionally occur.
Do not use any cables that are damaged.
Never disassemble, modify, or repair the product or
touch any of the internal parts. Minor electric shock,
fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a. This product is UL listed*1 as Open Type Process
Control Equipment. It must be mounted in an
enclosure that does not allow fire to escape
externally.
b. More than one disconnect switch may be required to deenergize the equipment before servicing the product.
c. Signal inputs are SELV, limited energy. *2
d. Caution: To reduce the risk of fire or electric shock, do not
interconnect the outputs of different Class 2 circuits. *3
If the output relays are used past their life expectancy,
contact fusing or burning may occasionally occur.
Always consider the application conditions and use
the output relays within their rated load and electrical
life expectancy. The life expectancy of output relays varies
considerably with the output load and switching conditions.
Even if you replace only the Main Unit of the E5DC, check
the condition of the Terminal Unit.
If corroded terminals are used, contact failure in the
terminals may cause the temperature inside the
Digital Temperature Controller to increase, possibly resulting in
fire.
If the terminals are corroded, replace the Terminal Unit as well.
Tighten the terminal screws to the rated torque of
between 0.43 and 0.58 N•m. *4
Loose screws may occasionally result in fire.
Set the parameters of the product so that they are
suitable for the system being controlled. If they are
not suitable, unexpected operation may occasionally
result in property damage or accidents.
A malfunction in the product may occasionally make
control operations impossible or prevent alarm
outputs, resulting in property damage.
To maintain safety in the event of malfunction of the
product, take appropriate safety measures, such as installing a
monitoring device on a separate line.
*1. E5CC, E5EC, E5AC, and E5DC Digital Temperature Controllers that were
shipped through November 2013 are UL recognized.
*2. An SELV (separated extra-low voltage) system is one with a
power supply that has double or reinforced insulation between the
primary and the secondary circuits and has an output voltage of
30 V r.m.s. max. and 42.4 V peak max. or 60 VDC max.
*3. A class 2 circuit is one tested and certified by UL as having the current and
voltage of the secondary output restricted to specific levels.
*4. The specified torque is 0.5 N·m for the E5CC-U.
E5@C/E5@C-T
Precautions for Safe Use
Be sure to observe the following precautions to prevent malfunction
or adverse affects on the performance or functionality of the product.
Not doing so may occasionally result in faulty operation. Do not
handle the Digital Temperature Controller in ways that exceed the
ratings.
1. This product is specifically designed for indoor use only.
Do not use this product in the following places:
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to dust or corrosive gas (in particular, sulfide gas
and ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
2. Use and store the product within the rated ambient temperature
and humidity.
Gang-mounting two or more Digital Temperature Controllers, or
mounting Digital Temperature Controllers above each other may
cause heat to build up inside the Digital Temperature Controllers,
which will shorten their service life. In such a case, use forced
cooling by fans or other means of air ventilation to cool down the
Digital Temperature Controllers.
3. To allow heat to escape, do not block the area around the Digital
Temperature Controller.
Do not block the ventilation holes on the Digital Temperature
Controller.
4. Be sure to wire properly with correct signal name and polarity of
terminals.
5. Use the specified size of crimped terminals (M3, width of 5.8 mm
or less) to wire the E5CC, E5EC, E5AC, E5DC, or E5@C-T. To
connect bare wires to the terminal block of the E5CC, E5EC,
E5AC, E5DC, or E5@C-T, use copper braided or solid wires with
a gage of AWG24 to AWG18 (equal to a cross-sectional area of
0.205 to 0.823 mm2). (The stripping length is 6 to 8 mm.) Up to two
wires of the same size and type, or two crimped terminals can be
inserted into a single terminal.
Use the specified size of crimped terminals (M3.5, width of 7.2 mm
or less) to wire the E5CC-U. To connect bare wires to the terminal
block of the E5CC-U, use copper braided or solid wires with a
gage of AWG24 to AWG14 (equal to a cross-sectional area of
0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.) Up to two
wires of the same size and type, or two crimped terminals can be
inserted into a single terminal.
Use the specified size of crimped terminals (M3, width of 5.8 mm
or less) to wire the E5GC.*
To connect bare wires to the terminal block of the E5GC, use
copper braided or solid wires with a gauge of AWG24 to AWG18
(equal to a cross-sectional area of 0.205 to 0.823 mm2). (The
stripping length for Digital Temperature Controllers with screw
terminal blocks is 6 to 8 mm. The stripping length for Digital
Temperature Controllers with screwless clamp terminal blocks is 8
to 12 mm.)
Up to two wires of the same size and type, or two crimped
terminals can be inserted into a single terminal. When connecting
two wires into one terminal of a Digital Temperature Controller with
a screwless clamp terminal block, use ferrules with a diameter of
0.8 to 1.4 mm and an exposed conductor length of 8 to 12 mm that
two wires are crimped for a ferrule.*
* The Digital Temperature Controller with screwless clamp
terminals underwent UL testing with one braided wire connected.
6. Do not wire the terminals that are not used.
7. Use a commercial power supply for the power supply voltage input
to a Digital Temperature Controller with AC input specifications.
Do not use the output from an inverter as the power supply.
Depending on the output characteristics of the inverter,
temperature increases in the Digital Temperature Controller may
cause smoke or fire damage even if the inverter has a specified
output frequency of 50/60 Hz.
8. To avoid inductive noise, keep the wiring for the product’s terminal
block away from power cables carry high voltages or large
currents. Also, do not wire power lines together with or parallel to
product wiring. Using shielded cables and using separate conduits
or ducts is recommended.
Attach a surge suppressor or noise filter to peripheral devices that
generate noise (in particular, motors, transformers, solenoids,
magnetic coils, or other equipment that have an inductance
component).
When a noise filter is used at the power supply, first check the
voltage or current, and attach the noise filter as close as possible
to the product.
Allow as much space as possible between the product and
devices that generate powerful high frequencies (high-frequency
welders, high-frequency sewing machines, etc.) or surge.
9. Use this product within the rated load and power supply.
10.Make sure that the rated voltage is attained within two seconds of
turning ON the power using a switch or relay contact. If the voltage
is applied gradually, the power may not be reset or output
malfunctions may occur.
11.Make sure that the Digital Temperature Controller has 30 minutes
or more to warm up after turning ON the power before starting
actual control operations to ensure the correct temperature
display.
12.When executing self-tuning with E5@C, turn ON power to the load
(e.g., heater) at the same time as or before supplying power to the
product. If power is turned ON to the product before turning ON
power to the load, self-tuning will not be performed properly and
optimum control will not be achieved.
13.A switch or circuit breaker must be provided close to the product.
The switch or circuit breaker must be within easy reach of the
operator, and must be marked as a disconnecting means for this
unit.
14.Use a soft and dry cloth to clean the product carefully. Do not use
organic solvent, such as paint thinner, benzine or alcohol to clean
the product.
15.Design the system (e.g., control panel) considering the 2 seconds
of delay that the product's output to be set after power ON.
16.The output may turn OFF when you move to the initial setting level.
Take this into consideration when performing control operations.
17.The number of non-volatile memory write operations is limited.
Therefore, use RAM write mode when frequently overwriting data
during communications or other operations.
18.Always touch a grounded piece of metal before touching the
Digital Temperature Controller to discharge static electricity from
your body.
19.Use suitable tools when taking the Digital Temperature Controller
apart for disposal. Sharp parts inside the Digital Temperature
Controller may cause injury.
20.For compliance with Lloyd’s standards, the E5CC, E5CC-U,
E5EC, and E5AC must be installed under the conditions that are
specified in Shipping Standards.
21.For the Digital Temperature Controller with two Setup Tool ports
(E5EC/E5AC/E5DC/E5GC), do not connect cables to both ports at
the same time. The Digital Temperature Controller may be
damaged or may malfunction.
22.Do not place heavy object on the Conversion Cable, bend the
cable past its natural bending radius, or pull on the cable with
undue force.
23.Do not disconnect the Communications Conversion Cable or the
USB-Serial Conversion Cable while communications are in
progress. Damage or malfunction may occur.
24.Do not touch the external power supply terminals or other metal
parts on the Digital Temperature Controller.
25.Refer to the E5@C Digital Temperature Controllers User’s Manual
(Cat. No. H174) for information on the communications distances
and cables for the E5@C.
For details on the E5@C-T, refer to the E5@C-T Digital
Temperature Controllers Programmable Type User’s Manual (Cat.
No. H185).
26.Do not bend the communications cables past their natural bending
radius. Do not pull on the communications cables.
27.Do not turn the power supply to the Digital Temperature Controller
ON or OFF while the USB-Serial Conversion Cable is connected.
The Digital Temperature Controller may malfunction.
28.Make sure that the indicators on the USB-Serial Conversion Cable
are operating properly. Depending on the application conditions,
deterioration in the connectors and cable may be accelerated, and
normal communications may become impossible. Perform
periodic inspection and replacement.
29.Connectors may be damaged if they are inserted with excessive
force. When connecting a connector, always make sure that it is
oriented correctly. Do not force the connector if it does not connect
smoothly.
105
E5@C/E5@C-T
30.Noise may enter on the USB-Serial Conversion Cable, possibly
causing equipment malfunctions. Do not leave the USB-Serial
Conversion Cable connected constantly to the equipment.
31.For the E5DC, when you attach the Main Unit to the Terminal Unit,
make sure that the hooks on the Main Unit are securely inserted
into the Terminal Unit.
32.For the E5CC-U, when you attach the Main Unit to the socket,
make sure that the hooks on the socket are securely inserted into
the Main Unit.
33.Install the DIN Track vertically to the ground.
34.For the E5DC, always turn OFF the power supply before
connecting the Main Unit to or disconnecting the Main Unit from
the Terminal Unit, and never touch nor apply shock to the
terminals or electronic components. When connecting or
disconnecting the Main Unit, do not allow the electronic
components to touch the case.
35.Observe the following precautions when you remove the terminal
block or pulling out the interior of the product of the E5GC.
• Always follow the instructions provided in the E5@C Digital
Temperature Controllers User’s Manual (Cat. No. H174).
• Turn OFF the power supply before you start and never touch
nor apply shock to the terminals or electric components.
When you insert the interior body of the Digital Temperature
Controller, do not allow the electronic components to touch
the case.
• Check for any corrosion on the terminals.
• When you insert the interior body into the rear case, confirm
that the hooks on the top and bottom are securely engaged
with the case.
Shipping Standards
The E5CC, E5CC-U, E5EC, and E5AC comply with Lloyd's
standards. When applying the standards, the following installation
requirements must be met in the application.
Application Conditions
● Installation Location
The E5CC, E5CC-U, E5EC, and E5AC comply with installation
category ENV1 and ENV2 of Lloyd's standards. Therefore, they must
be installed in a location equipped with air conditioning. They cannot
be used on the bridge or decks, or in a location subject to strong
vibration.
Precautions for Correct Use
● Service Life
1. Use the product within the following temperature and humidity ranges:
Temperature: -10 to 55°C (with no icing or condensation)
Humidity:
25% to 85%
If the product is installed inside a control board, the ambient
temperature must be kept to under 55°C, including the temperature
around the product.
2. The service life of electronic devices like Digital Temperature
Controllers is determined not only by the number of times the relay is
switched but also by the service life of internal electronic components.
Component service life is affected by the ambient temperature: the
higher the temperature, the shorter the service life and, the lower
the temperature, the longer the service life. Therefore, the service
life can be extended by lowering the temperature of the Digital
Temperature Controller.
3. When two or more Digital Temperature Controllers are mounted
horizontally close to each other or vertically next to one another,
the internal temperature will increase due to heat radiated by the
Digital Temperature Controllers and the service life will decrease.
In such a case, use forced cooling by fans or other means of air
ventilation to cool down the Digital Temperature Controllers. When
providing forced cooling, however, be careful not to cool down the
terminals sections alone to avoid measurement errors.
● Measurement Accuracy
1. When extending or connecting the thermocouple lead wire, be sure to
use compensating wires that match the thermocouple types.
2. When extending or connecting the lead wire of the platinum resistance
thermometer, be sure to use wires that have low resistance and keep
106
the resistance of the three lead wires the same.
3. Mount the product so that it is horizontally level.
4. If the measurement accuracy is low, check to see if input shift has
been set correctly.
● Waterproofing (Not applicable to the E5CC-U/
E5DC.)
The degree of protection is as shown below. Sections without any
specification on their degree of protection or those with IP@0 are not
waterproof.
Front panel: IP66, Rear case: IP20, Terminal section: IP00
When waterproofing is required, insert the Waterproof Packing on the
backside of the front panel. Keep the Port Cover on the front-panel
Setup Tool port of the E5EC/E5AC/E5EC-T/E5AC-T securely closed.
The degree of protection when the Waterproof Packing is used is
IP66. To maintain an IP66 degree of protection, the Waterproof
Packing and the Port Cover for the front-panel Setup Tool port must
be periodically replaced because they may deteriorate, shrink, or
harden depending on the operating environment. The replacement
period will vary with the operating environment. Check the required
period in the actual application. Use 3 years or sooner as a guideline.
If the Waterproof Packing and Port Cover are not periodically
replaced, waterproof performance may not be maintained. If a
waterproof structure is not required, then the Waterproof Packing
does not need to be installed.
● Operating Precautions
1. When using self-tuning, turn ON power for the load (e.g., heater)
at the same time as or before supplying power to the Digital
Temperature Controller. If power is turned ON for the Digital
Temperature Controller before turning ON power for the load, selftuning will not be performed properly and optimum control will not
be achieved.
When starting operation after the Digital Temperature Controller
has warmed up, turn OFF the power and then turn it ON again at
the same time as turning ON power for the load. (Instead of turning
the Digital Temperature Controller OFF and ON again, switching
from STOP mode to RUN mode can also be used.)
2. Avoid using the Digital Temperature Controller in places near a
radio, television set, or wireless installing. These devices can
cause radio disturbances which adversely affect the performance
of the Controller.
● Others
1. Do not Connect or disconnect the Conversion Cable connector
repeatedly over a short period of time.
The computer may malfunction.
2. After connecting the Conversion Cable to the computer, check the
COM port number before starting communications. The computer
requires time to recognize the cable connection. This delay does
not indicate failure.
3. Do not connect the Conversion Cable through a USB hub. Doing
so may damage the Conversion Cable.
4. Do not use an extension cable to extend the Conversion Cable
length when connecting to the computer. Doing so may damage
the Conversion Cable.
E5@C/E5@C-T
● Mounting
E5EC/E5AC/E5EC-T/E5AC-T
Adapter
Mounting to a Panel
E5GC
Adapter
Panel
Adapter
Terminal Cover
(E53-COV24)
Waterproof
Packing
Terminal Cover
(E53-COV24)
Panel
Water Proof Packing
1. For waterproof mounting, waterproof packing must be installed on
the Digital Temperature Controller. Waterproofing is not possible
when group mounting several Digital Temperature Controllers.
Waterproof packing is not necessary when there is no need for the
waterproofing function.
2. Insert the E5GC into the mounting hole in the panel.
3. Use two Mounting Adapters, either on the top and bottom or on the
right and left.
4. Push the Adapters from the terminals up to the panel, and
temporarily fasten the E5GC.
5. Tighten the two fastening screws on the Adapter. Alternately
tighten the two screws little by little to maintain a balance. Tighten
the screws to a torque of 0.29 to 0.39 N·m.
E5CC/E5CC-T
1. For waterproof mounting, waterproof packing must be installed on
the Digital Temperature Controller. Waterproofing is not possible
when group mounting several Digital Temperature Controllers.
Waterproof packing is not necessary when there is no need for the
waterproofing function.
2. Insert the E5EC/E5AC/E5EC-T/E5AC-T into the mounting hole in
the panel.
3. Push the adapter from the terminals up to the panel, and
temporarily fasten the E5EC/E5AC/E5EC-T/E5AC-T.
4. Tighten the two fastening screws on the adapter.
Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
E5DC
Adapter
There are two models of Terminal Covers that you can use with the E5CC/
E5CC-T.
Terminal Cover
(E53-COV17)
(Sold separately)
Adapter
Panel
Terminal Cover
(E53-COV23)
Terminal Unit
Main Unit
Water Proof Packing
Panel
E5CC-U
For the Wiring Socket for the E5CC-U, purchase the P2CF-11 or
PG3A-11 separately.
1. Insert the E5DC into the mounting hole in the panel. (Attach the
Terminal Unit after you insert the Main Unit.)
2. Push the Adapter from the Terminal Unit up to the panel, and
temporarily fasten the E5DC.
3. Tighten the two fastening screws on the Adapter. Alternately
tighten the two screws little by little to maintain a balance. Tighten
the screws to a torque of 0.29 to 0.39 N·m.
Mounting to and Removing from DIN Track
E5DC
1. For waterproof mounting, waterproof packing must be installed on the
Digital Temperature Controller. Waterproofing is not possible when
group mounting several Digital Temperature Controllers. Waterproof
packing is not necessary when there is no need for the waterproofing
function.
The E5CC-U cannot be waterproofed even if the Waterproof Packing
is inserted.
2. Insert the E5CC/E5CC-U/E5CC-T into the mounting hole in the
panel.
3. Push the adapter from the terminals up to the panel, and
temporarily fasten the E5CC.
4. Tighten the two fastening screws on the adapter.
Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
• Mounting a Unit
Pull down the DIN Track hook on the Terminal Unit and catch the
top hook on the DIN Track.
Press the Unit onto the DIN Track until the DIN Track hooks are
locked in place.
2. Catch the top hook on
the DIN Track.
3. Press the Unit onto
the DIN Track.
1. Pull down the hook.
4. Make sure that the hooks
are locked in place.
107
E5@C/E5@C-T
• Removing a Unit
Pull down on the DIN Track Hook with a flat-blade screwdriver and
lift up the Unit.
Mounting the DIN Track
Attach the DIN Track to the inside of the control panel with screws to
at least three locations.
• DIN Track (sold separately)
PFP-50N (50 cm) and PFP-100N (100 cm)
Install the DIN Track vertically to the ground.
Removing the Main Unit
Press in the two hooks on the Main Unit and remove the Main Unit
from the Terminal Unit.
(1)
Horizontal: NG
Vertical: OK
(2)
Mounting the Terminal Cover
E5CC/E5CC-T
(1)
End Plate Installation
Make sure to attach PFP-M End Plates to the ends of the Units.
B
A
Slightly bend the E53-COV23 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction. E53-COV17 Terminal
Cover can be also attached.
Make sure that the "UP" mark is facing up, and then attach the E53COV17 Terminal Cover to the holes on the top and bottom of the
Digital Temperature Controller.
E53-COV17
E53-COV23
Adapter
Individual
Mounting
Group Mounting
Terminal Cover
(E53-COV17)
(Sold separately)
Enlarged illustration of
Terminal Section
E5EC/E5AC/E5EC-T/E5AC-T
Slightly bend the E53-COV24 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.
Slightly bend the
E53-COV24 Terminal
Cover in the direction
shown by the arrows to
attach it to the terminal block.
Enlarged illustration of the terminal part
108
E5@C/E5@C-T
Attaching the End Cover
E5DC
4. Secure the End Cover so that the double-sided tape is firmly
attached.
1. Install the E5DC in a panel.
2. Peel off the release paper from the double-sided tape on the End
Cover.
Double-sided tape
Removing the Digital Temperature Controller from the
case
E5GC
You can use the Y92F-55 Draw-out Jig to remove the interior body of
the Digital Temperature Controller from the case to perform
maintenance without removing the terminal wiring. This is possible
only for the E5GC. It is NOT possible for the E5CC, E5CC-U, E5EC,
E5AC, E5DC, or E5@C-T. Check the specifications of the case and
Digital Temperature Controller before removing the Digital
Temperature Controller from the case.
Draw-out Jig
insertion hole
Panel
3. Align the tabs on the End Cover with the depressions on the E5DC
and attach the End Cover.
Mounting Adapter
Y92F-55
Draw-out Jig
Hook
1
3
1
Draw-out Jig
insertion hole
2
Hook
1. Insert the Y92F-55 Draw-out Jig securely into the Draw-out Jig
insertion holes (one hole each on the top and bottom) and press it
in firmly until the hooks engage on the top and bottom.
2. Pull out the Y92F-55 Draw-out Jig together with the front panel.
Do not apply unnecessary force.
3. When inserting the body of the Temperature Controller into the
case, make sure the PCBs are parallel to each other, make sure
that the sealing rubber is in place, and press the E5GC toward the
rear case into position. While pushing the E5GC into place, push
down on the hooks on the top and bottom surfaces of the rear case
so that the hooks are securely locked in place. Be sure that
electronic components do not come into contact with the case.
Sealing rubber
PCBs
Keep the PCBs parallel to
each other and inset them
into the rear case.
Right Side View of the E5GC
109
E5@C/E5@C-T
● Precautions when Wiring
• Separate input leads and power lines in order to prevent external
noise.
• Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205
to 0.8231 mm2) twisted-pair cable. Use a shielded, AWG24 to
AWG14 (cross-sectional area of 0.205 to 2.081 mm2) twisted-pair
cable for the E5CC-U. The stripping length is 6 to 8 mm for the
E5CC, E5EC, E5AC, E5DC, or E5CC-T and 5 to 6 mm for the
E5CC-U.
The E5GC stripping length is 6 to 8 mm for models with screw
terminal blocks and 8 to 12 mm for models with screwless clamp
terminal blocks.
• Use crimp terminals when wiring the terminals.
• Use the suitable wiring material and crimp tools for crimp terminals.
• Tighten the terminal screws to a torque of 0.43 to 0.58 N·m.
The specified torque is 0.5 N·m for the E5CC-U.
• For the E5GC, E5CC, E5EC, E5AC, E5DC, or E5@C-T, use the
following types of crimp terminals for M3 screws.
• For E5GC Controllers with screwless clamp terminal blocks, use
braided or solid wires with a gauge of AWG24 to AWG18 (equal to
a cross-sectional area of 0.205 to 0.823 mm2).
The length of the conductive portion inserted into the terminal must
be 8 to 12 mm. Ferrules must be 0.8 to 1.4 mm in diameter..
0.8 to 1.4 mm
8 to 12 mm
Ferrules
• For the E5CC-U, use the following types of crimp terminals for
M3.5 screws.
7.2 mm max.
7.2 mm max.
Three-year Guarantee
● Period of Guarantee
The guarantee period of the Unit is three years starting from the date
the Unit is shipped from the factory.
Scope of Guarantee
The Unit is guaranteed under the
following operating conditions.
Top
1. Average Operating Temperature
(see note): −10°C to 50°C
2. Mounting Method: Standard mounting
Bottom
Note: Average Operating Temperature
Refer to the process temperature
of the Unit mounted to a control
panel and connected to peripheral
devices on condition that the Unit
is in stable operation, sensor input
type K is selected for the Unit, the
positive and negative thermocouple input terminals of the Unit
are short-circuited, and the ambient temperature is stable.
Should the Unit malfunction during the guarantee period, OMRON
shall repair the Unit or replace any parts of the Unit at the expense of
OMRON.
110
wires
• Recommended Ferrules for E5GC Screwless Clamp Terminals
Manufacturer
Altech Corp.
Model number
2623.0
Daido Solderless Terminal Mfg. Co.
AVA-0.5
J.S.T. Mfg. Co.
TUB-0.5
5.8 mm max.
5.8 mm max.
8 to 12 mm
Single (1 wire)
TGNTC-1.25-9T
TGVTC-1.25-11T
TGNTC-1.25-11T
TC0.3-9.5
TC1.25-11S-ST
TC1.25-11S
TC2-11S
Double (2 wires)
TGWVTC-1.25-9T
TGWVTC-1.25-11T
Nichifu Co.
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2011-2014 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. H177-E1-07
0314 (1111)