Bel LDX-D20 Active oring controller Datasheet

LDX-D20 is a Universal Active ORing Controller used for redundant
connection of two DIN rail DC power supplies of same rating, with any
voltage in the range 12 – 85 VDC and Load Current ≤ 20 A.

Ultra Compact Redundancy Module

Wide input voltage range: 12 – 85 VDC (on a single model)

Out: 20 A Max

Extremely low loss up to 99% efficiency

Pluggable connectors

Hot pluggable

Up to 70°C operating temperature with no derating
LDX-D20
2
Input DC Voltage Range
12 - 85 VDC
Maximum Input Current
20 A
Output DC Voltage Range
12 - 85 VDC
Maximum Continuous Output
Current
20 A
Peak Output Current
> 100 A
Conduction Resistance
< 9 mΩ
Maximum Dissipated Power
<4W
No Load Input Power
< 0.2 W
IN1 OK green LED
IN2 OK green LED
Redundancy IN1OK & IN2OK simultaneously
Dry contact (1 A / 30 V)
Overvoltage
Reverse polarity connection
Status Signals
Input Protection
Operating Temperature
≥ 100 V
No derating
- 40°C to 70°C
Storage Temperature
Humidity
- 40°C to +80°C
Non-condensing
5 - 95% r.H.
Overvoltage Category
Pollution Degree
III
2 (IEC664-1)
Insulation Enclosure To Live Parts
0.75 kVDC
UL508 (reference)
EN60950 (reference)
EN55022:2010 (CISPR22)
EN55011:2009 /A1:2010
EN61000-4-2:2008
EN61000-4-3:2006 /A2:2010
EN61000-4-4:2012
EN61000-4-5:2014
EN61000-4-11:2004 /A1:2010
Class A
Class A
Level 3
Level 3
Level 3
Level 1
Level 2
Protection Degree
EN60529:1989 /A:2013
IP20
Vibration Sinuosoidal
IEC 60068-2-6:2007
Shock
IEC 60068-2-27:2008
Safety Standards
Emission
EMC
Immunity
5-17.8 Hz: ±1.6 mm; 17.8-500 Hz:
2g 2 Hours / axis (X,Y,Z)
30 g 6 ms, 20g 11ms; 3 bumps / direction,
18 bumps total
NOTES:



Technical parameters are typical, measured in laboratory environment at 25°C and 240 VDC.
Power rating, losses, efficiency, ripple, thermal behaviour and start-up may change outside of the nominal rated input range.
Contact factory for details.
Data may change without prior notice in order to improve the product.
Weight
250 g
Dimensions
35 x 103 x 104 mm
Mounting Rail
IEC 60715/H15/TH35-7.5(-15)
IN / OUT Connectors
Pluggable screw type (24 – 12 AWG), 6 poles
2.5 mm²
Dry Contact Connector
Pluggable screw type (24 – 12 AWG), 2 poles
2.5 mm²
Case Material
Aluminum
[email protected]
LDX-D20
3
Figure 1. Mechanical Drawing
INPUT CONNECTION


IN1 (+/-) = connect DC (+/-) power supply
IN2 (+/-) = connect DC (+/-) power supply
OUTPUT CONNECTION


OUT (+/-) = connect DC (+/-) Load
Dry contact = NC
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
Europe, Middle East
+353 61 225 977
North America
+1 408 785 5200
© 2016 Bel Power Solutions & Protection
BCD.00859_AA
Asia-Pacific
+86 755 298 85888
Similar pages