OMRON 61F-GP-N8H

Conductive Level Controller
61F-GP-N8
Compact Plug-in Level Controllers for Single
or Two-point Level Control of Conductive
Materials (Liquids and Solids)
Level
Controllers
• Wide range of models: long-distance, high and low-sensitivity,
and two-wired types available.
• 24/100/110/120/200/220/230/240 VAC operation possible.
• Easy installation on DIN track.
• Low-voltage (AC) electrodes.
• Red LED operation indicator provided.
• Conforms to EMC and LVD Directives.
• UL/CSA approved.
Model Number Structure
■ Model Number Legend
61F-GP-N8@
1
2
3
1. Plug-in Type
2. Compact 8-pin Type
3. Applications
None: General-purpose type
L:
Long-distance type
H:
High-sensitivity type (reverse acting)
HY: High-sensitivity type (standard acting)
D:
Low-sensitivity type
R:
Two-wired type
Ordering Information
■ List of Models
Application
General-purpose type
Long-distance type
High-sensitivity type
Model number
61F-GP-N8
2 km
61F-GP-N8L 2KM
4 km
61F-GP-N8L 4KM
61F-GP-N8H
Low-sensitivity type
61F-GP-N8D
Two-wired type
61F-GP-N8R
Conductive Level Controller
61F-GP-N8
E-5
■ Accessories (Order Separately)
Selection Guide for Electrode Holders and Separators
Electrode Holders
Applications
For city water and other
general-use electrodes.
Easy-to-replace separate versions facilitate
maintenance of electrodes.
When mounting space is
limited. Special 3-pole
holder of small size and
light weight. Ideal for soft
drink vendors, etc., where
only limited space is available.
For low specific liquids. Used for sewage,
sea water, etc., having a low specific resistance. In sewage use, electrode holders
must be installed 10 to 20 cm apart from
one another. For acids, alkalis and sea water, electrode holders may be as much as
1 meter apart to operate properly.
When resistance to high
pressure is required. Ideal for use in tanks where
temperature or pressure
inside the tank is high,
e.g. 250°C
Mounting style
Flange
Screw
Flange
Screw
Insulator material
Phenol resin
Phenol resin
Ceramics
Teflon
Max. temperature
70°C
No. of
electrodes
1
---
---
BF-1
BS-1
3
PS-3S
PS-31
---
---
150°C (without water drips or vapor on the 250°C (without water
surface of the electrode holder)
drips or vapor on the surface of the electrode
holder)
Electrode Separators
No. of electrodes
Model
1
F03-14 1P
3
F03-14 3P
Selection Guide for Electrodes, Connecting, and Lock Nuts
Applicable liquids
Material
Models for individual electrode assembly components
Electrode (1m long)
Model
Indication
mark
Connecting nut
Model
Inscription
Lock nut
Model
Inscription
Purified city water,
industrial water,
sewage
Equivalent
to SUS 304
(AISI-304)
F03-01 SUS201
1 line
F03-02 SUS201
---
F03-03 SUS201
---
Purified city water,
industrial water,
sewage, dilute
alkaline solution
SUS316
(AISI-316)
F03-01 SUS316
2 lines
F03-02 SUS316
6
F03-03 SUS316
316
E-6
Conductive Level Controller 61F-GP-N8
Specifications
■ Ratings and Characteristics
Model/Items
General-purpose
Controller
61F-GP-N8
Long-distance
Controllers
61F-GP-N8L 2KM
(for 2 km)
61F-GP-N8L 4KM
(for 4 km)
High-sensitivity
Controllers
61F-GP-N8H
61F-GP-N8HY
(see note 1)
Low-sensitivity
Controller
61F-GP-N8D
Two-wired
Controller
61F-GP-N8R
For control of liquids
with high specific resistance such as distilled water
For control of liquids
with low specific resistance such as salt
water, sewage water,
acid chemicals, alkali
chemicals
For control of ordinary
purified water or sewage water used in
combination with twowired-type electrode
holder (incorporating
a resistor of 6.8 kΩ)
For control of ordinary For control of ordinary
purified water or sew- purified water in casage water
es where the distance
between sewage
pumps and water
tanks or between receiver tanks and supply tanks is long or
where remote control
is required.
Supply voltage
24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
Operating voltage range
85% to 110% of rated voltage
Interelectrode voltage
8 VAC
24 VAC
8 VAC
Interelectrode current
Approx. 1 mA AC max.
Approx.
0.4 mA AC max.
Approx. 1 mA AC max.
Power consumption
Approx. 3.5 VA max.
Interelectrode operate
resistance
Approx. 0 to 4 kΩ
Approx. 0 to 1.3 kΩ
(for 2 km)
Approx. 0 to 0.5 kΩ
(for 4 km)
Approx. 15 kΩ to
70 kΩ
(see note 3)
Approx. 0 to 1.3 kΩ
Interelectrode release
resistance
Approx. 15 k to ∞ Ω
Approx. 4 k to ∞ Ω (for Approx. 300 k to ∞ Ω Approx. 4 k to ∞ Ω
2 km)
Approx. 2.5 k to ∞ Ω
(for 4 km)
Approx. 15 k to ∞ Ω
Response time
Operate: 80 ms max.
Release: 160 ms max.
Cable length
(see note 2)
1 km max.
2 km max.
4 km max.
800 m max.
Control output
1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
Ambient temperature
Operating: −10°C to 55°C
Ambient humidity
Operating: 45% to 85% RH
Insulation resistance
(see note 3)
100 MΩ max. (at 500 VDC)
Dielectric strength
(see note 4)
2000 VAC, 50/60 Hz for 1 min.
Life expectancy
Electrical:
100,000 operations min.
Mechanical: 5,000,000 operations min.
50 m max.
1 km max.
Level
Controllers
Controlling materials and
operating conditions
Approx. 0 to 2 kΩ
Note: 1. The relay in the 61F-GP-N8H de-energizes when there is water present across the electrodes, whereas the relay in the 61F-GP-N8HY
energizes when there is water present across the electrodes.
2. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtyre cables. Usable cable lengths will become shorter
as the cable diameter or number of conductors becomes larger.
3. The insulation resistance and dielectric strength indicate values between power terminals and electrode terminals, between power terminals and contact terminals, and between electrode terminals and contact terminals.
4. Possible to use with 10 kΩ or less, however, this may cause reset failure.
Conductive Level Controller
61F-GP-N8
E-7
Connections
■ Internal Circuit Diagrams
61F-GP-N8/-N8L/-N8D/-N8HY
Power
supply
61F-GP-N8R
61F-GP-N8H
Power
supply
24 V
Power
supply
24 V
24 V
Control circuit
Control circuit
Control circuit
8V
24 V
8 V (see note)
2
Note: 24 V for the 61F-GP-N8HY.
■ Automatic Water Supply and Drainage Control
1. Water Supply
• Connect electromagnetic switch coil terminal A to terminal 2.
• The pump stops when the water level reaches E1 and starts when
the water level drops below E2.
200-VAC power supply
2. Drainage
• Connect the electromagnetic switch coil terminal A to terminal 3.
• The pump starts when the water level reaches E1 and stops when
the water level drops below E2.
61F-GP-N8
MCCB
0V
200 V
8V
24 V Control circuit
(See note 1
below.)
Contactor (See note 2
below.)
PS-3S
Stop
Start
THR
Tank
Reservoir
Note: 1. The diagram shows the connections for water supply. When draining, change the connection from terminal 2 to terminal 3.
2. The earth terminal must be earthed.
E-8
Conductive Level Controller 61F-GP-N8
Operation
The Conductive Level Controller consists of a plug-in controller connected to a set of stainless steel probes. These are cut to length and
inserted vertically into the liquid. A low voltage is applied between
these probes and the earth probe (or tank, if it is electrically conductive). The water provides a current between the earth probe and the
high-level probe. The output relay in the Controller is energized when
the water level reaches the high-level probe and de-energized when
the water level falls below it.
For two-point control a low-level probe is used as well. In this case
the relay does not de-energize until the water level falls below the
low-level probe. Using the low-level probe allows a wide differential
between switching a pump on and off, and can avoid excessive pump
operation during tank emptying or filling. If this differential is not
required, the low-level probe need not be connected.
Surge Suppressor Unit (61F-03B/04B)
A high-capacity protective device is available which protects 61Fseries Floatless Level Controllers against faults arising from electrical surges (such as indirect strokes of lightning) when the Controllers
are employed in elevated water tanks or in high-altitude locations.
3. When connecting the Surge Suppressor Unit, wire as shown in
the following example (with three electrodes).
Discharge start voltage
90 V ±20 VDC
Impulse withstand voltage
200,000 V (1 x 40 µs)
Impulse withstand current
6,000 A (1 x 40 µs)
61F-03B
Ground
Internal Connections
Ground
61F-04B
61F-03B
Level
Controllers
Specifications
E2
E1
E3
Connection Sockets
PF113A-E Track-mounted Socket
PL11 Back-connecting Socket
Precautions
1. Mount the Surge Suppressor Unit as close to the Controller as
possible.
2. When grounding the Surge Suppressor Unit in the vicinity of the
Controller, connect the ground side of the Surge Suppressor Unit
to electrode E3.
Long distance
61F-03B
Ground
Conductive Level Controller
61F-GP-N8
E-9
Dimensions
Note: All units are in millimeters unless otherwise indicated.
61F-GPN8
91
PF083A-E
Electrode Holders
PS-@S
9-dia. rubber
bushing (inner)
PF2 parallel thread
(effective dia.: 58.135)
PS-3S/-3SR
PS-4S/-4SR
PS-5S/-5SR
34 dia.
E2
92
80
E1
26
E2
E3
E1
E1
E4
E4
E3
13
40
E2
E3
80
20
Mounting Holes
Screw Holes
Used with coupling
PF2
Used with mounting bracket
65-dia. hole
PS-31
PF1/2 Parallel thread
38.5
32
7 12
11
11 dia.
Mounting Holes
4 dia.
Electrode
SUS304
Dust preventive rubber cap (optional)
3
M3
PF1/2
Rubber
packing
26
(see note)
29.5 dia.
Note: Standard holder construction includes three integral 300-mm-long electrodes. However, a model having 1,000-mm-long electrodes is available
on request.
BF-1
Cast iron
Two M5 x 25
mounting
screws
Terminal bolt
SUS201 (M6)
Nut (M6)
60
26-dia. hole
48
33
48 dia.
20 dia.
Two, 6-dia. holes
17
14
(49)
72
E-10
Conductive Level Controller 61F-GP-N8
18
23
BS-1
Width across flats: 20 Two M4
Terminal bolt
P = 0.7
M18
SUS304 (M4) P=0.7
P = 1.5
24 dia.
Nut (iron)
12
50
M18 P=1.5
(fine screw thread)
39
51
101
Electrode Separators
F03-14 1P (for Single Pole)
F03-14 3P (for Three Poles)
6.5 dia.
Three, 7 dia.
Level
Controllers
20
41 dia.
28 dia.
Connecting Sockets
Track Mounted Socket
PF083A-E
Eight, M3.5 x 7
sems screws
Terminal Arrangement/
Internal Connections
(Top View)
7±0.2
Two, 4.2-dia.
holes
52 max.
Mounting Holes
25 dia.
Two, M4 or 4.5-dia. holes
21 max.
41 max.
Back Connecting Socket
PL08
Terminal arrangement/
Internal Connections
(Bottom View)
Two, 2-dia. holes
50.5 max.
Mounting Holes
Two, 3.5-dia. or
M3 Controller
mounting holes
Two, 3.5-dia. or M3
socket mounting holes
30 dia.
31-dia.
hole
35 max.
Approx. 20.5
Conductive Level Controller
61F-GP-N8
E-11
Holding Brackets
To mount the 61F-GP-N8 Conductive Level Controller on the
PF083A Track Mounted Socket, use the PFC-N8 Mounting Brackets
attached to the Socket as an accessory.
PFC-N8
Approx.
80
Surge Suppressor Unit
61F-03B
61F-04B
61F-03B
61F-04B
PF113A-E
Application Examples
• Level control in tanks, reservoirs, sewage plants, underground
wells, mixing plants etc.
• Level control for element protection in pipes, channels, and irrigation systems.
• Flow detection in pipes, channels, and irrigation systems.
• Ice bank control in cold drink dispensers, ice makers, water chillers,
bulk milk tanks, etc.
•
•
•
•
Dispensing of liquids by volume.
Indication of liquid buildup due to filter blockages.
Pollution/foul water detection for rivers, drains, etc.
Alarm control warning of abnormal or dangerously high or low levels.
■ Application
When using electrodes in sea water or sewage, provide a sufficient
interval (normally 1 m) between the electrodes. If the sufficient interval cannot be provided, employ a low-sensitivity-type Floatless Level
Controller.
E1
When taping one of the electrodes to prevent it from contacting the
other electrodes in water, do not tape the electrode entirely but leave
at least 100 mm of its end uncovered.
When the required length of the electrode is more than 1 m, use a
separator at each joint of two electrodes so as to prevent the electrodes from contacting one another.
Note: Avoid use of the separators in dust-containing liquids.
Usually, electrodes are used in a set of three: long, medium, and
short. Connect the short electrode to E1, the medium electrode to
E2, and the long electrode to E3. Make E3 at least 50 mm longer
than E2.
E-12
Conductive Level Controller 61F-GP-N8
E2
E3
1m
Min
50 mm
1m
Electrodes are in actual contact with the liquid. Standard electrodes
are made of stainless steel and usable in purified water, sea water,
sewage, acid (except acetic acid, sulfuric acid, etc.) and alkaline liquids, although they may corrode depending upon the temperature
and working conditions.
Note that the 61F-GP-N8 Conductive Level Controller is capable of
controlling liquids with specific resistances of up to 30 kΩ-cm when
the Controller employs a PS-3S electrode holder with the electrode(s) submerged to a depth of 30 mm max.
Kind of water
Specific resistance
Applicable type
City water
5 to 10 kΩ-cm
Standard type
Well water
2 to 5 kΩ-cm
Standard type
Industrial water
5 to 15 kΩ-cm
Standard type
Rainwater
15 to 25 kΩ-cm
Standard type
Sea water
0.03 kΩ-cm
Low-sensitivity type
Sewage
0.5 to 2 kΩ-cm
Low-sensitivity type
Distilled water
100 kΩ-cm or less
High-sensitivity type
Over 100 kΩ-cm
Consult OMRON
Precautions
Level
Controllers
■ How to Mount Electrodes
Connecting Electrodes to Electrode Holders
Electrode holder
Clamp screw
3. Tighten the electrode with
the two clamp screws.
Connecting nut
1. Spin a lock nut and a spring
washer onto the electrode.
Spring washer
4. Secure the connecting
nut by tightening the lock
nut and spring washer.
Lock nut
Electrode
2. Fully fit the electrode into the
connecting nut attached to the
electrode holder.
Connecting One Electrode to Another
Electrode
Lock nut
Spring washer
Connecting nut
Spring
washer
2. Fully fit the
electrode into the
connecting nut
attached to the
electrode holder.
3. Tighten the electrode with
the two clamp screws.
4. Secure the connecting
nut by tightening the lock
nut and spring washer.
1. Spin a lock nut and a spring
washer onto the electrode.
Conductive Level Controller
61F-GP-N8
E-13
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. F043-E1-02
E-14
In the interest of product improvement, specifications are subject to change without notice.
Conductive Level Controller 61F-GP-N8