Panasonic APF3318 Compliant with european standards 1a/1c 6a slim power relay Datasheet

PF (APF)
VDE
Compliant with
European standards
1a/1c 6A Slim power relays
RoHS compliant
PF RELAYS (APF)
FEATURES
TYPICAL APPLICATIONS
1. High density mounting with 5 mm
.197 inch width
Space saved with 5 mm .197 inch slim
type with 28 mm 1.102 inch length.
Allows high density mounting and use in
compact devices.
2. Satisfies reinforced insulation
standard (EN/IEC 61810-1).
3. High switching capacity
Supports 6A 250 V AC nominal switching
capacity (resistive load) and AC15 and
DC13 (inductive load).
4. 1 Form A and 1 Form C contact
arrangements with options for a
variety of applications.
5. 4,000 V high breakdown voltage and
6,000 V high surge breakdown voltage.
Controller protection against surges and
noise with a breakdown voltage of 4,000
Vrms for 1 min. between contacts and
coil, and 6,000 V surge breakdown
voltage between contacts and coil.
6. Resistance to heat and fire;
EN60335-1, clause 30 (GWT)
approved.
7. Sealed construction allows
automatic washing.
8. Complies with all safety standards.
UL/C-UL, VDE certified.
1. Interface relays for programmable
controllers
2. Output relays for measuring
equipment, timers, counters and
temperature controllers
3. Industrial equipment, office
equipment
4. Household appliances for Europe
ORDERING INFORMATION
APF
0
Contact arrangement
1: 1 Form A
3: 1 Form C
Contact type
0: Single contact
Contact material
2: AgNi type
3: AgNi type/Au-plated
Nominal coil voltage (DC)
4H: 4.5 V 05: 5 V 06: 6 V 09: 9 V 12: 12 V 18: 18 V
24: 24 V 48: 48 V 60: 60 V
Note: Certified by UL/C-UL and VDE
ASCTB205E 201202-T
Panasonic Corporation
Automation Controls Business Unit
industrial.panasonic.com/ac/e/
PF (APF)
TYPES
Contact arrangement
Nominal coil voltage
Part No.
1 Form A
(AgNi type)
4.5V DC
5V DC
6V DC
9V DC
12V DC
18V DC
24V DC
48V DC
60V DC
APF1024H
APF10205
APF10206
APF10209
APF10212
APF10218
APF10224
APF10248
APF10260
1 Form A
(AgNi type/Au-plated)
4.5V DC
5V DC
6V DC
9V DC
12V DC
18V DC
24V DC
48V DC
60V DC
APF1034H
APF10305
APF10306
APF10309
APF10312
APF10318
APF10324
APF10348
APF10360
Contact arrangement
Nominal coil voltage
Part No.
1 Form C
(AgNi type)
4.5V DC
5V DC
6V DC
9V DC
12V DC
18V DC
24V DC
48V DC
60V DC
APF3024H
APF30205
APF30206
APF30209
APF30212
APF30218
APF30224
APF30248
APF30260
1 Form C
(AgNi type/Au-plated)
4.5V DC
5V DC
6V DC
9V DC
12V DC
18V DC
24V DC
48V DC
60V DC
APF3034H
APF30305
APF30306
APF30309
APF30312
APF30318
APF30324
APF30348
APF30360
Standard packing: Tube: 20 pcs.; Case: 1,000 pcs.
RATING
1. Coil data
4.5V DC
Nominal operating
current
[±10%] (at 20°C 68°F)
37.8mA
5V DC
6V DC
9V DC
12V DC
18V DC
24V DC
48V DC
60V DC
34.0mA
28.3mA
18.9mA
14.2mA
9.4mA
7.1mA
4.5mA
2.9mA
Nominal coil
voltage
Pick-up voltage
(at 20°C 68°F)
Max. 70%V
nominal voltage
(Initial)
Panasonic Corporation
Drop-out voltage
(at 20°C 68°F)
Min. 5%V
nominal voltage
(Initial)
Automation Controls Business Unit
Coil resistance
[±10%] (at 20°C 68°F)
Nominal operating
power
Max. applied voltage
(at 20°C 68°F)
119Ω
147Ω
212Ω
476Ω
847Ω
1,906Ω
3,388Ω
10,618Ω
20,570Ω
170mW
120%V of
nominal voltage
217mW
175mW
industrial.panasonic.com/ac/e/
ASCTB205E 201202-T
PF (APF)
2. Specifications
Characteristic
Contact
Rating
Item
Arrangement
Contact resistance (Initial)
Contact material
Nominal switching capacity (resistive load)
Max. switching power (resistive load)
Max. switching voltage
Max. switching current
Nominal operating power
Min. switching capacity (Reference value)*1
Specifications
1 Form A
1 Form C
Max. 100 mΩ (By voltage drop 6 V DC 1A)
AgNi type, AgNi type/Au-plated
6 A 250 V AC
1,500 VA
250V AC
6 A (AC)
170 mW (5 to 24 V DC), 217 mW (48 V DC), 175 mW (60 V DC)
100 mA 5 V DC (without Au-plated), 1 mA 1 V DC (with Au-plated)
Min. 1,000MΩ (at 500V DC)
Measurement at same location as “Breakdown voltage” section.
Insulation resistance (Initial)
Between open contacts
Between contact and coil
Surge breakdown voltage*2
(Between contact and coil) (Initial)
Breakdown voltage
(Initial)
Electrical
characteristics
Temperature rise (coil) (at 20°C 68°F)
Operate time (at 20°C 68°F)
Release time (at 20°C 68°F)
Shock resistance
Mechanical
characteristics
Expected life
Conditions
Functional
Destructive
Functional
Vibration resistance
Destructive
Mechanical
Electrical*4
Conditions for operation, transport and storage*3
Unit weight
1,000 Vrms for 1 min. (Detection current: 10 mA)
4,000 Vrms for 1 min. (Detection current: 10 mA)
6,000 V
Max. 45°C 113°F
(By resistive method, nominal coil voltage applied to the coil; contact carrying current: 6A.)
Max. 8 ms
(Nominal coil voltage applied to the coil, excluding contact bounce time.)
Max. 4 ms
(Nominal coil voltage applied to the coil, excluding contact bounce time.) (without diode)
Min. 49 m/s2
Min. 98 m/s2
(Half-wave pulse of sine wave: 11 ms;
(Half-wave pulse of sine wave: 11 ms;
detection time: 10µs)
detection time: 10µs)
Min. 980 m/s2 (Half-wave pulse of sine wave: 11 ms.)
10 to 55 Hz at double amplitude of 1 mm (Detection time: 10µs.)
10 to 55 Hz at double amplitude of 1.5 mm
Min. 5×106 (at 180 times/min.)
N.O.: Min. 5×104
N.O.: Min. 5×104, N.C.: Min. 3×104
(at resistive load, 6 times/min. and
(at resistive load, 6 times/min. and
nominal switching capacity)
nominal switching capacity)
Ambient temperature: –40°C to +85°C –40°F to +185°F;
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature)
Approx. 5 g .18 oz
Notes: *1. This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the
actual load.
*2. Wave is standard shock voltage of ±1.2×50µs according to JEC-212-1981
*3. The upper operation ambient temperature limit is the maximum temperature that can satisfy the coil temperature rise value. Refer to “Usage, transport and storage
conditions” in NOTES.
*4. For cycle lifetime, refer to “Cautions for use 4)” in NOTES.
ASCTB205E 201202-T
Panasonic Corporation
Automation Controls Business Unit
industrial.panasonic.com/ac/e/
PF (APF)
REFERENCE DATA
1. Electrical life
Tested sample: APF30224
Load type
Resistive load
AC 15
Inductive load
DC 13
Voltage
250V AC
250V AC
24V DC
Current
6A
3A
2A
Ambient temperature
85°C 185°F
25°C 77°F
25°C 77°F
No. of ops.
30,000
20,000
6,000
Notes: 1. Switch contacts are all on N.O. side.
2. AC 15 and DC 13 comply with IEC-60947-5-1 testing conditions.
4. Ambient temperature characteristics
Tested sample: APF30224
Measured portion: Inside the coil
Ambient temperature: 28°C 82°F
Tested sample: APF30224, 6 pcs.
10
90
6
5
4
3
80
2
1
0.5
0.4
0.3
Rate of
change, %
3. Coil temperature rise
Temperature rise, °C
Contact current, A
2. Max. switching capacity (AC)
6A
0A
70
60
50
-40
40
-20
DIMENSIONS (mm inch)
Drop-out
voltage
-5
40 60 85
Ambient
temperature,
°C
-10
-15
10
10 20 30 50 100 250
Contact voltage, V
Pick-up voltage
10
0
20
0
30
0
15
5
20
0.2
20
90
100
110
120
130
Coil applied voltage, %V
The CAD data of the products with a
CAD Data
-20
140
mark can be downloaded from: http://industrial.panasonic.com/ac/e/
1. 1 Form A type
External dimensions
PC board pattern (Bottom view)
15.0max.
.591max.
0.5
.020
0.4 +0.2
−0.1
.016 +.008
−.004
1.2
.047
−0.1
2-0.6 +0.2
2-.024 +.008
−.004
3.78
.149
2-1.0
2-.039
5.04
.198
1.9
.075
21.42
.843
28.0max.
1.102max.
0.48 +0.2
−0.1
.019 +.008
−.004
1.2
.047
3.5±0.5 5.0max.
.138±.020 .197max.
3.78
.149
2-1
.
2-. 3 dia
05 .
1d
ia.
2-1
.
2-.0 0 dia.
39
dia
.
CAD Data
21.42
.843
5.04
.198
1.2
.047
1.9
.075
Tolerance: ±0.1 ±.004
Schematic (Bottom view)
COIL
COM
NO
General tolerance: ±0.3 ±.012
2. 1 Form C type
2-1
.
2-.0 0 dia.
39
dia
.
15.0max.
.591max.
0.5
.020
0.4 +0.2
−0.1
.016 +.008
−.004
1.2
.047
+0.2
−0.1
+.008
−.004
2-0.6
2-.024
3.78
.149
+0.2
0.48 +.008
−0.1
.019 −.004
1.2
.047
3-1.0
3-.039
5.04
.198
1.9
.075
3.5±0.5 5.0max.
.138±.020 .197max.
5.04
21.42
.198
.843
28.0max.
1.102max.
3-1
.
3-. 3 dia
05 .
1d
ia.
PC board pattern (Bottom view)
External dimensions
CAD Data
1.2
.047
5.04 5.04
21.42 .198 .198
.843
3.78
.149
1.9
.075
Tolerance: ±0.1 ±.004
Schematic (Bottom view)
COIL
NC
COM
NO
General tolerance: ±0.3 ±.012
Panasonic Corporation
Automation Controls Business Unit
industrial.panasonic.com/ac/e/
ASCTB205E 201202-T
PF (APF)
SAFETY STANDARDS
Certification
authority
File No.
UL/C-UL
E120782
VDE
40027672
Applicable standard
Rating
Remarks
277V AC 8A, General use,
UL508, CSA C22.2 No.14
24V DC 6A, General use,
UL1604 (class I, Division 2, Group A, B, C, D)
B300, R300 (Pilot Duty)
250V AC 6A (cosφ = 1.0) 85°C 185°F
N.O. side, N.C. side
EN/IEC 61810-1
250V AC 8A (cosφ = 1.0) 25°C 77°F
N.O. side
Insulation: Reinforced insulation between contact
and coil.
Resistance to heat and fire; EN60335-1, clause
30 (GWT) approved.
NOTES
Usage, transport and storage
conditions
1) Temperature:
–40 to +85°C –40 to +185°F
2) Humidity: 5 to 85% RH
(Avoid freezing and condensation.)
The humidity range varies with the
temperature. Use within the range
indicated in the graph below.
3) Atmospheric pressure: 86 to 106 kPa
Temperature and humidity range for
usage, transport, and storage
Humidity, %RH
85
Tolerance range
(Avoid freezing
when used at
temperatures
lower than
0°C 32°F)
5
–40
–40
(Avoid
condensation
when used at
temperatures
higher than
0°C 32°F)
0
+32
Temperature, °C °F
85
+185
4) Condensation
Condensation forms when there is a
sudden change in temperature under
high temperature and high humidity
conditions. Condensation will cause
deterioration of the relay insulation.
5) Freezing
Condensation or other moisture may
freeze on the relay when the
temperatures is lower than 0°C 32°F. This
causes problems such as sticking of
movable parts or operational time lags.
6) Low temperature, low humidity
environments
The plastic becomes brittle if the relay is
exposed to a low temperature, low
humidity environment for long periods of
time.
For Cautions for Use.
ASCTB205E 201202-T
Panasonic Corporation
Automation Controls Business Unit
industrial.panasonic.com/ac/e/
Similar pages