EPCOS B84142A0100R123

EMC filters
2-line filters
for converters and power electronics
Rated current 12 to 100 A
Series/Type:
B84142A*R123
Date:
January 2006
 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
2-line filters
B84142A*R123
for converters and power electronics
Power line filters for 1-phase systems
Rated voltage 520 V DC/AC, 50/60 Hz
Rated current 12 to 100 A
Construction
■ 2-line filters
■ Metal case
Features
■
■
■
■
■
High insertion loss
Optimized leakage current
Easy to install
Space-saving design
Low weight
Applications
■ Power supplies
■ DC applications
Terminals
■ Finger-safe terminal blocks
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, rated temperature,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Typical circuit diagram
LINE
L
LOAD
L’
N
N’
SSB2129-F
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
2-line filters
B84142A*R123
for converters and power electronics
Technical data and measuring conditions
Rated voltage VR
520 V DC/AC, 50/60 Hz
Rated current IR
Referred to 70 °C ambient temperature
Test voltage Vtest
2250 V DC, 2 s (line/line)
3000 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current Ileak
At 520 V AC, 50 Hz
Climatic category (IEC 60068-1)
25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Characteristics and ordering codes
VR
AC/DC
V
520
IR
70 °C
A
IR
50 °C
A
Terminal
Ileak
cross section
mm2
mA
12
15
4
< 120
25
32
10
38
48
50
64
75
100
Ordering code
mΩ
Approx.
weight
kg
11.0
2.5
B84142A0012R123
< 120
2.5
3.0
B84142A0025R123
10
< 120
2.4
3.0
B84142A0038R123
35
< 120
1.4
3.5
B84142A0050R123
96
35
< 120
1.2
6.0
B84142A0075R123
128
50
< 120
0.7
8.0
B84142A0100R123
Please read Cautions and warnings and
Important notes at the end of this document.
Rtyp
3
01/06
2-line filters
B84142A*R123
for converters and power electronics
Dimensional drawings
B84142A0012R123 (12 A)
8
200
58
35±0.3
100
5.5
1.5
121.5
PE M6 x 24
L
N
L’
Marking
LINE
LOAD
N’
Terminal blocks 4 mm 2
Tightening torque 0.5 ... 0.6 Nm
257±0.5
265
SSB2205-9-E
B84142A0025R123, B84142A0038R123 (25 and 38 A)
8
200
58
35±0.3
120
5.5
1.5
141.5
PE M6 x 24
L
N
L’
Marking
LINE
LOAD
N’
Terminal blocks 10 mm 2
Tightening torque 1.2 ... 1.5 Nm
257±0.5
265
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2206-H-E
4
01/06
2-line filters
B84142A*R123
for converters and power electronics
B84142A0050R123, B84142A0075R123 (50 and 75 A)
240
80
13
63
135
PE M10 x 34
100
25
46
6.5
N
L’
Marking
LINE
LOAD
60±0.3
L
N’
Terminal blocks 35 mm 2
Tightening torque 3.2 ... 3.7 Nm
255±0.5
290
SSB2207-Q-E
B84142A0100R123 (100 A)
90
73.6
6.5
1
PE M10 x 35
60
86
150
54
326
240
N
L’
Marking
LINE
LOAD
65±0.3
L
N’
255±0.5
270
Terminal blocks 50 mm 2
Tightening torque 6 ... 8 Nm
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2208-Y-E
5
01/06
2-line filters
B84142A*R123
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
Filters for 12 A
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 25 A
SSB2226-W
120
dB B84142A0012R123
α
α
100
80
60
60
40
40
20
20
10 4
10 5
10 6
0
10 3
10 7 Hz 10 8
f
Filters for 38 A
10 6
10 7 Hz 10 8
f
80
60
60
40
40
20
20
10 5
10 6
0
10 3
10 7 Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2229-L
100
80
10 4
10 5
120
dB B84142A0050R123
α
100
0
10 3
10 4
Filters for 50 A
SSB2228-D
120
dB B84142A0038R123
α
100
80
0
10 3
SSB2227-5
120
dB B84142A0025R123
6
01/06
10 4
10 5
10 6
10 7 Hz 10 8
f
2-line filters
B84142A*R123
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
Filters for 75 A
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 100 A
SSB2230-P
120
dB B84142A0075R123
α
α
100
100
80
80
60
60
40
40
20
20
0
10 3
10 4
10 5
10 6
0
10 3
10 7 Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2231-X
120
dB B84142A0100R123
7
01/06
10 4
10 5
10 6
10 7 Hz 10 8
f
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro­
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low­
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■
■
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger­
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen­
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
8
01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1.Some parts of this publication contain statements about the suitability of our products for cer­
tain areas of application. These statements are based on our knowledge of typical requirements
that are often placed on our products in the areas of application concerned. We nevertheless ex­
pressly point out that such statements cannot be regarded as binding statements about the
suitability of our products for a particular customer application. As a rule, EPCOS is either un­
familiar with individual customer applications or less familiar with them than the customers them­
selves. For these reasons, it is always ultimately incumbent on the customer to check and decide
whether an EPCOS product with the properties described in the product specification is suitable for
use in a particular customer application.
2.We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the cur­
rent state of the art, even if they are operated as specified. In customer applications requiring
a very high level of operational safety and especially in customer applications in which the malfunc­
tion or failure of a passive electronic component could endanger human life or health (e.g. in acci­
dent prevention or life-saving systems), it must therefore be ensured by means of suitable design
of the customer application or other action taken by the customer (e.g. installation of protective cir­
cuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunc­
tion or failure of a passive electronic component.
3.The warnings, cautions and product-specific notes must be observed.
4.In order to satisfy certain technical requirements, some of the products described in this pub­
lication may contain substances subject to restrictions in certain jurisdictions (e.g. because
they are classed as “hazardous”). Useful information on this will be found in our Material Data
Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions,
please contact our sales offices.
5.We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product spec­
ifications. Please check therefore to what extent product descriptions and specifications contained
in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently,
we cannot guarantee that all products named in this publication will always be available.
6.Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry” pub­
lished by the German Electrical and Electronics Industry Association (ZVEI).
7.The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap, PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are trademarks
registered or pending in Europe and in other countries. Further information will be found on the
Internet at www.epcos.com/trademarks.
9
01/06