Construction
3−line filter
Metal case
Features
High insertion loss
Low leakage current
Easy to install
Degree of protection IP 20 1)
Space−saving design
Design complies with
IEC / EN 60939, UL 1283, CSA 22.2 No.8
Optimized for long motor cables
and operation under full load
UL and cUL approval
Applications
Frequency converters for motor drives, e.g.
− elevators
− pumps
− traction systems
− conveyor systems
− HVAC systems (heating, ventilation and air conditioning)
Wind farms
Power supplies
Terminals
Finger−save terminal blocks
Marking
Marking on component:
manufacturer’s logo, ordering code, rated voltage, rated current,
rated temperature, climatic category, date code
Minimum marking on packaging: manufacturer’s logo, ordering code,
date code, quantity
1)
To IEC 60529:2001
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 2 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Typical circuit diagram
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
Technical data and measuring conditions
Rated voltage
VR
760/440
V AC
Rated frequency
fR
50/60
Hz
Test voltage line to line for 2 s
Vtest
3270
V DC
Test voltage line to case for 2 s
Vtest
3000
V DC
Rated temperature
TR
40
°C
Overload capability (thermal)
for 3 min per hour or
for 30 s per hour
1.5 x IR
2.5 x IR
leakage current Ileak
at 690
Climatic category (IEC 60068−1)
25/100/21
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 3 of 12
V AC, 50Hz
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Characteristics and ordering codes
IR
Terminal
cross
section
Ileak 2)
Rtyp
Approx.
weight
A
mm2
mA
mΩ
kg
25
10
<7
8.0
4
B84143A0025R021
36
10
<7
3.8
4
50
10
< 12
2.0
80
25
< 12
120
50
150
180
Ordering code
Approvals
600/350V
600/350V
−
x
x
B84143A0036R021
−
x
x
4
B84143A0050R021
−
x
x
1.0
9.5
B84143A0080R021
−
x
x
< 12
0.75
10
B84143A0120R021
−
x
x
50
< 12
0.4
10
B84143A0150R021
−
x
x
95
< 12
0.4
13
B84143A0180R021
−
x
x
X = approval granted
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 4 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Marking
4 x M6 / 6mm deep
Dimensional drawings
B84143A0025R021; B84143A0050R021
all dimensions in mm
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 5 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Marking
Dimensional drawings
B84143A0080R021
all dimensions in mm
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 6 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Marking
Dimensional drawings
B84143A0120...A0150R021
all dimensions in mm
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 7 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Marking
Dimensional drawings
B84143A0180R021
all dimensions in mm
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 8 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143A0025R021
B84143A0036R021
100
dB
100
dB
80
80
60
60
40
40
20
20
0
104
105
106
107
0
104
Hz 108
105
106
107
f
Hz 108
f
B84143A0050R021; B84143A0080R021
B84143A0120R021
100
dB
100
dB
80
80
60
60
40
40
20
20
0
104
105
106
107
Hz 108
f
Please read and Cautions and warnings and
Important notes at the end of this document.
0
104
105
106
107
Hz 108
f
Page 9 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143A0150R021
B84143A0180R021
100
dB
100
dB
80
80
60
60
40
40
20
20
0
104
105
106
107
Hz 108
f
Please read and Cautions and warnings and
Important notes at the end of this document.
0
104
105
106
107
Hz 108
f
Page 10 of 12
B84143−A25_A180−R21−04−7659
3−line filters
B84143A0025...A0180R021
for converters and power electronics
Caution and warnings
Please note the advices in our data book “EMC Filters” (latest edition); attention should
be paid to the chapter “General safety notes”.
It shall be ensured that only qualified persons (electricity specialists) are engaged on work
such as planning, assembly, installation, operation, repair and maintenance. They must
be provided with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge.
Dangerous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is
installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective−earth connection must be observed.
Impermissible overloading of the EMC filter, such as with circuits able to cause resonances, impermissible voltages at higher frequencies etc. can lead to bodily injury and
death as well as cause substantial material damages (e.g. destruction of the filter housing).
EMC filters must be protected in the application against impermissible exceeding of the
rated currents by overcurrent protective.
In case of leakage currents > 3.5 mA you shall mount the PE conductor stationary with
the required cross section before beginning of operation and save it against disconnecting. For leakage currents IL 4) < 10 mA the PE conductor must have a KU value 3) of 4.5;
for leakage currents IL 10 mA the PE conductor must have a KU value of 6.
3) The KU value (symbol KU) is a classification parameter of safety−referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
A value of KU = 4.5 with respect to interruptions is attained:
− with a permanently connected protective earth circuit 1.5 mm2
− with a protective earth circuit 2.5 mm2 connected via shroud connectors (IEC 60309−2).
KU = 6 with respect to interruptions is achieved for fixed−connection lines 10 mm2 where the type of connection and line layout correspond to the requirements for PEN conductors as specified in relevant standards.
4) IL = leakage current let−go
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 11 of 12
B84143−A25_A180−R21−04−7659
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with
them than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or failure
before the end of their usual service life cannot be completely ruled out in the current state
of the art, even if they are operated as specified. In customer applications requiring a very
high level of operational safety and especially in customer applications in which the malfunction
or failure of an electronic component could endanger human life or health (e.g. in accident
prevention or life-saving systems), it must therefore be ensured by means of suitable design of
the customer application or other action taken by the customer (e.g. installation of protective
circuitry or redundancy) that no injury or damage is sustained by third parties in the event of
malfunction or failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
The aforementioned does not apply in the case of individual agreements deviating from the
foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSMP, CSSP, CTVS, DSSP, MiniBlue,
MKK, MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, SIFERRIT, SIFI, SIKOREL,
SilverCap, SIMDAD, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
12
04/09