EPCOS B84144B0400S120

EMC filters
4-line filters
for converters and power electronics
Rated current 250 A to 600 A
Series/Type: B84144B*120, B84144B*121
Date:
January 2006, April 2009
Data Sheet
© EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet, enclosures
hereto and the information contained therein without EPCOS’ prior express consent is prohibited.
4-line filters
B84144B*S120, S121
for converters and power electronics
Power line filters for 3-phase systems
Rated voltage 530/305 V AC, 50/60 Hz
Rated current 250 to 600 A
Construction
n 4-line filter
n Metal case
n Polyurethane potting (UL 94 V-0)
Features
n
n
n
n
n
Easy to install
Space-saving design
Optimized leakage current
Optimized for operation under full load
Design complies with
EN 133200, UL 1283, CSA C22.2 No.8
n UL and cUL approval
Applications
n
n
n
n
General applications for power electronics
UPS
Wind farms
Industrial applications (textile and packaging machines)
Terminals
n Busbars
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, rated temperature,
rated frequency, climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document.
2
04/09
4-line filters
B84144B*S120, S121
for converters and power electronics
Typical circuit diagram
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
N
N
PE
PE
SSB2220-H
Technical data and measuring conditions
Rated voltage VR
530/305 V AC, 50/60 Hz
Rated current IR
Referred to 40 °C ambient temperature
Test voltage Vtest
2280 V DC, 2 s (line/line)
2740 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current Ileak
At 530 V AC, 50 Hz
Climatic category (IEC 60068-1)
25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Approvals
UL 1283, CSA C22.2 No.8
Characteristics and ordering codes
Ileak
Ordering code
Approvals
μΩ
Approx.
weight
kg
68
15
B84144B0250S120
×
×
<3
59
20
B84144B0400S120
×
×
<3
59
21
B84144B0600S120
×
×
250
<6
68
16
B84144B0250S121
×
×
400
<6
59
22
B84144B0400S121
×
×
600
<6
59
23
B84144B0600S121
×
×
VR
AC
V
A
mA
530/305
250
<3
400
600
IR
Rtyp
High performance
530/305
× = approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
3
04/09
4-line filters
B84144B*S120, S121
for converters and power electronics
Dimensional drawings
B84144B0250S1** (250 A)
390
365±1.5
12.5
83
126
25
12.5
180
135
45
21
ø11
45
PE M10 x 40
301.5
240±0.2
205±0.3
230
5
Marking
LINE LOAD
Marking
ø12
40±3
40±3
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2240-W
4
01/06
4-line filters
B84144B*S120, S121
for converters and power electronics
B84144B0400S1**, B84144B0600S1** (400 and 600 A)
440
410±1.5
15
100
149.5
30
15
210
150
50
29.5
ø11
PE M10 x 40
50
351.5
290±0.2
235±0.3
260
5
Marking
LINE LOAD
Marking
ø12
40±3
40±3
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2241-5
5
01/06
4-line filters
B84144B*S120, S121
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 250 and 400 A (S120)
α
Filters for 600 A (S120)
SSB2242-D
120
dB B84144B0250S120
B84144B0400S120
α
100
80
60
60
40
40
20
20
10 5
10 6
10 7
120
dB B84144B0250S121
B84144B0400S121
0 4
10
Hz 10 8
f
Filters for 250 and 400 A (S121)
α
100
80
0 4
10
SSB2244-U
α
10 7
Hz 10 8
f
60
60
40
40
20
20
10 7
0 4
10
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2245-3
100
80
10 6
10 6
120
dB B84144B0600S121
80
10 5
10 5
Filters for 600 A (S121)
100
0 4
10
SSB2243-L
120
dB B84144B0600S120
6
01/06
10 5
10 6
10 7
Hz 10 8
f
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appropriate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in lowvoltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
n It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
n
n
n
n
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Dangerous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequencies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
Please read Cautions and warnings and
Important notes at the end of this document.
7
01/06
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with
them than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or failure
before the end of their usual service life cannot be completely ruled out in the current state
of the art, even if they are operated as specified. In customer applications requiring a very
high level of operational safety and especially in customer applications in which the malfunction
or failure of an electronic component could endanger human life or health (e.g. in accident
prevention or life-saving systems), it must therefore be ensured by means of suitable design of
the customer application or other action taken by the customer (e.g. installation of protective
circuitry or redundancy) that no injury or damage is sustained by third parties in the event of
malfunction or failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
The aforementioned does not apply in the case of individual agreements deviating from the
foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSMP, CSSP, CTVS, DSSP, MiniBlue,
MKK, MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, SIFERRIT, SIFI, SIKOREL,
SilverCap, SIMDAD, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
8
04/09